Duomo CO200 Скачать руководство пользователя страница 4

Technical Specifications

Power supply

12-24V DC +/- 10% from detector

Electrical input

110mA @ 13.8V

External protection rating

IP55

Working temperature

-10

o

C to 40

o

C

Sensor type

Electrochemical

Detection precision

1% full scale

CE certification

No. 96125

Detection

0 to 300ppm

Response time

< 10 seconds

Interconnecting cable size

1mm csa

Material used for housing

Aluminium

Dimensions

75 x 158 x 58

Function check period

6 months

Guarantee

3 years

Commissioning

It is strongly recommended that this sensor should be commissioned by Duomo Commissioning Engineers or engineers
approved by Duomo to carry out this work. A quotation for commissioning or service will be provided upon request.
Contact our service department by;

Telephone - 01905 797989
Fax - 01905 774296
Email - [email protected]

The benefits of this equipment being commissioned by Duomo are:

The 3 year guarantee period will start from the date of commissioning and not from the date of manufacture
On board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will carry spares
to ensure that the commissioning is successful
A Duomo Commissioning Certificate is provided

It is prudent to make electrical connection to the sensor terminal plug when withdrawn and leave the plug
disconnected from the sensor so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to
be checked prior to commissioning and avoids damage due to incorrect connection. Guarantees for this product will
become void if damage is caused by the installer.

Electrical Installation

If the CO200 Duct is to be used to monitor possible leakage of carbon monoxide in boiler rooms due to
spillage or damaged or unsuitable flue systems, it is advisable to connect the sensor directly to a Duomo gas
control panel. These are safety devices and are designed to give audible alarms and automatically provide
latched electrical isolation of associated gas safety shut off valves.

The CO200 Duct is also suitable for carbon monoxide sensing in car parks and can be connected either to
Duomo gas control panels or to Building Management Systems (BMS). The sensor can be located up to 100m
from the gas detector. Cable size should be 1mm csa. If the sensor cables are run seperately in specific conduit
it is not essential to use screened cable.

However, if the cables are routed through conduit or trunking containing other wiring the use of screened
cable is advisable. The wiring should be performed by a qualified person in accordance with current
regulations. The plug in terminal rail makes installation easy and quick.

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

Duomo (UK) Ltd. 2007

Содержание CO200

Страница 1: ...gas valves sirens or air extract systems Operation The CO200 Duct is a carbon monoxide sensor which provides a linear 4 20mA output The sensor automatically calculates carbon monoxide concentration relative to time Time Weighted Average and will give a 20mA output from terminal 3 should the carbon monoxide levels remain above predetermined levels for extended periods This is useful when carbon mon...

Страница 2: ...he use of gas appliances the ventilation of the environment and the elimination of combustion products in accordance with local recommendations regulations and byelaws For any damage caused to people property or animals resulting from incorrect connection installation or application of this gas detector Duomo will not be held responsible or liable 1600 Replacing Sensor When replacing sensors NEVER...

Страница 3: ...e audible alarm changes from continuous to intermittent the levels of gas have dropped A responsible qualified person is now safe to find the cause of the alarm If the alarm sound remains constant and the cause is not evident or possible to eliminate turn off the emergency isolation valves to the area and contact your gas provider emergency line They will advice accordingly TWA Alarm Reaction Time...

Страница 4: ...thdrawn and leave the plug disconnected from the sensor so that the Duomo Engineer is the first to power up the unit on site This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection Guarantees for this product will become void if damage is caused by the installer Electrical Installation If the CO200 Duct is to be used to monitor possible leakage of carb...

Отзывы: