Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
1. Install line voltage power supply to unit from a properly
sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is provided in the
bottom of the control box. Connect conduit to the
control box using a proper conduit fitting.
NOTE − Units are approved for use only with copper
conductors. 24V, Class II circuit connections are
made in the low voltage junction box (see figure 12).
NOTE − A complete unit wiring diagram is located
inside the unit control box cover.
NOTE − For proper voltages, select thermostat wire
gauge per the following chart:
Wire run length
AWG #
Insulation type
less than 100’ (30m)
18
color−coded, temperature
rating 35
º
C minimum
more than 100’ (30m)
16
3. Install room thermostat (ordered separately) on an
inside wall approximately in the center of the
conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it
can be effected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit (see figure 12).
R
C
W1
Y1
O
G
R
C
W1
W2
W3
G
REVERSING VALVE
THERMOSTAT
INDOOR
UNIT
R
C
W1
Y1
O
OUTDOOR
UNIT
POWER
COMMON
FIRST STAGE
AUXILIARY HEAT
INDOOR BLOWER
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
FIRST STAGE
AUXILIARY HEAT
COMMON
POWER
HEAT PUMP WITH AIR HANDER
AND ELECTRIC HEAT
E
L
Figure 12. Typical Low Voltage Connections