DSM SUM-40 Скачать руководство пользователя страница 4

 
 
 
 
 

 

R. 171011 

114 Southeast Parkway Ct. 

Ste 160 

Franklin, TN  37064 

Tel: 615/595-6665 

Fax: 615/595-6610

 

Torque-speed performance 

The SUM-40 uses a unique internal drive mechanism that features high direct drive torque and 
true zero-power hold. The motor does not have a traditional “stall torque” in that the maximum 
torque does not increase linearly as the max speed goes to zero. The full torque-speed plot is 
shown below. 
 

 

External torque loads above 100 mNm should not be applied to the system, as this may cause 
backdriving. Backdriving the motor may reduce the overall life of the motor. A backdriving load 
is distinguished from a frictional load in that a backdriving load attempts to cause motion on the 
motor output shaft, whereas a frictional load simply resists motion on the motor output shaft. 
 

Temperature limitations 

The SUM-40 motor is designed as a precision positioning device. As such, it is not capable of 
running at a 100% duty cycle. An internal temperature sensor in the control electronics monitors 
the internal device temperature, and will not allow operation if the internal temperature exceeds 
80 C. The external case does not have an integrated temperature sensor, but should not be 
allowed to exceed 55 C. Refer to the programming documentation for information on querying 
the internal temperature of the SUM-40. Many factors determine the temperature of the SUM-40, 
including duty cycle, mounting conditions, torque load, and external environmental temperature. 
The maximum duty cycle for a particular application is best determined experimentally by 
monitoring the internal and external temperature of the SUM-40 during operation in a 
representative environment. 
 
The table below gives approximate maximum continuous run-times at various rotation speeds for 
an unmounted SUM-40. The table assumes no load operation. This data is provided for reference 
only, and should not be considered as a specification. Actual run times before cooling down must 
be determined in a specific application. 

Отзывы: