background image

You can select two audible signals for each Alarm Input- with 
the exception of the Internal Tamper Input which has only one 
audible signal (up-scale modulated frequency between 800 
and 2000 Hz)
The audible signals and modulated frequency range can be 
found in the "PROGRAMMING" section.
There are two frequency ranges: 800/2000 Hz and 1100/2400 
Hz.
The audible signalling will stop as soon as the maximum Alarm 
Time expires, whereas, the visual signalling will continue until 
the Alarm conditions clear (Memory Flashing).
The Memory and Alarm flash sequences (Flasher bulb ONLY)
are as follows:

ON (ms)

OFF (ms)

Alarm flashing

250

750

Memory flashing

250

1500

Under low battery conditions, this SIREN will bypass the 
strobe / flasher and use the residual charge to power the hom 
-- this status will be signalled on terminal [G].
The Open-Collector Terminal [G] (dosed to ground during 

Fig. 2

 - Board Components

T

G

GND

AS

MODE

B

0

0

3

Wire
Jumpers

LAMP

Link
Jumpers

SP

AS

ASG

G

A

IN

RCS NER

S

P

A

+

N

standby status) will disconnect in the event of low battery or damage to the hom or flasher bulb.
If you remove the on-board Jumper [G] (inserted at factory) Alarm signalling will be inhibited, and only 
Trouble conditions will be signalled.
Flasher trouble -- the horn will sound twice
Horn trouble -- the flasher will blink twice
Battery trouble -- the horn will sound once and the flasher will blink once
No trouble (OK!) -- the horn will sound twice and the flasher will blink twice
The signals will be repeated every 4 seconds until the Jumper is reinserted,
This SIREN will accept a maximum of 6 Alarm signals in 4 minutes after which, it will block the horn for 4 
minutes. This process will protect the SIREN against persistent Alarms generated by the Control panel.

ALARM PRIORITY

This SIREN priodty is as follows:
Alarm signals triggered by the Tamper device will override Alarm signals triggered by terminals [+N] and [A].
Alarm signals triggered by terminal [+N] will override Alarm signals from terminal [A].
Override will generate a variation in the audible signal.

WIRE JUMPERS

Programming

Alarm Sonnd x 

A

Polarity terminal 

A

Alarm sound x 

+N

Jumper

S
P

+N

Connected

Disconnected

LINK JUMPERS

Programming

Trouble signalling

Selection 
antitamper mode

Maximum alarm 
time

Jumper

G

AS(MODE)

AS(GND)

T

Connected

Disconnected

Interruption of trouble signalling

Opening of the as contacts with activation
of hom and strobe/flasher signalling for
internal tamper (Automatic mode)
If t is disconnected the maximum alarm-time will be 3 minutes.
If t is connected the maximum alarm-time will be 10 minutes.

Interruption of alarm signalling to allow
trouble signalling (in test phase only)
Opening of the as contacts without
audible or visual signalling for intemal
tamper (normal mode)

Multitone (HF)
Alarm if connected to 12V
(Negative polarity)
Up and down scale modulation (HF)

Up and down scale modulation (LF)
Alarm if connected to negative
(Positive polarity)
Up and down scale modulation (LF)

Parts

Cover

Cover screw locations (2)

Innerplate screw locations (2)

Protective innerplate

Backplate anchor screw locations (5)

Battery location

Exponential horn

Connector for strobe board or flasher bulb

Connector for tamper device switch

Terminal board

Tamper device

Tamper device bracket

Strobe board

Strobe board screws (2)

Strobe

Cable entry

Alternative flasherbulb

P.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

TAMPER PROTECTION

The Tamper device (to be anchored to the wall) will trigger Alarms when either the frontplate or innerplate is 
removed, or when this SIREN is pulled from the wall (Snatch Tamper). If you setup this SIREN to operate in 
Automatic mode, Tamper signalling will cease 40 seconds after the Alarm conditions clear, or after a 
maximum of 10 minutes (maximum Alarm time).
This SIREN can operate in Normal or Automatic mode. In both modes, the [AS] and [ASG] terminals will 
open in the event of Tamper, thus signalling the condition to the Control panel. If you setup this SIREN to 
operate in Automatic mode, it must be the last peripheral device on the Control panel Tamper line, as the 
[ASG] terminal is closed to negative and cannot be utilized. In Automatic mode, audible and visual signalling 
will be activated automatically by this SIREN (see fig. 3a-b-d). In Normal mode, audible and visual signalling 
will not be activated automatically (see fig. 3c),

ACTIVATION

This SIREN can be activated by the Tamper device, and 
by signals from terminals [+N] and [A].
For example: this SIREN will activate when the voltage 
fails on terminal [+N].
This process will allow the SIREN to detect wire cutting, 
as this Input also supplies the power and battery charge. 
Input Terminal [A] (with programmable polarity) can be 
used for connection to other devices.

SIGNALLING

The audible and visual signals on the horn and strobe / 
flasher depend on the type of Alarm, and the Alarm signal 
configuration.
The sound modulation extremes generate a fastidious 
shrill tone -- intended to discourage intruders, and a low 
tone -- to ensure good audibility. 

2

3

1

3

6

5

7

5

4

11 12

13 14

15 14

16

10

5

9

8

5

5

Fig. 1

17

Содержание EAS-202

Страница 1: ...rong weatherproof polycarbonate moulding Tropicalized steel innerplate 2 Audible and visual signal Inputs Modulated frequency sound emission with sound options High output magneto dynamic exponential horn with test circuit Protected against Tamper Snatch Flasher bulb damage and Wire cutting Programmable maximum Alarm Time Battery Test circuit with Flasher shutdown under low battery or battery trou...

Страница 2: ...nal tamper Automatic mode If t is disconnected the maximum alarm time will be 3 minutes If t is connected the maximum alarm time will be 10 minutes Interruption of alarm signalling to allow trouble signalling in test phase only Opening of the as contacts without audible or visual signalling for intemal tamper normal mode Multitone HF Alarm if connected to 12V Negative polarity Up and down scale mo...

Страница 3: ...ral it will activate the horn and strobe flasher for 30 seconds Table 2 shows how the lower pdority Alarm signal A will activate the horn and strobe flasher after the higher pdority Alarm Alarm signal N has been executed Memory flashing will stop after the maximum Alarm Time when all the signals that triggered the Alarm restore to standby for 5 seconds Restoral Time Internal Tamper Restoral requir...

Страница 4: ...xpires In the latter case the flasher will continue to signal If you apply the Alarm signal to the A terminal with programmable polarity you should connect it to a Control panel terminal that closes with compatible polarity in the event of an Alarm see fig 3d Fig 3 shows a connection using the AS terminals of this SIREN These terminals and the A S terminals of the detector in the wiring diagram wi...

Отзывы: