13HPD SPLIT SYSTEM HEAT PUMP
WITH DRY NITROGEN HOLDING CHARGE
INSTALLATION / START−UP INSTRUCTIONS
These instructions must be read and understood completely before attempting installation.
TABLE OF CONTENTS
Shipping and Packing List
. . . . . . . . . . . . . . . . . . . . . .
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque Requirements
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement
. . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves
. . . . . . . . . . .
Recovering Refrigerant from Existing System
. . . . . . .
New Outdoor Unit Placement
. . . . . . . . . . . . . . . . . . . . .
Replacement Line Set
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Brazing Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Existing Metering Device and Flushing Line
Set and Indoor Coil
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing Indoor Metering Device
. . . . . . . . . . . . . . . .
Leak Test Line Set and Indoor Coil
. . . . . . . . . . . . . . .
Evacuating Line Set, Indoor Coil and Outdoor Unit
.
Electrical Connections
. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Outdoor Unit Delivered Void of Nitrogen
Charge
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−up and Weigh−In Charging
. . . . . . . . . . . . .
Optimizing System Charge
. . . . . . . . . . . . . . . . . . . . . .
System Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist
. . . . . . . . . . . . .
WARNING
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation
MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code
NFPA 70/ANSI C1−1993 or current edition and Canadian Electrical Code Part 1 CSA C22.1.
CAUTION
Improper selection of a matching indoor unit and a matching metering device, improper installation, adjust-
ment, alteration, service or maintenance may void the warranty. The qualified installer or agency must use
factory−authorized kits or accessories when modifying this products. Refer to the individual instructions
packaged with the kits or accessories when installing.
NOTE
These instructions are intended as a general guide and do not supersede national, state or local codes in any way.
These instructions must be left with the property owner.
This unit is factory−charged with dry nitrogen. The unit is intended for installation in existing HCFC−22
systems. Carefully follow all installation procedures.
NOTICE TO INSTALLER