background image

16

MLR2/DVL2A. These four digits overwrite the SG-DRL3-IP receiver and line number before being
sent to the printer and computer. This allows existing DVACS accounts to be sent to the automation
software without alteration and account duplication on the same SG DRL3-IP line card using a differ-
ent line and/or receiver number.

NOTE: If a new account is created, the first four digits must be programmed as ‘0000’.

9.4

T-Link TL300 Programming

Step 1: Program the static IP address for the T-Link TL300 module in section [001].

Program 000.000.000.000 for DHCP.

Step 2:  Program the subnet mask for T-Link TL300 in section [002] if required.

This option will be ignored if the unit is set for DHCP (Section [001])

Step 3: Program the T-Link account number in section [003].

NOTE: The T-Link account number can be up to 10 digits long. If account number is less then 10 digits lead-
ing zeros must be entered.

Step 4: Program the static IP address of the receiver (DRL3-IP line card) in section [007].
Step 5: If the Sur-Gard receiver is on a different network segment than the T-Link TL300 module,

program the gateway address associated with the T-Link TL300 in section [008].

NOTE: This step is optional. Verify with the Network Administrator if this step is required.

Step 6: If a specific dial tone is required for the panel connected to T-Link TL-300 T1/R1, refer to

section [071].

Содержание T-LINK TL250

Страница 1: ...T Link TL250 TL300 Network Internet Alarm Communicator Software Version 1 5 Installation Manual...

Страница 2: ...may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke d...

Страница 3: ...stallation 9 6 2 DVACS Events 9 Section 7 TL300 Telephone Simulation 11 7 1 TL300 Panel Installation 11 7 2 T Link TL300 Operation 11 Section 8 T Link TL250 TL300 Operation 12 8 1 Remote Control 12 8...

Страница 4: ...rovided the recipient agrees to the terms of thisEULA IftheSOFTWAREPRODUCTisanupgrade anytransfermustalso includeallpriorversionsof the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Страница 5: ...Installer Code has changed from CAFE to 5555 for this software version Software Version 1 3 1 5 Supports TL250 and TL300 and all version 1 20 options Supports programmable heart beat interval Section...

Страница 6: ...nected and is intended to be installed by service persons i e having the appropriate technical training and experience necessary to be aware of hazards which that person may be exposed to in performin...

Страница 7: ...h conduit to a junction box if possible 4 Mount the T Link TL250 300 Panel 2 2 Testing Mode 4 Standard Mode Ensure the panel is programmed to use the T Link TL250 in accor dance with the settings outl...

Страница 8: ...can be done only on power up for 30 seconds and only if the reset to factory default is not activated Access the Installer mode using 8 followed by the installer code NOTE The and keys are not support...

Страница 9: ...C enclosure model PC5003C when used in a Bell Follower configuration Refer to section 036 99 Connect the and terminals to the external 12 24Vdc power source NOTE Bell Follower mode can not be used in...

Страница 10: ...uire an external 12VDC power supply PC5003C Cabinet NOTE Wiring between the control panel and the T Link TL250 TL300 must be enclosed in metal conduit Outputs Input 12 24Vdc TX RX GND RED BLK YEL GRN...

Страница 11: ...earth ground connection 5 2 Standard Connection with PC1616 1832 1864 PC4020 CF PC5020 CF NOTE All circuits are supervised and power limited Refer to section 5 4 UL Listed Commercial Fire Sys tems di...

Страница 12: ...should power up Program the T Link TL250 as instructed in Section 9 NOTE If a Bell Siren will not be used wire the Bell Siren terminals on the panel with a 1000 ohm resistor For Commercial Fire instal...

Страница 13: ...ith receiver set as 1 digit line number Printer Computer Example 2 DVACS with receiver set as 3 digits line number Printer Computer 01 Nov 2004 11 38 22 01 02 SG 01 1 001 Burgl Alm Zn 02 1011 001 A 02...

Страница 14: ...represents the receiver and line number originally used on the SG DVL2A and are programmed as the first 4 digits of the T Link account refer to Appendix F of SG DRL3 IP Installation Manual NOTE If the...

Страница 15: ...tral Station receiver are as follows When an alarm triggers the panel goes off hook The T Link TL300 module sends a dial tone to the panel The panel dials the telephone number of the central station T...

Страница 16: ...h the network administrator that the following ports are locked open and that the SG DRL3 IP has network access for all required network segments 8 5 Integrated Call Directions The T Link TL250 TL300...

Страница 17: ...eive pairs and allows two hosts to communicate without the use of a network hub Upon T Link power up without the Ethernet cable connected LED2 will blink periodically approximately once every 12 secon...

Страница 18: ...s Phone Numbers NOTE You must delete the D in the telephone number first this is the dial tone detection Step 2 Program YES for T Link Enabled option section 000401 Communication Toggles Step 3 If usi...

Страница 19: ...static IP address of the receiver DRL3 IP line card in section 007 Step 9 If the Sur Gard receiver is on a different network segment than the T Link TL250 module the gateway address associated with th...

Страница 20: ...subnet mask for T Link TL300 in section 002 if required This option will be ignored if the unit is set for DHCP Section 001 Step 3 Program the T Link account number in section 003 NOTE The T Link acco...

Страница 21: ...er can program a value from 1 8 bytes long in each section To disable the encryption program both sections with zeros If the encryption key does not match the central station key then the communicatio...

Страница 22: ...or UL installations this option shall be set to B4h 180s For ULC installations this option shall be set to 5Ah 90s for Security Level 4 and to 4Bh 75s for Security Level 5 025 Receiver Restoral Deboun...

Страница 23: ...E mail server Contact your Internet ser vice provider or system administrator for this information This option can only be programmed with T Link Console software 031 E mail Account 64 characters max...

Страница 24: ...is input is violated the panel immediately communicates to the central station SIA Reporting Code BA BH 16 24hr Panic Input If this input is violated when the system is armed or disarmed the panel rep...

Страница 25: ...nerated Refer to options 062 through 065 Mode 1 Bell Follower Operation 048 Input 1 Configuration Default 0 Set to 0 for normally open inputs Set to 1 for normally closed inputs NOTE Select this optio...

Страница 26: ...Default 03 The Fire Pulse Count is used with Digital Input 1 when configured for Bell Follower mode The pulsed count will be the minimum number of pulses high and low forming 1 cycle before the T Lin...

Страница 27: ...1400Hz 071 TL300 Dial Tone Selection Default 00 Enter the 2 digit code corresponding to country indicated in the table below 072 Heart Beat Interval This option will control the heart beat interval Va...

Страница 28: ...s 0 0 0 0 _______ _______ _______ ______ _______ _______ _______ _______ ________ _______ _______ ________ 009 Receiver Local Port 3060 0BF4Hex _______ _______ _______ _______ 010 Receiver Remote Port...

Страница 29: ...____ ______ ______ ______ ______ ______ ______ ______ ______ ______ 032 E mail Password Null ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ __...

Страница 30: ...l Input 10 SIA Reporting Code 0xFF _______ _______ 060 Digital Input 11 SIA Reporting Code 0xFF _______ _______ 061 Digital Input 12 SIA Reporting Code 0xFF _______ _______ 062 Fire On Time 0x05 _____...

Страница 31: ...of 1 Gigabit 1 000 Megabits per second IEEE Abbreviation of Institute of Electrical and Electronics Engineers pronounced I triple E Founded in 1963 the IEEE is an organization composed of engineers sc...

Страница 32: ...the main protocols in TCP IP networks Whereas the IP protocol deals only with packets TCP enables two devices to establish a connection and exchange data TCP guarantees delivery of data and also guara...

Страница 33: ...om with a valid password For use with PC1616 1832 1864 v4 2 or higher DLS2002 Required CD from distributor or free download from dsc com with a valid password Maxsys PC4020 V3 3 with TCP IP support Dr...

Страница 34: ...a 20P Napco 2600 Paradox Digiplex 848 Simplex 4005 4006 4008 4010 4100U NOTE The T Link TL300 is designed to work with the Contact ID com munication format as described in SIA DC 05 Standard Before co...

Страница 35: ...YS0001 FTC1 Restoral YK0001 FTC2 Alarm YS0002 FTC2 Restoral YK0002 PC5108 Tamper Alarm ES0000 PC5108 Tamper Restoral EJ0000 PC5108 Absent ET0002 PC5108 Restored ER0002 Keyswitch Arm CS0000 Keyswitch D...

Страница 36: ...ant BURGLAR ALARMS 130 Burglary Burg Burglary 131 PERIMETER Burg Perimeter 132 INTERIOR Burg Interior 133 24 HR BURG AUX Burg 24 Hour 134 ENTRY EXIT Burg Entry Exit 135 DAY NIGHT Burg Day Night 136 Ou...

Страница 37: ...tion Appl Ckt 4 SYSTEM PERIPHERAL TROUBLES R330 System Peripheral E355 Trouble Sys Peripheral From LRR ECP data connection to panel 331 Polling Loop Open Trouble Polling Loop Open 332 POLLING LOOP SHO...

Страница 38: ...n the detector s operation 389 DET SELF TEST FAIL Trouble Sensor Test Fail 391 Sensor Watch Failure Trouble Sensor Watch Fail 392 Drift Comp Error Trouble Drift Comp Error Reported by Firelite panels...

Страница 39: ...store Not Applicable 431 Access Threat Level Change Access ACS Threat Level Chg 432 Access Relay Trigger Fail Access ACS Relay Trig Fail 433 Access RTE Shunt Access ACS RTE Shunt 434 Access DSM Shunt...

Страница 40: ...ing to log correctly 627 PROGRAM MODE ENTRY Trouble Program Mode Entry Restore Not Applicable 628 PROGRAM MODE EXIT Trouble Program Mode Exit Restore Not Applicable SCHEDULING 630 Schedule Change Trou...

Страница 41: ...te to T Link Network Connector INSTALLATION of CAT 5 Ethernet Cable NOTE Install the ferrite inside the control panel as close to the T Link network connector as allowable 6 150 mm max from center of...

Страница 42: ...to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DSC...

Страница 43: ......

Страница 44: ...nd on the user is encouraged to try to correct the interference by one or more of the following mea sures Re orient the receiving antenna Increase the separation between the equipment and receiver Con...

Отзывы: