Contatto
ModKB
When the ModKB receives a message from the keyboard,
it verifies that the SITE code is correct, then verifies that
the entered PIN code is one of those stored; if everything
matches, before allowing access, ModKB module also
evaluates the following parameters related to that PIN:
•
the day of the week when the access is allowed
•
the two time slots when the access is allowed
If all the listed conditions have satisfied, then the ModKB
module generates a pulse on the relay in order to activate
the electrical door lock or other similar device.
Moreover, whether those conditions have been satisfied or
not, ModKB will send on the bus some information related
to the recognized PIN as described below.
Information from and to ModKB module
ModKB module takes, inside the
Contatto
system, one in-
put and one (optional) output address with the same value.
The output address, if it is not needed, can be disabled dur-
ing the setting up.
Input section
The input address provides four 16-bit channels, used as
described in the following.
Input channel 1: digital inputs
Point
Description
1
Generic input 1 status (1=activated)
2
Generic input 2 status (1=activated)
3
-
4
-
5
-
6
-
7
-
8
-
9
Wrong SITE code
10
Wrong PIN code
11
Access denied for not allowed day of the week
12
Access denied for not allowed time slot
13
-
14
-
15
-
16
-
The
points 1 and 2
report the status of the two generic in-
puts of ModKB module. The logic of the contacts connec-
ted to these inputs depends on the NC/NO configuration
which has been chosen, during the setting up, for each one
of them. If the input has been configured as NC, then the
status on the bus will be 1 when the contact is opened; if
the input has been instead configured as NO, the the status
will be 1 when the contact is closed.
The
points 9
÷
12
will be activated when ModKB module
denies the access for one of the reasons described above.
The information related to these points remains for the time
set in the configuration panel of ModKB (Code Perman-
ence, 5 seconds typical value).
Input channel 2: entered code
This channel shows the last PIN code typed on the keypad;
this code remains in this channel for the set time (Code
Permanence) then it returns to zero.
Input channel 3 and 4: valid PIN codes
These channels report 30 mutually exclusive points, each
one corresponding to the occurred recognition of one of the
30 PIN code set in ModKB. The point related to the last val-
id entered code remains active for the set time (Code Per-
manence), then it returns to zero.
Point
CH3
CH4
1
PIN 1 OK
PIN 17 OK
2
PIN 2 OK
PIN 18 OK
3
PIN 3 OK
PIN 19 OK
4
PIN 4 OK
PIN 20 OK
5
PIN 5 OK
PIN 21 OK
6
PIN 6 OK
PIN 22 OK
7
PIN 7 OK
PIN 23 OK
8
PIN 8 OK
PIN 24 OK
9
PIN 9 OK
PIN 25 OK
10
PIN 10 OK
PIN 26 OK
11
PIN 11 OK
PIN 27 OK
12
PIN 12 OK
PIN 28 OK
13
PIN 13 OK
PIN 29 OK
14
PIN 14 OK
PIN 30 OK
15
PIN 15 OK
-
16
PIN 16 OK
-
Output section
On the output address, if it has been enabled during the
ModKB setting up, four 16-bit channels are available; the
following tables shows the arrangement:
Point
CH1
CH2
CH3
CH4
1
Relay pulse
-
PIN 1 lock
PIN 17 lock
2
-
-
PIN 2 lock
PIN 18 lock
3
-
-
PIN 3 lock
PIN 19 lock
4
-
-
PIN 4 lock
PIN 20 lock
5
-
-
PIN 5 lock
PIN 21 lock
6
-
-
PIN 6 lock
PIN 22 lock
7
-
-
PIN 7 lock
PIN 23 lock
8
-
-
PIN 8 lock
PIN 24 lock
9
-
-
PIN 9 lock
PIN 25 lock
10
-
-
PIN 10 lock
PIN 26 lock
11
-
-
PIN 11 lock
PIN 27 lock
12
-
-
PIN 12 lock
PIN 28 lock
13
-
-
PIN 13 lock
PIN 29 lock
14
-
-
PIN 14 lock
PIN 30 lock
15
-
-
PIN 15 lock
ALL lock
16
-
-
PIN 16 lock
-
Activating the
point 1
of CH1, ModKB module generates a
pulse on the internal relay, whose duration can be fixed
during the setting up; only one pulse will be generated even
if the output point 1 remains in active status or less.
DUEMMEGI
s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 –
www.duemmegi.it
Rel.: 1.1 July 2012
Page 3 of 6