Differential Pressure Switches

The diaphragm type differential pressure switches are 

connected by vinyl tubing to the gas valve and the air 

inlet connection on the negative side and the sight glass 

adapter on the positive side. The pressure switches monitor 

air fl ow by sensing the differential pressure measured in 

inches of water (” w.c.). The factory settings on these 

switches are 0.5” w.c. on normally open switch and 3.5” 

w.c. for normally closed switch. See pages 30-32, “Detailed 

Sequence of Operation,” for details on operation of 

differential pressure switches.

Blower 

The blower provides a means for pushing combustion air 

into and through the mixer, the burner, the fl ue ways of 

the cast aluminum boiler section before being discharged 

through the vent piping to the outdoors. 

Circulator Pump

Every forced hot water system requires at least one 

circulating pump. The circulating pump imparts the 

necessary energy to move the water through the closed 

loop supply and return piping systems, terminal heating 

equipment (fi nned tube radiators, etc.) and back through 

the boiler for reheating. To provide the required hot water 

fl ow rates, the circulator pump must be properly sized to 

overcome frictional losses (usually measured in feet of 

water, also referred to as “pump head loss”) of the supply 

and return piping systems and boiler. The circulator pump 

is furnished in a carton within the boiler cabinet. The 

circulator(s) should always be located on the downstream 

(i.e., “pumping away”) side of the expansion tank.

Drain Valve

The manual drain valve provides a means of draining the 

water in the heating system, including the boiler and hot 

water supply and return piping systems installed above the 

drain valve. This drain valve is installed in the ¾” tapping 

at the bottom of the boiler. Any piping installed below the 

elevation of this drain valve will require additional drain 

valves to be installed at low points in the piping systems in 

order to drain the entire system.  

A.S.M.E. Rated Pressure Relief Valve

Each boiler must have a properly sized and installed 

A.S.M.E. rated pressure relief valve. Water expands as it is 

heated by the burner/boiler sections. If there is no place 

for the water to expand its volume, (i.e., a properly sized 

and functioning expansion tank) pressure on the inside of 

the boiler and heating system will increase. The furnished 

relief valve will automatically open at 30 psig pressure to 

relieve the strain on the boiler and heating system from 

the increasing pressure. The pressure relief valve discharge 

must be piped with the same size as the valve discharge 

opening to an open drain, tub or sink, or other suitable 

drainage point not subject to freezing, in accordance with 

A.S.M.E. specifi cations. 

Failure to provide the pressure relief valve with piping as 

herein described may cause water damage and/or serious 

bodily injury. The boiler manufacturer is not responsible for 

any water damage or personal injury.

Blocked Vent Safety Shutoff

The boiler is equipped with a blocked vent safety shutoff 

which shuts off the main burner gas in the event that the 

airfl ow of combustion products through the fl ue-way is 

reduced. In the event of a blocked fl ue-way, enough air 

will not be available to support combustion and the IBC will 

lock out due to loss of adequate air fl ow. 

Pressure switches monitor air fl ow by sensing differential 

pressure. The contacts are normally open and close when 

the draft inducer is running and causing the differential 

pressure at the switch to exceed its setting. The closed 

switch proves there is adequate air fl ow for combustion. 

The pressure switch shuts off the main burner if the 

differential pressure is inadequate due to a blocked vent 

pipe, a blocked air intake, a blocked boiler section, or 

a blocked air inducer. After 5 minutes of inadequate 

differential pressure, the IBC will lock out. 

The “Purge” indicator lamp (see Figure #16) will blink, 

indicating a failure to prove adequate combustion air fl ow 

or fl ue gas fl ow. The IBC will automatically reset after 15 

minutes or can be manually reset as noted on page 20 of 

this manual, “Hot Surface Igniter.” If the boiler cannot be 

restored to normal operating condition by resetting the 

control, contact a qualifi ed service agency to check the 

heat exchanger fl ue-ways for blockage.

Low Water Cut Off

This unit is equipped with a low water cut off control that 

protects against dry fi ring. This control provides burner cut 

off if there is an unsafe water loss, which can result from 

a broken or leaking radiator, pipe, or boiler. A water/glycol 

mixture up to 50% concentration may be used with the low 

water cut off.

External Condensate Pump (Optional)

For installations where there is no fl oor drain or other 

appropriate drainage available to receive condensate from 

the boiler, an external fl oat activated condensate pump with 

integral sump (supplied by others) is required. 

The condensate pump can be piped to a remote tie in point 

to a sanitary sewer system. For this application, the boiler 

must be installed so that proper pitch of piping to the 

external condensate reservoir (sump) can be accomplished. 

Use wood frame or blocks (not factory supplied) to raise 

boiler as required for proper installation.

CONTROLS AND ACCESSORIES

Содержание Q90-125

Страница 1: ...RECT VENT CONDENSING HOT WATER BOILER INSTALLATION OPERATION MAINTENANCE MANUAL An ISO 9001 2008 Certified Company DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com P...

Страница 2: ...otential hazards of varying risk levels KEEP THIS MANUAL NEAR BOILER AND RETAIN FOR FUTURE REFERENCE NOTICE Indicates information which should be followed to ensure proper installation and operation S...

Страница 3: ...ents This may cause dangerous operation Under firing may result in too much air for the pre mix burner causing poor or loss of combustion Never vent the products of combustion from this boiler 5 to an...

Страница 4: ...196 500 172 400 172 200 147 800 147 400 123 500 123 000 2 000 194 000 193 000 169 800 169 400 145 600 144 800 122 000 121 000 3 000 191 000 189 500 167 200 166 600 143 400 142 200 120 500 119 000 4 00...

Страница 5: ...s gas fired direct vent condensing hot water boilers Heating Capacity indicates amount of heat available after subtracting losses up the stack Most of this heat is available to heat water Small portio...

Страница 6: ...r external condensate pump with reservoir at per foot 21 mm m wood frame or blocks may be used to raise boiler Locating The Boiler Select location which is level central to piping systems 1 served and...

Страница 7: ...dripping spraying rain etc during operation and service circulator replacement condensate trap control replacement etc Boiler must be located where ambient temperatures 8 minimum possible room tempera...

Страница 8: ...ated with 1 2 armaflex or equivalent In extremely cold climate areas use 3 4 armaflex or equivalent Combustion air must be clean outdoor air Combustion air must not be taken from inside structure beca...

Страница 9: ...te at maximum speed Do not operate a summer exhaust fan Close fire dampers Place in operation the appliance being inspected 4 Follow the lighting instructions Adjust thermostat so appliances will oper...

Страница 10: ...ns U S Size expansion tank accordingly Consult expansion tank manufacturer for proper sizing information Connect properly sized expansion tank not furnished as shown in Figure 6 for diaphragm type exp...

Страница 11: ...Single Zone Boiler Piping Figure 9B Multi Zone Boiler Piping With Zone Valves Figure 9A Multi zone Boiler Piping with Circulators Individual boiler discharge piping shall be independent of other disch...

Страница 12: ...use CSA or ULC certified schedule 40 PVC drain pipe and cement Condensate pump with reservoir not furnished may be used to remove condensate to drain line sanitary line above boiler if floor drain is...

Страница 13: ...s unit of CSA or ULC certified schedule 40 CPVC schedule 40 PVC PVC DWV or ABS DWV pipe and pipe cement SDR pipe is NOT approved in Canada For Canadian installations all plastic venting material must...

Страница 14: ...re vent vapors will not damage plants shrubs air conditioning equipment or siding on the house Termination should be positioned so that it will not be effected by wind eddy air born leaves snow or rec...

Страница 15: ...y having jurisdiction or in the absence of such requirements United States National Fuel Gas Code ANSI Z223 1 NFPA 54 Canada Natural Gas and Propane Installation Code CAN CSA B149 1 Use pipe joint com...

Страница 16: ...ocated on exterior boiler jacket See Figure 13 for diagram showing location of service switch junction box and power supply connection points Connect black hot lead from power supply to either of unus...

Страница 17: ...tions If the two 120 volt circulator wire terminals inside the junction box are not used please leave the two wire nuts to prevent the short circuit CAUTION Label all wires prior to disconnection when...

Страница 18: ...BLOWER G 2 4 3 1 P5 W BK CASTING TEMPERATURE SAFETY SWITCH MANUAL RESET BR BL W V BR SET AT 3 5 WC SWITCH N C AIR PRESSURE DIFFERENTIAL CONTROL HI LIMIT AQUASTAT SET AT 0 5 WC BL BR AIR PRESSURE DIFFE...

Страница 19: ...3K 5K GAS VALVE 4K1 3K1 P3 5 24 VAC 4 5 P2 2 P3 2 BLOWER P5 1 1K1 P10 1 2K1 P7 1 P4 1 TRANSFORMER P1 1 120 VAC 3 P1 3 1 HOT SURFACE IGNITER P12 1 P6 1 5K1 P12 2 5K2 P6 2 P10 3 CIRCULATOR FIELD WIRED P...

Страница 20: ...gure 16 will blink indicating the failure mode as a lack of flame signal The IBC is manually reset from lockout by either removing and reestablishing the thermostat s call for heat or by turning the s...

Страница 21: ...valve discharge must be piped with the same size as the valve discharge opening to an open drain tub or sink or other suitable drainage point not subject to freezing in accordance with A S M E specifi...

Страница 22: ...type 356 T6 aluminum Use of incompatible antifreeze could damage the heat exchanger and will void the product warranty Antifreeze must be maintained per specifications of manufacturer Failure to do so...

Страница 23: ...turn by hand do not try to repair it call a qualified service technician Force or attempted repair may cause fire or explosion Do not use this appliance if any part has been under 4 water Immediately...

Страница 24: ...piping section in this manual Check for orifice in negative pressure hose at gas valve and 2 air intake pipe upstream of 3 gas valve Relight boiler 4 If boiler still does not light the air inlet pipe...

Страница 25: ...n port on the boiler A z B C z D E 6 After the igniter warm up period the integrated boiler control energizes the gas valve initiating a 6 second trial for ignition mode which is indicated by the illu...

Страница 26: ...manual reset high limit or additional safety controls test for operation as outlined by the control manufacturer Burner should be operating and should go off when controls are tested When safety contr...

Страница 27: ...e should read between 4 and 10 w C For natural gas and between 10 and 14 w c For propane gas Drill a hole in the plastic CPVC combustion analyzer 2 Turn the thermostat to the closed position so the ap...

Страница 28: ...akage and tighten G bolts or replace gaskets if necessary Remove jacket front and top panels and check for H piping leaks around relief valve and other fittings Repair if found DO NOT use stop leak co...

Страница 29: ...raying or running water Use a flexible handle nylon brush to loosen I sediment and aluminum oxide on all exposed heating surfaces of boiler see Repair Parts Manual for diagram Be sure that brush does...

Страница 30: ...30 SERVICE HINTS DETAILED SEQUENCE OF OPERATION...

Страница 31: ...ntrol will attempt to relight boiler 3 times if flame is not proven control lockout problem establishing a flame signal Valve light is blinking Control will automatically reset after 1 hour HIGH LIMIT...

Страница 32: ...t Gas valve and circulator pump are de energized valve and flame lights go out Blower runs for 30 seconds post purge purge light is on Blower is de energized after 30 seconds purge light shuts off Boi...

Страница 33: ...vere injury or death Do not attempt to modify the physical or electrical characteristics of this boiler in any way NOTICE In a reset from lockout condition all electrical meter readings at the gas con...

Страница 34: ...F Off during purge cycle draft inducer is not powered on or air flow is not proven Off during igniter and run cycle normal operation purge cycle complete Blinking IBC is locked out Problem could indic...

Страница 35: ...he gas supplier s instructions If you can not contact your gas supplier call the fire department Should overheating occur or the gas supply fail to shut off do not turn off or disconnect the electrica...

Страница 36: ...36 Troubleshooting Chart 2 TROUBLESHOOTING...

Страница 37: ...SAGS OR LOW SPOTS WHERE CONDENSATE MAY PUDDLE AND BLOCK THE VENT YES CHECK AIR PRESSURE SWITCH PER INSTRUCTIONS ON FOLLOWING PAGES ARE SAMPLING LINES CLEAR AND CONNECTED PROPERLY NO CLEAN OUT SAMPLIN...

Страница 38: ...R LIGHT CHECK FOR 24 VAC ACROSS TERMINALS MV ON THE GAS CONTROL WHILE VALVE FLAME INDICATOR LIGHT IS ON NO NO CHECK FOR 24 VAC ACROSS TERMINALS CN6 2 AND CN6 5 ON IBC WHILE THE VALVE FLAME LED IS LIT...

Страница 39: ...39 Troubleshooting Chart 5 TROUBLESHOOTING...

Страница 40: ...IC INSTRUCTIONS REQUIRES SPECIFIC TOOLS NO YES REPLACE BURNER REPLACE IBC BOILER SHUTS OFF BEFORE END OF CALL FOR HEAT ARE HI LIMIT AQUASTAT CONTACTS CLOSED NO BOILER OFF ON HIGH LIMIT IS ACTUAL BOILE...

Страница 41: ...s Blockage or moisture in suction lines to switch Blockage or moisture in orifice installed in suction lines to switch Blockage in air intake or vent pipes Undersized air intake or vent pipes Loose bl...

Страница 42: ...42 This Page Intentionally Left Blank...

Страница 43: ...d Service issues reviewed with owner maintenance person Installation booklet affixed on or adjacent to boiler Installer Company __________________________________________ Address _____________________...

Страница 44: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Отзывы: