Duemmegi DISP 2 Скачать руководство пользователя страница 9

DISP2

Rel.: 2.0 - September 2004      -      Page 9

7.2- Centralized alarm outputs and “first out”

As said in a previous paragraph, each message of DISP2 may be set for the activation or less of the centralized alarm
outputs (siren and flasher).

If a message has the centralized alarm outputs disabled, then it does not affect the output relays, and the activation of
the related input simply will cause the displaying of the message.
If instead a message has this function enabled, then the siren output relay will be energized and the flasher output relay
will be de-energized at the activation of the related input (or binary code); this means that both signaling devices will be
activated.

To silence the siren press the button 

 (but the flasher remains activated); the siren will be restarted at the

activation of a new alarm not yet inserted in the queue. Every pressing of the button 

 will cause the displaying of

the first message in the queue, that is the first occurred event (“first out”).

To reset the flasher, all alarms in the queue must be removed by the reset sequence (if no more inputs or binary codes
are still active).

7.3- Messages displaying in MEM or NOMEM modes

If the NO MEMORY mode has been selected (NOM) the displayed messages show, in direct mode, the current condition
of the inputs in the chronological order they occurred. In binary mode, instead, the message related to the  binary code
currently applied to the inputs will be displayed .

If the MEMORY mode has been selected (MEM), the displayed message show the inputs (or binary codes) that have
been activated from last reset sequence, in the chronological order as they occurred.
This last operating mode is the recommended when handling temporary events.

Note that if DISP2 is set for binary mode, the NOMEM setting should be avoided because, as said above, DISP2 will
show only the message related to the currently applied binary code; the NOMEM mode will be instead useful when
DISP2 is connected to an intelligent device (e.g. PLC) and DISP2 is used as a “monitor” of the PLC.

7.4- Reset of the queue

The reset sequence, in MEM mode, allows to clear the displaying queue; this means that all messages in the queue
related to the inputs that are not still active will be removed.

The reset sequence is the following:

¾

  Silence the siren pressing the button  

¾

  Press the button 

; DISP2 will display the message as

in the figure here shown

¾

  Press the button 

 within 3 second to confirm the

clearing of the queue

If no confirmation occurs within 3 seconds, then the reset sequence will be automatically aborted.

Содержание DISP 2

Страница 1: ...MS AND MESSAGES DISPLAY DISP 2 User s Manual Notes Information in this document may be modified without notice For additional information and details contact DUEMMEGI srl via LONGHENA 4 20139 MILANO ITALY Tel 02 57 30 03 77 Fax 02 55 21 36 86 ...

Страница 2: ...ect to the previous family DISP2 performs several features as listed in the following paragraph 2 DISP2 GENERAL CHARACTERISTICS LCD display 2 x 16 characters with back lighting 1 alarm pending message made by 2 lines LCD contrast may be adjusted by the button on the front panel Cyclic displaying of more messages the cycle time may be set by user in the range 1 to 10 seconds Message programming by ...

Страница 3: ...pply the input terminals COM Positive voltage output to be used as common terminal of the contacts connected to the inputs SUPPLY Power supply input 24 Vac dc 20 refer to the shown polarity when supplied by a dc source SERIAL PROGRAM Connector for the serial programming trough a PC OUTPUT CONTACTS N O Relay output contact for external alarm device e g siren N C Relay output contact for external al...

Страница 4: ...the STROBE activation the message related to the binary code currently applied to inputs 1 8 will be removed INS This terminal allows the electrical insulation of the inputs see next paragraph connect this terminal to 0V of the external voltage source used to supply the input terminals COM Positive voltage output to be used as common terminal of the contacts connected to the inputs SUPPLY Power su...

Страница 5: ...se of the figure on the right side and connect the 0 volt terminal of the external supply source to the terminal INS of DISP2 If the electrical insulation is not needed use terminal COM to supply the external contacts connected to the inputs and move the jumper as shown in the second case of the figure The factory setting of this jumper is for NO electrical insulation 4 OUTLINE DIMENSION PANEL HOL...

Страница 6: ... input 8 is the most significant bit this means that each code is related to a well defined message The amount of message in this mode is 255 The setting of the direct binary mode can be done only by the configuration program DISPTools running on the PC ALARM OUTPUTS Each message of DISP2 regardless of direct or binary mode may be set to cause or less the activation of the 2 centralized alarm outp...

Страница 7: ...he same time the buttons and move in the menu until the BUZZER OPTION is reached using the buttons and To modify the displayed option refer to paragraph 8 1 The setting of this option can be done through the keyboard on DISP2 front panel or by the configuration program DISPTools running on the PC CYCLE TIME This parameter identifies the time between the displaying of a message and another one Allo...

Страница 8: ... first message after the alarm pending message is the first occurred event the next one is the second and so on The number on the bottom left side in the alarm pending message is the total amount of messages in the queue DISP2 can store up to 64 message in chronological order 7 1 Pushbuttons function and keyboard lock The 6 pushbuttons on the front panel during normal operation and regardless of t...

Страница 9: ...RY mode has been selected NOM the displayed messages show in direct mode the current condition of the inputs in the chronological order they occurred In binary mode instead the message related to the binary code currently applied to the inputs will be displayed If the MEMORY mode has been selected MEM the displayed message show the inputs or binary codes that have been activated from last reset se...

Страница 10: ...ecause in the edit mode a cursor under the current character to be edited is shown the cursor is a small line under the character the cursor is not displayed during searching mode Note direct binary and centralized alarm outputs options cannot be changed from the DISP2 keyboard these options can be changed by the PC only see next paragraph In the searching mode the pushbuttons perform the followin...

Страница 11: ... two connectors are pin to pin pin 1 to pin 1 pin 2 to pin 2 and so on all pins must be connected The operating parameters options and messages of DISP2 can be fully programmed by the PC in addition the reverse operation can be also performed so it is possible to read all parameters options and message stored in the DISP2 The PC must be equipped with a program named DISPTools and free distributed ...

Отзывы: