Notice the preceding tables give two (2) different units of measur-
ing fuel pressure.  The first is with a pressure gauge calibrated in
ounces per square inch.  The second and most accurate is the
use of a simple water manometer.  A manometer is calibrated in
inches of water column.

LP LIQUID WITHDRAWAL SYSTEMS

When installing a unit equipped the LP liquid withdrawal a
primary regulator is not required on the supply tank.   The supply
line is connected to a liquid withdrawal valve on the supply tank
and runs directly to the fuellock strainer mounted on the engine
generator set.  Normally a 3/8 inch copper line is acceptable for
this type of fuel installation.  You must be sure that the valve you
have connected to on the supply tank is in fact a liquid supply
valve and has a drop tube inside the tank that is pulling fuel from
the bottom of the supply tank.  Before starting the unit you must
confirm that you have a good liquid supply at the unit.  Engine
generator sets equipped for liquid withdrawal will not run
properly when supplied with high pressure vapor fuel.

LUBRICATION

Before starting the engine, check the oil level in the crankcase. If
it is low, refill to the full mark with the proper weight/grade of oil as
recommended by the engine manufacturer’s maintenance
instructions.  The necessity of using the correct oil, and keeping
the crankcase full cannot be over emphasized.  Failure to use the
proper oil and keep the crankcase properly filled will cause
excessive engine wear and shorten its useful life.

COOLANT

Before starting the engine, check the coolant level in radiator. If it
is low, refill as specified in the engine manufacturer’s mainte-
nance instructions.  The radiator should be filled to about 1 inch
below the filler neck. For additional information on engine coolant
requirements see engine manufacturer’s maintenance instruc-
tions.

INSTALLING THE BATTERY

****  CAUTION  ****

In the following battery installation procedure, check to be sure
the selector switch remains in the “stop” position. This should be
your last step before initial start-up.

A customer supplied twelve-volt battery is required to complete
the installation.  Installation of the highest CCA rated battery,
within the correct BCI group, will increase cold weather starting
performance.  Gel batteries should not be used with the battery
tender installed in the generator enclosure.

MINIMUM

Model

Voltage

BCI Group CCA Rating

PSS27LS

  12

24

650

PSS40LS

  12

24

650

Installation and servicing of batteries must be performed or
supervised only by personnel knowledgeable of batteries and the
required precautions.  Keep unauthorized personnel away from
batteries.

When installing or replacing batteries, use the proper group/size
starting battery.  The battery should be a Maintenance Free lead
acid design.  Deep cycle batteries will not  work for this applica-
tion.

CAUTION – PERSONAL DANGER

CAUTION - NEVER dispose of a battery in a fire. The battery is
capable of exploding.

CAUTION - DO NOT open or mutilate the battery.  Released
electrolyte is known to be harmful to the skin and eyes and to be
very toxic.

These engine generator sets are all NEGATIVE ground.  Be very
careful not to connect the battery in reverse polarity, as this may
short circuit the battery charging system on the engine.

CAUTION – A battery presents a risk of electrical shock and high
short circuit current. The following precautions must be observed
when working with batteries.

1.

Remove watches, rings and other metal objects.

2.

Use tools with insulated handles.

3.

Check both the battery cable ends and the battery posts to be

sure they are free of corrosion.
4.

Always connect the battery positive cable first and then

connect the battery negative cable.  When removing the battery
cables from the battery reverse the procedure, disconnect the
negative cable first and then the positive cable.
5.

Be sure all connections are tight and coat the terminals and

cable end with dialectic grease.

WARNING – The electrolyte is a diluted sulfuric acid that is
harmful to the skin and eyes.  It is electrically conductive and
corrosive.  The following precautions must always be taken.

*

Always wear full eye protection and protective clothing

*

Where electrolyte contacts the skin, wash off immediately

with water.
*

If electrolyte contacts the eyes, flush thoroughly and immedi-

ately with water and seek immediate medical attention.
*

Spilled electrolyte is to be washed down with an acid neutral-

izing agent.  A common practice is to use a solution of one pound
of bicarbonate of soda (baking soda) to one gallon of water.  The
bicarbonate of soda solution is to be added until the evidence of
reaction, foaming, has ceased.  The resulting liquid is to be
flushed with water and the area dried.

DANGER – Explosive Fire Risk

*

Never smoke when near batteries

*

Do not cause a flame or spark in the battery area

*

Always discharge static electricity from your body before

touching batteries by first touching a grounded metal surface.

SERVICING BATTERIES

Batteries used on these units may over time lose water.  This is
especially true if you are using a trickle charger to maintain your
battery.  When refilling the battery with water use only distilled
water.  Tap water will shorten the service life of the battery.

Содержание Winco PSS27LS/D

Страница 1: ...PSS40LS Engine Generator Set PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS27LS D PSS40LS C...

Страница 2: ...SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions in...

Страница 3: ...electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or...

Страница 4: ...4 Industrial four cylinder liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles varia...

Страница 5: ...temperature battery voltage speed engine load coolant level from ECU ECU specific parameters and run time statistics A Liquid Crystal Display The backlit 64 by 128 pixel LCD serves as the local infor...

Страница 6: ...e system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to enter Password OP as fol...

Страница 7: ...uld the instructions or information provided be interpreted to conflict with any local state or national codes If in doubt always consult your local fire marshal or gas supplier WARNING FIRE HAZARD Al...

Страница 8: ...d from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible obstru...

Страница 9: ...rformed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper gr...

Страница 10: ...t Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition CONNECTING THE BATTERY CHARGER BLOCKHEATER A two...

Страница 11: ...nect your ground wire from the transfer switch to The lugs on the 40 kW will handle wire sizes 6 AWG to 250 MCM and should be torqued to 250 in lbs The lugs on the 27 kW will accommodate 6 AWG to 250...

Страница 12: ...tart relay is closed again F CUSTOMER REMOTE STOP LIGHT This set of terminals can be use to light a 12 volt remote light to indicate that the unit is in emergency stop The terminal blocks are designed...

Страница 13: ...nd a solid neutral connection The voltage between G1 and G N should be about 120 volts AC 277 on 480 units The same approximate voltage should be found between terminals G3 and G N 120 volts AC On thr...

Страница 14: ...OUTPUT FROM GENERATOR 1 Defective diode 2 Defective voltage regulator 3 Defective rotor 4 Defective stator 5 Defective exciter rotor 6 Defective exciter stator 7 AC short in the output leads 8 Defecti...

Страница 15: ...s the solenoid opens the pressure should rise to 2 5 to 3 oz just as the engine starts to crank If it is within this range replace the cap on the column If not adjust the screw down to increase and up...

Страница 16: ...Page 14 7263 00 60706 188 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS...

Страница 17: ...60706 188 Page 15 7263 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS...

Страница 18: ...Page 16 7263 00 60706 188...

Страница 19: ...60706 188 Page 17 7263 00 PSS40LS 27LS OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES...

Страница 20: ...e are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on t...

Отзывы: