057-042 704 Operating Instructions Issue 2.1 18/06/2007 11:27:00 JR - 11 -
FUNCTIONS AND CONFIGURATION TABLE
Function
!
1
!
2
Value (Default in Bold)
Auxiliary Output 1
Function
O
{
{
O
{
{
{
{
Not used
{
{
O
Pre-heat
{
O
{
Engine Running
{
O
O
Common Warning
O
{
{
Common Shutdown
O
{
O
System in Auto
O
O
{
Common Alarm
O
O
O
Energise to Stop
Programmable output can be configured to one of the following.
♦
Pre-heat. - The output is energised for the period of pre-heat time prior to cranking, and between the cranking
attempts.
♦
Engine Running. - The output is active after the saftey timer has elapsed.
♦
Common warning. - The output is active if there are any warning alarm active.
♦
Common shutdown - The output is active if there are any shutdown alarms active.
♦
System in auto. - The output is active when the system is in automatic mode.
♦
Common Alarm. - The output is active if there is any alarm condition.
♦
Energise to stop. - The output is energised when the engine is required to stop (normal or fault conditions), and
will remain energised for the period of the Energise To Stop Timer, to ensure the engine has come to a complete
stop.
Auxiliary Output 2
Function
O
{
{
O
O
{
{
{
Not used
{
{
O
Pre-heat
{
O
{
Engine Running
{
O
O
Common Warning
O
{
{
Common Shutdown
O
{
O
System in Auto
O
O
{
Common Alarm
O
O
O
Energise to Stop
Programmable output can be configured to one of the following.
♦
Pre-heat. - The output is energised for the period of pre-heat time prior to cranking, and between the cranking
attempts.
♦
Engine Running. - The output is active after the saftey timer has elapsed.
♦
Common warning. - The output is active if there are any warning alarm active.
♦
Common shutdown - The output is active if there are any shutdown alarms active.
♦
System in auto. - The output is active when the system is in automatic mode.
♦
Common Alarm. - The output is active if there is any alarm condition.
♦
Energise to stop. - The output is energised when the engine is required to stop (normal or fault conditions), and
will remain energised for the period of the Energise To Stop Timer, to ensure the engine has come to a complete
stop.
Mains Under
Voltage
(Trip / Return)
O
{
O
{
{
{
{
{
60V / 70V
{
{
O
70V / 80V
{
O
{
80V / 90V
{
O
O
90V / 100V
O
{
{
120V / 140V
O
{
O
140V / 160V
O
O
{
160V / 180V
O
O
O
180V /200V
If for example 180/200 is selected the generator will be started and the load transferred if any phase falls below 180V
with respect to the neutral for the duration of the delay start timer. The load will be transferred back to mains when the
mains voltage returns to 200V or higher for the duration of the mains return timer. (The system must be in Auto)