Self-exiting generators respond to severe overload-
ing differently than utility power.  When overloaded, 
the engine is not able to supply enough power to 
bring the electric motor up to operating speed.  the 
generator responds with high initial starting current, 
but the engine speed drops sharply.  The overload 
may stall the engine.  If allowed to operate at very 
low speeds, the electric motor starting winding will 
burn out in a short time.  The generator winding 
might also be damaged.

CAUTION:  EQUIPMENT DAMAGE

    

RUNNING THE GENERATOR SET UNDER 

THESE CONDITIONS MAY RESULT IN DAMAGING 
THE GENERATOR STATOR AS WELL AS THE MO-
TOR WINDING.

Because the heavy surge of current required for 
starting motors is required for only an instant, the 
generator will not be damaged if it can bring the 
motor up to speed in a few seconds of time.  If dif-
fi culty is experienced in starting motors, turn all other 
electrical loads off and if possible reduce the load on 
the electric motor.

PREPARING THE UNIT

UNPACKING

CAUTION:  EQUIPMENT DAMAGE

    THIS UNIT HAS BEEN SHIPPED WITHOUT OIL.  
Failure to maintain the engine oil at the proper level 
will result in serious engine damage.

When you unpack your new engine-generator set be  
sure to remove all the information sheets and manu-
als from the carton.

1.  This generator-set was in good order when 
shipped.  Inspect the generator-set promply after 
receiving it.  If any damage is noted, notify the trans-
portion company immediately; request proper pro-
cedures for fi ling a “concealed damage” claim.  Title 
to the equipment and responsibility for fi ling a claim 
rests with you when a generator-set is sent F.O.B. 
shipping point.  Only you can legally fi le a claim.

2.  Before proceeding with the prepartions of your 
new generator-set for operation, take a couple of 
minutes to insure the unit you have received is the 
correct model and review the specifi cation pages in 
this manual to insure that this unit meets your job 
requirements.

UNIT PREPARATION

Before your generator-set was shipped from our 
factory it was fully checked for performance.  The 
generator was load tested to its full capacity, and the 
voltage and frequency were carefully checked and 
adjusted.

LUBRICATION

Before starting the engine, fi ll the crankcase to the 
proper level with a good quality oil.  The recom-
mended grade of oil and quantity of oil required is 
listed in the engine operator’s manual.  The neces-
sity of using the correct oil, and keeping the crank-
case full cannot be overemphasized.  Engine failures 
resulting from inadequate or improper lubriant are 
considered abuse and not coverd by the the genera-
tor or engine manufacture’s warranty.

GASOLINE

When using gasoline always use a good grade of 
unleaded fuel.  This engine is certifi ed to operate on 
unleaded gasoline with a pump octane rating of 86 
or higher.  Gasoline containing no more than 10% 
ethanol (E10) or 5% methonal by volume may be 
used.  In addition methanol must contain cosolvents 
and corrosion inhibitors.  Use of fuels with content 
of ethanol or methanol greater than shown above 
may cause starting and/or performance problems.  
Always insure that the fuel is clean and free of all 
impurities.

WARNING:  FIRE DANGER

    Gasoline and its fumes are VERY explosive when 
proper precautions are not taken.

Never use gasoline that has been stored for an ex-
tended period of time as the fuel will lose it’s volatile 
properties and you will be left with only the varnish 
residue.  The varnish like substance will clog the 
carburetor and will not burn properly.

The use of fuel additives, such as STA-BIL, or an 
equivalent will minimize the formation of fuel gum 
deposits.  If a a unit has been out of operation for 
an extended period of time it is best to drain old fuel 
from the engine and replace with fresh fuel before 
attempting to start.

OIL ALERT SYSTEM

The Oil Alert system is designed to prevent engine 
damage causes by insuffi cient amount of oil in the 
crankcase.  Before the oil level in the crankcase can 
fall below a safe limit, the Oil Alert system will auto-
matically stop the engine.  

Содержание Winco W3000H

Страница 1: ...1 1203 00 60706 220 INSTALLATION AND OPERATORS MANUAL INDUSTRIAL PORTABLE W3000H...

Страница 2: ...UNIT Unpacking the Unit 5 Unit Preparation 5 Initial Start Up 6 Basic Operation 6 ENGINE CARE 7 GENERATOR CARE 8 TROUBLESHOOTING 9 WARRANTY INFORMATION 10 MAINTENANCE LOG 11 PROPER USE AND INSTALLATIO...

Страница 3: ...e earth 2 FIRE HAZARD Gasoline and other fuels pres ent a hazard of possible explosion and or fire a Do not refuel when the engine is running or hot b Keep fuel containers out of reach of children c D...

Страница 4: ...attempt to operate at 50 cycles These units are designed and governed to operate at 60 cycles only UNIT CAPABILITIES GENERATOR CONNECTIONS This generator is designed for 120 volt alternating current...

Страница 5: ...this unit meets your job requirements UNIT PREPARATION Before your generator set was shipped from our factory it was fully checked for performance The generator was load tested to its full capacity a...

Страница 6: ...ditive such as STA BIL or an equivalent will minimize the formation of gum depos its during storage Such an addative may be added to gasoline in the engines fuel tank or to gasoline in a storage conta...

Страница 7: ...appliances will have the volt age and amperage requirements on their individual nameplates When in doubt consult the manufac turer or a local electrician The nameplate amperage rating for electric mot...

Страница 8: ...cessary to ensure a long trouble free life 1 Exercising The Generator The generator should be operated every three to four weeks It should be operated for a period of time sufficient to warm the unit...

Страница 9: ...overloaded Defective stator Defective rotor field Circuit Breaker Defective load Trips Defective receptacle Voltage too high Engine speed is too high Generator Overloaded overheating Insufficient vent...

Страница 10: ...r or to WINCO Inc at LeCenter Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability and fitness for a particular purpose...

Страница 11: ...11 1203 00 60706 220 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 12: ...1203 00 12 60706 220 225 S CORDOVA AVE LECENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831...

Отзывы: