Dungs AA-A1-0 Series Скачать руководство пользователя страница 2

2 … 5

MC • Karl Dungs

, Inc.

 • AA...A1 • Edition 2016.03 • P/N 261392

Specifications

Max. Operating Pressure

MOP = 1.5 PSI (103 mbar)

Ambient / Medium Temperature

-40 °F ... +140 °F

(-40 °C … +60 °C)

Gases

Air and non-aggressive gases. 

Not

 suitable for natural gas, propane, 

butane and other combustable 

gases.

Materials in contact with Gas

Housing: Polycarbonate

Switch: Polycarbonate

Diaphragm: NBR-based rubber

Switching contact: Silver (Ag)

°F

0

-40

+140

Gas

AA...A1  

SPDT differential pressure switch in pressure and vacuum ranges. The differential pressure acts via the  

 

diaphragm against the force of the setting spring on the micro-switch. The pressure switch operates  

 

without any auxiliary power.

Contact Rating

5 A resistive, 

3 A inductive @ 120 VAC

1 A @ 12 - 48 VDC

Electrical Connection

1/4 x 1/32” (6.3 x 0.8 mm) 

flat male terminals

Enclosure

NEMA Type 1 / NEMA Type 12 with 

appropriate cover

Models Designations & Ranges

Type

Version

Description

Order No.

Factory setting 

range 

in. W.C.

Switching 

hysteresis

in. W.C.

AA-A1-0-...

AA-A1-0-2

AA-A1-0-3

AA-A1-0-4

No cover

No cover

No cover

266906

266904

266908

0.16 -   1.20

0.40 -   4.00

1.00 - 20.00

≤ 

0.14

≤ 

0.20

≤ 

0.40

AA-A1-3-...

AA-A1-3-2

AA-A1-3-3

AA-A1-3-4

Includes NEMA Type 12 cover 

and 1/2 NPT conduit connection

Includes NEMA Type 12 cover 

and 1/2 NPT conduit connection

Includes NEMA Type 12 cover 

and 1/2 NPT conduit connection

266907

266905

266909

0.16 -   1.20

0.40 -   4.00

1.00 - 20.00

≤ 

0.14

≤ 

0.20

≤ 

0.40

Ag

[A]

NEMA

[

V

]

 

[

A

]

 

[

Hz

]

 

[

VA

]

[PSI]

Содержание AA-A1-0 Series

Страница 1: ...essure switch perform a leak age and function test Please read the instruction be foreinstallingoroperating Keep theinstructioninasafeplace You find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Theinstallationandmaintenance of this product must be done under the supervision of an ex periencedandtrainedspecialist ...

Страница 2: ...essure switch operates without any auxiliary power Contact Rating 5 A resistive 3 A inductive 120 VAC 1 A 12 48 VDC Electrical Connection 1 4 x 1 32 6 3 x 0 8 mm flat male terminals Enclosure NEMA Type 1 NEMA Type 12 with appropriate cover Models Designations Ranges Type Version Description Order No Factory setting range in W C Switching hysteresis in W C AA A1 0 AA A1 0 2 AA A1 0 3 AA A1 0 4 No c...

Страница 3: ... Connection p2 lower pressure Connection p1 higher pressure Application Connection Examples System vacuum monitor AA A1 is connected to the air duct with the p2 connection p1 is not con nected with the air duct Donotsealthep1 connection itmust be open to the atmosphere Filter monitoring To monitor a filter the AA A1 can be connected as shown above Blower monitoring For blower monitoring connect co...

Страница 4: ...iring must comply with local electrical codes ordi nances and regulations Do not exceed the switch ratings given in the specifi cations and on the switch Standard installation position is vertical upright diaphragm When installed horizontally the pressure switch switches at a pressure higher by approx 0 2 in W C When installed upside down the pressure switch switches at a pressure lower by approx ...

Страница 5: ...d that the NO contact makes The NC contact will make automatically when pressure falls below the set point pressure 4 Connect a meter capable or reading 0 1 ohms to the NO and COM contacts 5 Measure the resistance across the NO and COM contacts If the resistance is more than 1 0 ohm the switch switch should be replaced since this indicates that the switch contacts are starting to either corrode or...

Отзывы: