Method B - Detailed Residential Sizing Sample Calculations
Example
1
A water heater is to be installed with a new boiler. The residence has the following fixtures:
Bath
#1
Bath #2
3 GPM Shower Head
Vanity
30 Gal. Bathtub
Vanity
Kitchen
Laundry
Kitchen Sink
Clothes Washer
Automatic Dishwasher
The heat loss of the house is 80,000 BTU/hr
Note:
Although a four section boiler would be capable of heating the house (Net Rating = 82,000 BTU/hr),
its DOE heating capacity is only 94,000 BTU/hr (Need 110,000 Btu/hr). For this reason, install a
five section boiler that has a heating capacity of 125,000 BTU/hr.
Solution:
The completed sizing sheet for this example is shown in figure 2. The adjusted peak hour demand
is 145 gallons per hour. From table 1, we see that
a
water heater 220 will fulfill this requirement
with the appropriate boiler. Refer to Table 1 for required boiler output. If the model 220 is used in
combination with a boiler capable of producing 110,000 Btu / hr. The output will give you 156 GPH
first hour ratings. The circulator on the boiler must be capable of producing 3.4 GPM.
Page 11
Содержание ARTESIAN 220
Страница 5: ...Page 5 ...
Страница 6: ...Page 6 ...
Страница 10: ...Page 10 ...
Страница 12: ...Page 12 ...
Страница 15: ...Page 15 ...
Страница 17: ...Page 17 ...
Страница 18: ...Page 18 ...
Страница 22: ...Page 22 ...
Страница 23: ...Page 23 ...
Страница 24: ...Page 24 ...
Страница 25: ...Page 25 ...
Страница 26: ...Page 26 ...
Страница 27: ...Page 27 ...
Страница 30: ...Page 30 ...
Страница 31: ...Page 31 ...
Страница 32: ...Page 32 ...
Страница 35: ...Page 35 ...
Страница 36: ...Page 36 ...
Страница 37: ...Page 37 ...
Страница 38: ...Page 38 ...
Страница 39: ...Page 39 ...