SYSTEM PIPING

WARNING

Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, 

scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:

• Connect to safety valve outlet. Piped down to safe point of disposal. Check local codes for maximum 

distance from floor or allowable safe point of discharge.

• Pipe size be of equal to or greater than of safety valve outlet over entire length of discharge line.
• Have no intervening shutoff valve between safety valve and discharge to atmosphere. Do not plug or 

place any obstruction in discharge line.

• Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing.
• Allow complete drainage of valve and discharge line.
• Install safety valve with spindle in vertical position.
• Do not install shutoff valve between boiler and safety valve.
• Support safety valve discharge piping.
• Be short and straight as possible.
• Terminate with plain end, not threaded.
• Constructed of material suitable for exposure to temperatures of 375° F (191°C); or greater.

Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation 

requirements.

!

   

Check local codes 

for maximum 

distance from 

floor or other 

allowable safe 

point of discharge

Safety Valve

Discharge 

Piping

6" Above Floor 

Figure 3 - Safety Valve

 P/N 14683003, Rev. D [08/03/2015]

Содержание PSB-3D

Страница 1: ...NANCE MANUAL P N 14683003 Rev D 08 03 2015 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 www ecrinternational com MODEL PSB Electronic Intermittent Ignition MODELS PSB 3D PSB 3DP PSB 4D PSB 4...

Страница 2: ...sions Inches Intermittent Ignition w Vent Damper Flue Diameter A Width PSB 3D 5 11 PSB 4D 6 14 PSB 5D 6 17 PSB 6D 7 21 PSB 7D 7 24 PSB 8D 7 27 PSB 9D 7 30 Add 5 to height for Vent Damper 1 Add model n...

Страница 3: ...et AHRI Rating Mbh Net AHRI Rating Sq Ft 1 PSB 3D 3 Natural Gas 75 62 82 7 47 196 Propane 70 58 82 7 44 183 1 PSB 4D 4 Natural Gas 112 91 82 0 68 283 Propane 105 85 80 4 64 267 1 PSB 5D 5 Natural Gas...

Страница 4: ...urring any obligation whatsoever Introduction Boiler is designed for use in closed heating systems where all steam is returned as condensate and make up water is minimal Boiler is not designed for or...

Страница 5: ...appliance with improper methods or materials could result in death or serious injury due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible WARNING...

Страница 6: ...se Boiler location should not interfere with proper circulation of air Introduce outside air if normal infiltration does not provide necessary air Fresh Air for Combustion on page 11 6 Notify owner to...

Страница 7: ...struction in discharge line Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing Allow complete drainage of valve and discharge line Install safety val...

Страница 8: ...r one for each main 6 All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figure 5 7 When piping the vertical risers from the boiler to the header the bottom of the...

Страница 9: ...9 Figure 4 Recommended Near Boiler Piping Using One Supply Tapping SYSTEM PIPING P N 14683003 Rev D 08 03 2015...

Страница 10: ...IPING Figure 6 Chilled Water Piping VALVES A B OPEN FOR HEATING CLOSE FOR COOLING VALVES C D CLOSE FOR HEATING OPEN FOR COOLING Figure 5 Recommended Near Boiler Piping Using Two Supply Tappings P N 14...

Страница 11: ...oom volume is greater than 21 cubic feet divided by ACH air changes per hour x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Ai...

Страница 12: ...er than 3 4 the chimney height HT Figure 7 page 13 Vent Pipe Fasten sections of vent pipe with 3 sheet metal screws at each joint to make piping rigid Support horizontal portions of vent system to pre...

Страница 13: ...appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI Z223 1 NFPA 54...

Страница 14: ...damper troubleshooting guide refer to manual packaged with vent damper Horizontal Installation To Boiler Vent Damper To Chimney NO NO YES YES Flow Install vent damper with actuator to sides of vent o...

Страница 15: ...ssive vibrations and prevent strain on gas connection Gas valve will not support piping weight Use thread joint compound pipe dope suitable for natural and liquefied petroleum gas Install field source...

Страница 16: ...es are black One wire is located on secondary of 24 volt transformer second wire is located on pressure limit control F Boilers with CG400 probe type low water cut off one wire is green and is located...

Страница 17: ...y and turn clockwise to OFF Do not force For Your Safety Read Before Operating WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal i...

Страница 18: ...of boiler Determine water level when boiler is off and cold when all water in the system is inside the boiler and return piping below water line and everything above water line is air no steam When b...

Страница 19: ...softer blue outer mantel with no yellow Remain still when observing main burner flames Check main burner orifices burner throat and flame ports for dust and lint obstruction if flame appearance is not...

Страница 20: ...n thermostat to call for heat C Gas valve opens for approximately 10 seconds time delay on probe type LWCO gas valve will close and red indicator illuminates on LWCO D When water is restored it waits...

Страница 21: ...ection from boiler drain valve to safe discharge point outside Shut off gas burners open drain valve allow all of water in boiler to drain out Close drain valve Allow boiler to cool slowly refill boil...

Страница 22: ...RTV silicone to four mounting surface flanges of flue collector Mount flue collector on heat exchanger Tighten nuts and bolts 6 Seal front edge and four corners of flue collector to heat exchanger wit...

Страница 23: ...t switch blown Have your service technician check heat exchanger for blockage Chimney flue is blocked Spill switch contacts open requiring manual reset of spill switch Have your service technician che...

Страница 24: ...t be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 13 Wiring Diagrams For Boilers With CG400 Probe Type Low Water Cut Off Shown CG400 PS802 CG400 N 2 H 1 C P...

Страница 25: ...nal wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 17 Wiring Diagrams For Boilers With 67D 1 Float Type Low Water...

Страница 26: ...water feeder maybe used with either of the low water cutoffs listed Water feeder maintains safe minimum water level Keeps boiler running by compensating for minor evaporative steam leaks and prevents...

Страница 27: ...27 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Страница 28: ...28 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Страница 29: ...29 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Страница 30: ...30 REPAIR PARTS Safety Relief Valve 14 11 NPT X 4 Nipple PF 033 02 CG400 LOW WATER CUT OFF 240009340 P N 14683003 Rev D 08 03 2015...

Страница 31: ...31 Date Service Performed Company Name Tech Initials Company Address Phone P N 14683003 Rev D 08 03 2015...

Страница 32: ...reases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLE...

Отзывы: