Air calibration

For the system to work correctly, it needs to be configured� This will ensure its operation is as quiet as possible and energy-ef-

ficient� For information on determining the ventilation flow rates, see Instruction Sheet Checking Product References and Flow 

Rates at www�duco�eu�

07.A 

Air calibration procedure for DucoBox Focus

The air calibration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling, 

feeling the wind in one’s face)�

DucoBox Focus air calibration

1

The exhaust vents must be set depending on the situation� Proper pre-setting makes for rapid and correct configuration�

SITUATION 1 : 

one vent per valve

Set all vents to the fully open 

position, regardless of the desired 

flow rate�

SITUATION 2 : 

Multiple vents per valve 

with equal flow rates

Set all vents to the fully open 

position, regardless of the desired 

flow rate� Set the valve to the 

sum of the vent flow rates via the 

display menu or the Duco Network 

Tool� Example: 2 vents, 50 m³/h 

each → set valve to 100 m³/h�

100

m

3

/h

+

=

SITUATION 3 : 

Multiple vents per valve 

with different flow rates

Set the exhaust vents so they 

match the desired flow rate in line 

with the table below� Set the valve 

to the sum of the vent flow rates 

via the display menu or the Duco 

Network Tool� Example: 25 m³/h 

vent and 75 m³/h vent → set valve 

to 100 m³/h�

100

m

3

/h

+

=

When using DucoVent Design exhaust vents always leave 

the outer ring in place for acoustic effect�

Flow rate

DucoVent 

Design

DucoVent Basic

and other vents

75m3/h

100% open

50m3/h

50% open

25m3/h

25% open

Содержание DucoBox Focus

Страница 1: ...SH L2000631 Installation guide for DucoBox Focus Revision L 06 09 2022 Installation guide ENGLISH DucoBox Focus Product version 17xxxx and above L2000631 Revision L 06 09 2022 Step by step instructions duco tv ...

Страница 2: ...aller User mode 9 06 B LED indications DucoBox Focus 9 06 C Pairing components 9 06 D Removing replacing components 11 06 E Tips 11 07 Air calibration 12 07 A Air calibration procedure for DucoBox Focus 12 07 B Checking 13 08 Maintenance service 14 09 Warranty 14 10 Legislation 15 Vero Duco Handelsstraat 19 8630 Veurne Belgium tel 32 58 33 00 33 info duco eu www duco eu DUCO HANDELSSTRAAT 19 VEURN...

Страница 3: ...content or relative humidity Thanks to integrated control valves air is only exhausted in the zone that requires it On the other hand it is the master or brain of the system It receives and interprets signals from slave components measurements from sensors or manual input on the basis of which it controls the ventilation system It is inadvisable to connect the DucoBox via a duct or directly to an ...

Страница 4: ... Or an equivalent based on a specific duct calculation p e for ducts placed in floor screed Make sure that the total counter pressure in the ducts is as low as possible preferably 150Pa and that the airspeed in every duct does not exceed 3 m s installation tips duct system DucoBox Silent Focus en 1 7 8 9 10 2 3 4 5 6 DISCLAIMER no rights can be derived from this document All tips are only advisory...

Страница 5: ...ed 25 RF Tronic vent Tronic vent 230 VAC 230 VAC DucoBox Focus 30 cm A B The power supply is to be determined depending on the technical data sheet for each component see www duco eu The power rating of all individual components needs to be checked The power supply needs to be capable of coping with the sum of these requirements with a cable length not exceeding 300 m RF obstacle free zone Do not ...

Страница 6: ... mm cable which can be connected via a splicing terminal block DUCO WIRED Power supply 24 VDC Wiring 5 x 0 75 mm 5 x 0 25 mm from Tronic window ventilators Maximum distance up to 300 m Maximum number of components Up to 99 wired components in a single system 04 Control valves The control valves whether or not they are fitted with a sensor for measuring CO or humidity can be built into the DucoBox ...

Страница 7: ... on the DucoBox and control valves will flash green rapidly 3 Long press the button once on the control valve to be removed in order to remove it from the network ATTENTION any underlying components will also be removed from the network 4 Disconnect the wiring from the control valve to be removed and slide it out of the DucoBox 5 Deactivate Installer mode by pressing INST on the DucoBox All LEDs w...

Страница 8: ...ms to communicate via ModBus and or ethernet ModBus integration enables them to be linked to a building management system Disconnect the DucoBox from the power supply before connect ing the Communication Print and follow the instructions in the manual included with the Communication Print ModBus Ethernet Micro SD card PWM OUT PWM IN Switch Contact 1 n133 Switch Contact 2 n134 Switch Contact 3 n135...

Страница 9: ...or associated components YELLOW blinking slowly Transitional phase please wait YELLOW on Initialising system configuration in progress WHITE or OFF Normal BLUE Component is displayed if changes are being put through via the master ORANGE The system is not working correctly because the DucoBox has not been calibrated Restart the DucoBox Follow the guidelines in 10 essential tips if the problem recu...

Страница 10: ...Activate Installer mode by tapping INST on the DucoBox The LED will flash green rapidly 2 Pairing components on the DucoBox Use this method for any components that are required to control the entire system e g a master user control 2a Tap on the button of the component to be paired once while the LED on the DucoBox is flashing rapidly The LED on this component will flash red briefly and then start...

Страница 11: ...ly or using the palm of your hand on a control featuring touch buttons The LED will turn white Replacing a component 1 Activate Installer mode by long pressing 2 diagonal buttons on a paired control The LED will flash green or yellow rapidly 5 sec 2 Briefly press twice on the button of the component to be replaced 2x OLD 3 Tap once on the button of the new component The latter will take on all set...

Страница 12: ...n SITUATION 1 one vent per valve Set all vents to the fully open position regardless of the desired flow rate SITUATION 2 Multiple vents per valve with equal flow rates Set all vents to the fully open position regardless of the desired flow rate Set the valve to the sum of the vent flow rates via the display menu or the Duco Network Tool Example 2 vents 50 m h each set valve to 100 m h 100 m3 h SI...

Страница 13: ...red automatically on start up Calibration takes 30 seconds 1 minute per connected control valve Iteration Rev Date Name Description 23 Nov 17 Status Date Status STEKKER_STOPCO mm dm m kg m mm Handelsstraat 19 8630 VEURNE tel 0032 58 330033 fax 0032 58 330044 email info duco eu www duco eu This drawing is property of Vero Duco NV and can not be copied neither shown to third party externally without...

Страница 14: ...se contact your Duco products seller Keep the serial number of your product to hand 09 Warranty All warranty conditions concerning the DucoBox and Duco s ventilation systems can be found on the DUCO website All complaints are to be reported to Duco by the Duco distributor with a clear description and the order invoice number under which the products were delivered In order to register the complain...

Страница 15: ...15 ENGLISH L2000631 Installation guide for DucoBox Focus Revision L 06 09 2022 10 Legislation Product card EC declaration of conformity and energy labels can be viewed and downloaded at www duco eu ...

Страница 16: ...16 ENGLISH L2000631 Installation guide for DucoBox Focus Revision L 06 09 2022 Installed by L2000631 Document last modified on 06 09 2022 revision L ...

Отзывы: