![Dungs GGAO-A4-4 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/dungs/ggao-a4-4/ggao-a4-4_installation-instructions_2539724003.webp)
3 … 5
MC • Karl Dungs
, Inc.
• GGA
O
...A4 • Edition 2016.02 • P/N 271843
... Threaded Connection
1 Pressure connection (+) 1/4” NPT, Gas or Air
2 Pressure connection (–) 1/8” NPT, Gas or Air. May also be
used as an atmospheric vent connection.
3 Test nipple p (+) Ø 0.35” (9 mm), integrated
GGAO-A4... Mounting Procedure
• Apply good quality pipe sealant to the male threads only.
• Use 13/16” Wrench to secure the switch to the pipe.
DO NOT Exceed 177 lb-in of Torque on 1/8” Connections
DO NOT Exceed 177 lb-in of Torque on 1/4” Connections
• After installation is complete, perform a leak test.
Pressure Conn. & Mounting GGAO-A4
Standard installation position is
vertical
upright diaphragm.
When installed
horizontally
, the pressure switch switches at a pressure higher by approx.
0.2 in. W.C.
When installed
upside down
, the pressure switch switches at a pressure lower by approx.
0.2 in. W.C.
When installed in
other positions
, the pressure switch switches at pressure deviating from
the set reference value by max.
±
0.2 in. W.C.
α
α
α
α
Made in Germany
0.4
4
in. W.C.
GGAO-A4-4
Adjustment
The scale indicates the setpoint when switch is mounted in
the vertical position and increasing pressure.
Installation Position
G 1/
4
3
2
1