LED Indicators

Two Status LED indicators, one red and one green are provided 

on the control panel of all models equipped with the Spectron 
option

Red Service Alert LED

Under normal operating 

conditions, the Service 

Alert LED indicator will 

remain off.  In the event the

Spectron Controller detects

 a malfunction, the Service Alert LED will blink at a 1 Hz. 
rate based on the following table:

Red Status LED Code 

Description

One blink ON/pause 

Battery not connected  

Two blinks ON/pause 

Battery fault

Three blinks ON/pause 

Charger fault

Four blinks ON/pause 

Transfer circuit fault

Five blinks ON/pause 

Emergency Lamp Fault

Green Operating Status LED

The green Operating Status 

LED serves as both an AC 

power and a self-test 

indicator. During normal 

operation, the Operating 

Status LED will be illuminated indicating the presence of 

AC power.  During all automatic or manual self-test cycles, 

the Operating Status LED will blink at a 1 Hz. rate.

Manual Tests

Using the unit test switch, users can initiate different duration test 
cycles based on the following table:

Initiating Action 

Test Cycle

Press test switch once 

1 minute

Press test switch twice 

5 minute

Press test switch 3 times 

30 minute

Press test switch 4 times 

60 minute

NOTE:

  Pressing test switch at any time after a test cycle has begun 

cancels remainder of test and returns unit to normal operation.

Spectron

®

 

 

Self-Diagnostic Electronics Option

Lamp Sensing Adjustment Procedure

Procedure 1 - LZ15

I

, LZB15

I

 Models Only

LZ15

I

 and LZB15

I

 Spectron models are shipped from the factory 

with a load sensing jumper provided as shown in position "A" 

of the illustration below.  In this position, the  diagnostic circuitry 

can sense a failure in any of the unit's three connected lamps  

(2 integral and 1 remote).

IMPORTANT

  

If the third (remote) lighting head is not to be connected (for the 
purpose of extended run time or other reasons), the load sensing 
jumper must be reinstalled as shown in Position "B" below to 
prevent a false lamp failure indication.  

Procedure 2 - All Other Remote Capacity 

Models 

Remote capacity models provide sufficient battery power to 

operate the unit's two integral lighting heads plus one or more 

remote lighting fixtures.  In order for the electronics module to 

detect a lamp failure in any of the connected fixtures, the lamp 

sensing circuit must be adjusted in the following manner:

NOTE:

 Models without remote fixture capacity are supplied 

with the lamp sensing circuit factory set and do not require 

this procedure.

1.

  Depending on the total amount of connected load, one of 

four different "RANGE"  switch settings will need to be selected 

(See Fig. 1).  Calculate the total connected wattage load and 

refer to the RANGE Switch Selector Chart below to determine 

the appropriate setting.

IMPORTANT:

 In calculating total connected wattage load,  

be sure to include the unit's two integral lighting heads.

RANGE Switch Selector Chart

Operating Instructions

Spectron Electronics

All models ordered with the Spectron® option provide:

  Visual indication of AC power status

  Visual Indication of all self-diagnostic test cycles

  Visual indication of unit malfunctions including:

   

• Battery fault

   

• Charger fault

   

• Transfer fault

   

• Lamp fault

  User initiated test cycles of 1, 5, 30 or 60 minutes

  Temperature compensated charger for longer battery life 

  15 minute retransfer delay 

Load Jumper Settings

 

"A"

(3 Lamp Position)

"B"

(2 Lamp Position)

operating status

on = ready
off = ac off
blinking = test in process

Total Connected 

Load Wattage

Load "RANGE" 

Switch Setting

15

1

16 - 30

2

31 - 45

3

46 - 60

4