Service Manual for Tri-Channel Cold Pan SUB-GP

Charging Procedure

NOTE:

 Prior to refrigeration system service,

special care must be taken during the evacuation
process to remove air, moisture and other non-
condensables from the system. Duke
Manufacturing recommends the following triple
evacuation method. Failure to follow this
procedure may result in poor refrigeration
system performance.

1. Evacuate system to 1500 microns.

2. Break vacuum to 2 psig with dry nitrogen. If

dry nitrogen is unavailable, use same type
of refrigerant as used in system.

3. Evacuate system to 500 microns.

4. Break vacuum to 2 psig with dry nitrogen. If

dry nitrogen is unavailable, use same type
of refrigerant as used in system.

5. Evacuate system to 500 microns.

The system is now ready to receive refrigerant
charge according to information on data plate.

CAUTION: Never use oxygen or acetylene

in place of dry nitrogen or
refrigerant for leak testing. A
violent explosion may result,
c a u s i n g   p r o p e r t y   d a m a g e ,
personal injury or death. When
using nitrogen to pressure test,
a l w a y s   u s e   a   p r e s s u r e
regulator. Failure to do so will
r e s u l t   i n   e x t r e m e l y   h i g h
pressure of the compressor or
other system components and
r e s u l t   i n   p r o p e r t y   d a m a g e ,
personal injury and death.

NOTE:

 Prior to repair, ensure there is enough

process hose (approximately 12") present to
complete the repair using the above procedure.
If not, install a new process hose before repair
sequence.

1. Install a temporary access valve on the high

and low side of process hoses as close to
factory crimps as possible.

2. Use temporary valves to perform repair.

Duke Manufacturing will not reimburse the
cost of permanently installed valves.

3. After completing repair, evacuate system

using the triple evacuation method described
in Duke Manufacturing Service Bulletin
Number 26.

4. After completing proper evacuation method,

recharge system, using proper refrigerant
according to information on data plate.

5. Continue crimping process hose just below

temporary valve and again 2" below crimp.

6. With crimp tool in place, remove temporary

valve.

7. Braze shut end of process hose.

8. Allow to cool for about 5 minutes.

9. Remove crimp tool.

10. Check brazed end for leaks.

Содержание SUB-GP

Страница 1: ...Duke is a registered trademark of the Duke Manufacturing Company Duke Manufacturing Company 2305 N Broadway St Louis MO 63102 Phone 314 231 1130 Toll Free 1 800 735 3853 Fax 314 231 5074 www dukemfg c...

Страница 2: ...E OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WARNING UNLESS ALL COVER AND ACCESS PANELS ARE IN PLACE AND PROPERLY SECURED DO NOT OPERATE THIS EQUIPMENT CAUTION...

Страница 3: ...nnection 4 MAINTENANCE 5 Stainless Steel Care and Cleaning 5 PREVENTIVE MAINTENANCE 6 Cleaning the Condenser Coil 6 PARTS REPLACEMENT 7 Thermostat Replacement 7 General 7 Evaporator 7 General 7 Refrig...

Страница 4: ...Be sure that the unit is placed on a firm flat surface floor Check for cracks in flooring or tile and avoid these areas if possible If necessary place support pads properly rated for the weight of th...

Страница 5: ...trial cleaners and also in hard water and salts If a chloride or alkaline cleaner has been used rinse repeatedly and dry thoroughly Always use only soft cloths or plastic scouring pads For routine cle...

Страница 6: ...or near the condenser coil 9 8 765 4 3 2 1 WARMER COLDER Figure 3 Location of Condensing Coil The condenser coil is located and accessed from the front of the unit Figure 3 A vent cover protects the...

Страница 7: ...m evaporator coil 5 Remove knob 6 Remove thermostat mounting screws 7 Remove thermostat from control panel 8 Install replacement thermostat mounting screws and knob NOTE Do not kink thermostat probe 9...

Страница 8: ...ly pressure check evaporator coils for leaks 9 Install replacement refrigeration assembly onto slide bars 10 Slide in refrigeration assembly to original position 11 Install refrigeration assembly moun...

Страница 9: ...l injury or death When using nitrogen to pressure test always use a pressure regulator Failure to do so will result in extremely high pressure of the compressor or other system components and result i...

Страница 10: ...Service Manual for Tri Channel Cold Pan SUB GP 10 ELECTRICAL Electrical Schematic Figure 7 Electrical Schematic...

Страница 11: ...ostat switch is stuck in the closed position Drain hose plugged Drain hose loose or disconnected from drain pan REMEDY Plug unit in Set thermostat to a higher number for a colder temperature Replace t...

Отзывы:

Похожие инструкции для SUB-GP