Calibrating the DMA

Note:

 The red and yellow switches are factory set outside of 

the 0 to 90˚ operating range.  Do not change these adjust-
ment dials until calibration is complete. 

DO NOT

 use these 

switches in lieu of the calibration.

To Adjust Minimum Position

1. Apply a 4 mA DC input signal.  
2. Turn the

 Y min

 

(Zero) potentiometer (adjusting 

    range 0 to 100 % of stroke)  to position the actua-    
    tor at the desired minimum position. Turning 

Y min 

    (Zero) CCW drives the minimum position towards 
    0˚.

To Adjust Maximum Position

1. Apply 20 mA DC input signal.
2. Turn the

 

Y max

 

(Span) potentiometer  (adjusting 

    range 25 to 100 % of stroke) to position the actua-
    tor at the desired maximum position. Turning 

Y max

 

   

(Span) CCW drives the setpoint towards 0˚.

Note:

 

 Y min 

 (

Zero) must be no more than 75 % of 

Y max

 

(Span) (reference: 90˚ = 100%).  E.g. if the maximum position 
is set at 85˚, the minimum position can be set at 64˚ maxi-
mum.  (85˚ * 0.75 = 64˚).

Switch Adjustment

:  

Note: Use the scale under the Red ST1 switch to field set
the switches.The DMA incorperates two limit switches that
limit the crank shaft from exceeding a set point if the zero
or span potentiometer fails. The DMA also has an 
SPDT auxilary switch. All switches can be adjusted 
anywhere over the 90˚stroke.

ST1 Limit Switch (Red)

:

 

This switch limits the mini-

mum position at 0˚ or more. Set the switch at approx. 
1˚ LESS than the Y Min. setpoint. The small set 
screw on the side of the red dial can be used for fine
tuning adjustment.

ST2 Limit Switch (Yellow)

This switch limits the maxi-

mum position at 90˚ or less.  Set the switch at ap-
prox. 1˚ MORE than the Y Max. setpoint. The small 
set screw on the side of the yellow dial can be used 
for fine tuning adjustment.

MV Auxiliary-Switch (Yellow): 

Set the switch to trip at 

the desired setpoint using the scale under the Red 
ST1 switch. When the motor is at 0˚, the NC contact 4
and 3 opens, and the NO contact 4 and 2 closes.