DUAL LITE SEMPRA SEWL Series Скачать руководство пользователя страница 1

Severe Conditions Die-Cast

Aluminum LED Exit Sign

Installation Instructions

 SEWL Series

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com 

Copyright

©

 Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.

  

 

93016017 D  

  

2/19

Self-Testing/Self-Diagnostic Models

All models ordered with the Dual-Lite Spectron  

self-testing/self-diagnostic electronics system provide:

 

Visual indication of AC power status

 

Visual indication of all self-diagnostic test cycles

 

Visual indication of unit malfunctions including:

 

 

Battery fault

 

 

Charger fault

 

 

Transfer Fault

 

 

Lamp fault

Bi-Color LED Status Indicator

Self-testing/self-diagnostic units are provided with a 

single, bi-color LED which serves as a combination AC 

power, self-test and service alert status indicator. During 

normal operation, the green status LED will be constantly 

illuminated, indicating the presence of AC power. During 

all automatic or manual self-test cycles, the green Status 

LED will blink at a one cycle per second rate indicating 

“Test In Progress". If a fault condition is detected during 

any automatic or manual self-test cycle, upon comple-

tion of test, the red status indicator will provide a “service 

alert code” – see table below.

Service Alert Code

Description

One blink ON/pause

Battery not connected

Two blinks ON/pause

Battery fault

Three blinks ON/pause

Charger fault

Four blinks ON/pause

Transfer circuit fault

Five blinks ON/pause

Lamp failure

Manual Test

Using the unit test switch, users can initiate different 

duration test cycles based on the following table:

To Initiate Action:

Test Cycle

Press switch once

1 minute

Press switch twice

90 minute

Pressing test switch at any time after a test cycle has 

begun cancels the remainder of test and returns the 

unit to normal operation. 

(NOTE: Batteries are often 

shipped in a discharged state – this is normal – battery 

requires charging. Allow several hours of charge before 

testing unit.)

Spectron units also provide:

Brownout protection – unit transfer to emergency mode 

with low AC input voltage.

Time Delay Re-transfer – unit will remain in emergency 

mode for additional time after AC power is restored.

TROUBLESHOOTING

AC-On Light does not illuminate

• Check AC wiring connections

Emergency LEDs do not work

• Battery is shipped disconnected. Connect leads from  

  battery to charger PCB and charge before testing.

• Make sure connections to charger board are properly  

  seated.

• Check wiring connections.

Maintenance

Exit signs should be tested and maintained in accor-

dance with National Electrical Code and NFPA 101 Life 

Safety Code requirements. It is recommended that exit 

signs be tested for a minimum of 30 seconds once a 

month and 90 minutes once a year.

The automatic monthly tests of the Spectron units satisfy 

this requirement. The required annual test can be initi-

ated manually with the test switch, as required by the 

safety code.

RECYCLING INFORMATION

All aluminum components are recyclable.

All cartons contain recycled materials. 

Please recycle.

NOTICE:

Exit signs contain rechargeable batteries which must be  

recycled or disposed of properly.

Use CAUTION when handling batteries.

LED REPLACEMENT

(Contact factory)

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed including the following.

READ AND FOLLOW ALL SAFETY 

INSTRUCTIONS

  1.  Do not let power supply cords touch hot surfaces.
  2.  Do not mount near gas or electric heaters.
  3.  Equipment should be mounted in locations and at heights where it will not readily be subject to tampering by 
     unauthorized personnel.
  4.  The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
  5.  Do not use this equipment for other than its intended purpose.
  6.  Service of this equipment should be performed by qualified service personnel.

SAVE THESE INSTRUCTIONS

93021636

93021638

93021640

93021641

93021643

93021644

93021645

93021646

WARNING

 – This product contains chemicals known to the State of California to cause cancer, birth defects and/

or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this 
product.

93021636

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when 
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful 
interference in which case the user will be required to correct the interference at his own expense.

Отзывы: