 • AA...A1 • Edition 2016.03 • P/N 261392

UL Recognized: UL 353

File # MH16628

CSA Certified: CSA C22.2 No. 14 

File # 201527

FM Approved: Class 3510, 3530

File # J.I. 1T7A8.AF

Commonwealth of Massachusetts Approved Product Approval code G3-0106-191

AA...A1 

Differential Air Pressure 

Switch

Installation Instructions

Table of Contents

USA

CDN

Table of Contents  . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Attention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2

Models Designations & Ranges  . . . . . . . . . . . . Page 2

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3

Pressure Connection . . . . . . . . . . . . . . . . . . . . . Page 3

Application & Connection Examples . . . . . . . . Page 3

Installation Position  . . . . . . . . . . . . . . . . . . . . . . Page 4

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4

Operation & Adjustment. . . . . . . . . . . . . . . . . . . Page 5

Maintenance & Testing . . . . . . . . . . . . . . . . . . . . Page 5

Accessories & Replacement . . . . . . . . . . . . . . . Page 5

Approvals

1, 2, 3 ... 

= Action

= Instruction

Explanation of symbols

Attention

On completion of work on the 

pressure switch, perform a leak-

age and function test.

Please read the instruction be-

fore installing or operating. Keep 

the instruction in a safe place. You 

find the instruction also at www.

dungs.com. If these instructions 

are not heeded, the result may 

be personal injury or damage to 

property.

The installation and maintenance 

of  this  product  must  be  done 

under the supervision of an ex-

perienced and trained specialist. 

Never perform work if gas pres-

sure or power is applied, or in 

the presence of an open flame.

Any adjustment and application-

specific adjustment values must 

be  made  in  accordance  with 

the equipment manufacturers 

instructions.

Check the ratings in the specifica-

tions to verify that they are suit-

able for your application.

IFGC

CSA

UL

ANSI

NFPA

This  product  is  intended  for 

installations covered by, but not 

limited to, the following codes 

and standards: NFPA 86, ANSI 

Z83.4/CSA 3.7, ANSI Z83.18/CSA 

4.9, ANSI Z21.13, CSD-1, UL 795, 

CSA B149.1 or CSA B149.3

[

V

] [

A

]

[

Hz

]

 

[

VA

]

Safety

first

O.K.

Содержание AA-A1-0 Series

Страница 1: ...essure switch perform a leak age and function test Please read the instruction be foreinstallingoroperating Keep theinstructioninasafeplace You find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Theinstallationandmaintenance of this product must be done under the supervision of an ex periencedandtrainedspecialist ...

Страница 2: ...essure switch operates without any auxiliary power Contact Rating 5 A resistive 3 A inductive 120 VAC 1 A 12 48 VDC Electrical Connection 1 4 x 1 32 6 3 x 0 8 mm flat male terminals Enclosure NEMA Type 1 NEMA Type 12 with appropriate cover Models Designations Ranges Type Version Description Order No Factory setting range in W C Switching hysteresis in W C AA A1 0 AA A1 0 2 AA A1 0 3 AA A1 0 4 No c...

Страница 3: ... Connection p2 lower pressure Connection p1 higher pressure Application Connection Examples System vacuum monitor AA A1 is connected to the air duct with the p2 connection p1 is not con nected with the air duct Donotsealthep1 connection itmust be open to the atmosphere Filter monitoring To monitor a filter the AA A1 can be connected as shown above Blower monitoring For blower monitoring connect co...

Страница 4: ...iring must comply with local electrical codes ordi nances and regulations Do not exceed the switch ratings given in the specifi cations and on the switch Standard installation position is vertical upright diaphragm When installed horizontally the pressure switch switches at a pressure higher by approx 0 2 in W C When installed upside down the pressure switch switches at a pressure lower by approx ...

Страница 5: ...d that the NO contact makes The NC contact will make automatically when pressure falls below the set point pressure 4 Connect a meter capable or reading 0 1 ohms to the NO and COM contacts 5 Measure the resistance across the NO and COM contacts If the resistance is more than 1 0 ohm the switch switch should be replaced since this indicates that the switch contacts are starting to either corrode or...