background image

 

 

6 of 12 

 

PRODUCT HOLDING CABINET 

RESTAURANT 
EQUIPMENT 
MANUAL 

REVISION: 

August 18, 2005 

U.S. Patent 6175099, 6262394 

Other U.S.  and Foreign Patents Pending 

DUKE MANUFACTURING CO. 

TOLL FREE 800-735-DUKE (3853) 

314-231-1130 

Troubleshooting 
 

 
 
 
 
 

Electronic Control Fault Indications 

 

The Service Light is located on the front of the control next to the heat light (see Figure 3).  It provides an 
indication to alert the operator to failures in the heater circuit.  When a Service Light is on, the affected unit 
should not be used until the cause of the fault is corrected by a qualified service technician.  The fault 
conditions that could cause the control to turn the service light on are as follows: 

 

1.

 

Over – Temperature Fault - 

An over-temperature 

fault occurs when the control senses that the shelf 
temperature is higher than the specified factory 
preset temperature.  This occurs when the power is 
not removed from the heating element after the shelf 
has achieved the preset temperature, causing the 
control to turn on the service light.  The auxiliary 
thermostat prevents the temperature from exceeding 
safe levels by regulating the temperature to a 
maximum of 250

°

 F.

 

 

2. 

Under – Temperature Fault - 

An under-temperature 

fault occurs when the control senses that the shelf 
temperature is lower than the specified factory preset 
temperature for more than 30 minutes continuously.  
This occurs when heating element circuit opens or 
the RTD Feedback signal is faulty, causing the 
control to turn on the service light.   

 

 

Temperature Check Procedure 

 

1.  A digital temperature meter that has been calibrated must be used to get an accurate temperature reading.  

Use a thermocouple surface temperature probe to measure temperatures. 

2. 

No pans should be in wells during the pre-heat and temperature check

. Pre-heat the warmer for 30 

minutes before taking any temperature readings.  Do not take readings unless the cavity has been empty 
for 30 minutes.  This will allow the temperature to stabilize and will prevent false readings. 

3.  The warmer cavity should be cleaned and empty before the temperature is checked.  Avoid any air drafts 

that might flow through the cavity. 

4.  Locate the surface temperature probe on the bottom of any cavity in the geometric center.  Make sure the 

probe is making good contact with the surface while taking readings. 

5.  All temperature controls exhibit a swing in temperature as the control cycles on and off while regulating to 

the set point.  The correct calibration temperature is the average of several readings taken over a period of 
20 minutes after the warmer has been pre-heated.  The average temperature should be 

±

 15

°

F from the set 

point. 

There are no user serviceable parts on the Duke Product Holding Cabinet. If a malfunction occurs, ensure unit 
is plugged in then check all switches and circuit breakers. If the malfunction still exists, contact your Duke 
Manufacturing Company authorized service agent or call 1-800-735-3853.

 

Figure 3 

 

Содержание FWM3-51 100

Страница 1: ...ation or technical assistance call TOLL FREE 800 735 DUKE 3853 or 314 231 1130 Product Holding Cabinet U S Patent 6175099 6262394 Other U S and Foreign Patents Pending 156112L Operators and Service Manual FWM3 51 ...

Страница 2: ...tained individually formed sealed compartments of the Duke Product Holding Cabinet eliminate food odor and taste transfer Because the compartments are sealed and formed to the shape of the pan no disassembly is required for cleaning and product changes The unique design of the Duke Product Holding Cabinet allows single temperature operation for all existing product groups This 190 F approved tempe...

Страница 3: ...UKE MANUFACTURING CO TOLL FREE 800 735 DUKE 3853 314 231 1130 Figure 1 1 FWM Specification Sheet Model FWM3 51 Shipping Weight 110 lbs 50 Kg Electrical FWM3 51 100 100V 10 A 1000 W 50 60 Hz FWM3 51 120 120 V 8 3 A 1000 W 50 60 Hz FWM3 51 208 208 V 7 2 A 1500 W 50 60 Hz FWM3 51 230CE 230 V 6 5 A 1500 W 50 60 Hz FWM3 51 240 240 V 6 3 A 1500 W 50 60 Hz ...

Страница 4: ...low instructions in the Operators Manual PERIODIC MAINTENANCE CHECKLIST AND CLEANING GUIDE Stacking Units WARNING TIP HAZARD Do not stack FWM3 51 units CAUTION Risk of fire or electric shock Replace cord with one of the following Duke cordsets only P N 156533 Cordset NEMA 5 15P 120 V P N 156811 Cordset NEMA 5 20P 120 V Canadian FWM3 24 FWM3 42 units P N 156421 Cordset NEMA 6 15P 208 240 V P N 1564...

Страница 5: ...ng Cabinet discontinue use of the affected shelf until the module is serviced 2 Operate using Menu Bar as outlined in the Menu Scoreboard Operators Manual Closing Checklist 1 Turn power switch OFF 2 Remove all pans and pan covers 3 Allow to cool for approximately 30 minutes 4 Clean Product Holding Cabinet as outline in the Daily Cleaning Instructions Cleaning Instructions 1 Wipe down the interior ...

Страница 6: ...rs when heating element circuit opens or the RTD Feedback signal is faulty causing the control to turn on the service light Temperature Check Procedure 1 A digital temperature meter that has been calibrated must be used to get an accurate temperature reading Use a thermocouple surface temperature probe to measure temperatures 2 No pans should be in wells during the pre heat and temperature check P...

Страница 7: ...on is not required DANGER LIVE ELECTRICAL COMPONENTS ONLY QUALIFIED SERVICE PERSONS SHOULD MODIFY CONTROL TEMPERATURE PRESETS Temperature Programming 1 Remove cover from control side of the Holding Cabinet and turn the Holding Cabinet on 2 Locate the pushbutton S1 and S2 on the rear of the control see Figure 4 3 To program press and hold S1 until any LED on the rear of the control illuminates appr...

Страница 8: ...1 156285 LATCH PAN 10 12 156288 SCREW SHOULDER 10 13 0653638 SCREW 1 4 20 X 3 4 20 14 155750 RTD 1K OHM THIN 2 15 157558 ELEMENT FOIL HEAT 100V FOR UPPER 3 WELLS 3 156564 ELEMENT FOIL HEAT 102V FOR UPPER 3 WELLS 3 156301 ELEMENT FOIL HEAT 208V 3 156565 ELEMENT FOIL HEAT 240V 3 156611 ELEMENT FOIL HEAT 230V 3 156994 ELEMENT FOIL HEAT 100V FOR LOWER 2 WELLS 2 156483 ELEMENT FOIL HEAT 102V FOR LOWER ...

Страница 9: ... MANUAL REVISION August 18 2005 U S Patent 6175099 6262394 Other U S and Foreign Patents Pending DUKE MANUFACTURING CO TOLL FREE 800 735 DUKE 3853 314 231 1130 Parts Lists and Illustrations Continued Figure 5 FWM3 51 Product Holding Cabinet Exploded View ...

Страница 10: ...CTURING CO TOLL FREE 800 735 DUKE 3853 314 231 1130 Wiring Schematics C O N N E C T W IR E 4 T O 2 4 0 V T E R M IN A L F O R 2 4 0 V A C A N D 2 3 0 V A C C E U N IT S S H O W N C O N N E C T W IR E 4 T O 2 0 8 V T E R M IN A L F O R 2 0 8 V A C U N IT S 1 0 0 1 2 0 V A C U N IT S U S E A 1 2 0 V T R A N S F O R M E R Figure 6 FWM3 51 Internal Wiring Schematic ...

Страница 11: ...LDING CABINET RESTAURANT EQUIPMENT MANUAL REVISION August 18 2005 U S Patent 6175099 6262394 Other U S and Foreign Patents Pending DUKE MANUFACTURING CO TOLL FREE 800 735 DUKE 3853 314 231 1130 Interface Cable Connection ...

Отзывы: