[08]  Restoral Reporting Codes
Zones 9 to 16

These reporting codes are used by the communicator to
transmit a zone restoral for zones 9 to 16. Use instructions in
section [05] as a guide for programming.

[09] Utility Alarm Reporting Codes

These reporting codes are used by the communicator to
transmit the following conditions.
• Fire Zone
• Auxiliary Input Zone
• Battery Trouble
• AC Failure Trouble
• Day Zone(s) Trouble
• Bell Circuit Trouble
• Fire Zone Trouble
• Auxiliary Power Supply Trouble

Use instructions in section [05] as a guide for programming.

See “Terminal Connections” section of manual for a
description of the operation of the Fire Zone and the
Auxiliary Input Zone. Section [28] contains options for
Auxiliary Input Zone. The Battery Trouble reporting code will
be sent when the battery voltage drops below 11.5 volts.
This reporting code will also be sent because of a battery
fuse failure. The battery is tested under load every 10
seconds. Only one transmission will be sent during an arm
or disarm period to prevent multiple transmission from a
weak battery. The AC Failure Trouble reporting code will be
sent after the delay time programmed in section [22]. This
prevents transmissions during temporary power failures.
Auxiliary Power Supply Trouble reporting code is  sent when
the auxiliary power supply fuse failed. The Bell Circuit
Trouble reporting code is sent when the bell circuit is open
or the fuse failed. The Fire Zone Trouble code is sent when
the fire zone becomes open circuit (E.O.L. resistor is
disconnected). The Day Zone Trouble code is sent when
any zone defined as a Day Zone (see section [16], [17])
goes open when the system is disarmed. See [

Q

][2]

“Trouble Command” section for additional description of
troubles.

[10] Utility Restoral Reporting Codes

These reporting codes are used by the communicator to
transmit the following list of restoral conditions which
correspond to alarm conditions in section [09]. Use
instructions in section [05] as a guide for programming.
• Fire Zone
• Auxiliary Input Zone
• Battery Trouble
• AC Trouble
• Day Zone(s) Trouble
• Bell Circuit Trouble
• Fire Zone Trouble
• Auxiliary Power Supply Trouble

[11] Reporting Codes for Closing
(Arming) with Access Codes 1 to 8

The reporting codes in sections [11] to [14] are used to
identify “Openings and Closings” (disarming and arming of
the system) by user access code.

After entering the section code [11], enter 8 two digit
reporting codes. The 8 reporting codes correspond to the
first 8 access codes which are programmed using the
[

Q

][5] command. When the system is armed using one of

the access codes, the corresponding reporting code is
transmitted.

When transmitting in any of the extended formats, (see
examples in section [05]), closing codes would be
programmed as follows.  [C1], [C2], [C3], [C4], [C5], [C6],
[C7], [C8]........

Where the first digit “HEX C” is one which is used to
represent a closing signal (this could be another number
depending on what is used at the monitoring station) the 2nd
digit represents the access code which was used to arm the
system.

The closing code transmission takes place after the exit
delay time. Therefore if the system is armed and disarmed
before the expiry of the exit time, no transmission will take
place.

Remember that the 1st user code is the master code and
that the 16th code may be the temporary or maid’s code.
The 16th user code can be converted to a normal code
using one of the options in section [18].

When the system has been armed using “Quick Arm” [

Q

][0]

or “Auto-arm” (see [

Q

][6] “Keypad Commands”), the 1st

reporting code (reporting code for master code) will be
transmitted. The master code is required to enable or
disable these functions.

When the system is armed with one or more zones
bypassed (see [

Q

][1] command for zone bypassing), the

monitoring station can be notified by programming the
Partial Arm reporting in section [15]. Note that the Partial
Closing code is sent in tandem with the regular closing code
to identify it as a partial closing condition.

[12] Reporting Codes for Closing
(Arming) with Access Codes 9 to 16

See section [11] for further information.

[13] Reporting Codes for Opening
(Disarming) with Access Codes 1 to 8

The 8 reporting codes correspond to the first 8 user access
codes which are programmed using the [

Q

][5] command.

When the system is disarmed using one of the access
codes, the corresponding reporting code in this section is
transmitted.

See section [11] for an example of “Opening and Closing”
reporting code programming.

Содержание PC3OOO

Страница 1: ...INSTALLATION MANUAL PC3OOO Version 7 51...

Страница 2: ...charge de l ensemble des dispositifs ne d passe pas 100 L indice de charge de cet dispositif est 42 DOC NOTICE NOTICE The Canadian Department of Communications label identifies certified equipment Thi...

Страница 3: ...er s Test ____________________ Q 6 Master Code 0 _____________ 10 Setting the Clock __________________ Q 6 Master Code 1 _____________ 10 Auto arm Time of Day _____________ Q 6 Master Code 2 _________...

Страница 4: ...umber 1 _____________________________ 19 26 Downloading Access Code ____________________________________________ 19 27 Communicator Format Options _________________________________________ 19 28 Progr...

Страница 5: ...ttery Transformer required 16 5 VAC 40VA Dimensions 11 x 11 8 x 3 3 deep 279 x 300 x 84 mm Weight 6 5 lbs 3 kg Remote Keypad Specifications PC3000RK Four wire QUAD hook up and up to 3 keypads per syst...

Страница 6: ...tors a number of possible trouble conditions including An active battery supervision circuit that periodically tests the battery under load A loss of the AC power supply A supervised circuit trouble c...

Страница 7: ...ed to the bell terminals may go on for a few seconds The Armed light may be on or off the first time the panel is powered The last armed disarmed condition is stored in the EEPROM memory so the panel...

Страница 8: ...ble See the Programming Guide section 28 for a list of options for the PGM OUT output The PGM OUT is a 50 mA maximum switch to ground A 100 ohm current limiting resistor is connected in series A small...

Страница 9: ...for testing and programming PC3000 systems Connect the transformer wait approx 5 seconds Enter a few keypad commands and open a zone to be sure that the panel and keypad are responding to signals If...

Страница 10: ...sleeping area and the rest of the family unit FIG 2 In the family living units with more than one sleeping area a smoke detector should be located to protect each sleeping area FIG 3 A smoke detector...

Страница 11: ...eypad buzzer will beep quickly Exit the premises through the designated exit entry door At the end of the allowed exit time all lights on the keypad will go out except the Armed light See the Installe...

Страница 12: ...grammed for 1 to 99 minutes See Programming Guide section 22 3 Day Zone Trouble This trouble applies only to zones which have been programmed as day zones Programming Guide section 16 17 A day zone cr...

Страница 13: ...5 command If the Master Code is forgotten and the panel is left armed the entire programming can be reset to factory default by using the Hardware Reset method described on page 22 7 To successfully p...

Страница 14: ...on then a valid 4 digit access code is required to abort the auto arm sequence The auto arm will be attempted at the same time the following day Auto arm abort with transmission Any time an auto arm i...

Страница 15: ...Use Code must be used for arming before it is erased Quick Exit Q 0 When Armed Entering Q 0 when the system is fully armed will allow the user 2 minutes to exit the premises through any delay zone wit...

Страница 16: ...he panel and program it as described below Enter the Installer s Programming section and edit the following sections Q 8 Installer s Code Section Printer Only Monitored and Printer 01 Do not program P...

Страница 17: ...zone light 7 is off and an answering machine is connected and it is set to answer before the panel the panel will be unable to receive a call from a downloading computer If the panel is set to answer...

Страница 18: ...Installers code portion of the command Just enter the number of another programming section When programming a section it is possible to exit by pressing Only the data entered before pressing will be...

Страница 19: ...anging the reporting codes in a section only code entries up to the one which is being changed need to be entered Press to exit from the programming sequence Only codes up to the last one entered will...

Страница 20: ...ower Supply Trouble 11 Reporting Codes for Closing Arming with Access Codes 1 to 8 The reporting codes in sections 11 to 14 are used to identify Openings and Closings disarming and arming of the syste...

Страница 21: ...expires no alarm will be generated Type 7 and 8 Delay zones are used where a longer entry delay time is required such as with a garage door With these two zone types the exit delay is the same as the...

Страница 22: ...trouble only armed or disarmed TLM Telephone Line Monitoring 6 Light off Accepts 2300 Hz standard handshake Light on Accepts 1400 Hz handshake for Radionics formats 3 4 B and C in section 27 See Radio...

Страница 23: ...Vertex 20 BPS 2300 Hz handshake 3 1 and 4 1 4 2 non extended format 2 Silent Knight fast 20 BPS 1400 Hz handshake 3 1 and 4 1 4 2 non extended format 3 Radionics 2300 1400 Hz handshake 3 1 4 2 non ex...

Страница 24: ...lity output Q 7 Group A access code 5 Utility output Q 7 Group B access code These options change the PGM OUT terminal to different options used with the keypad utility output Q 7 command See Utility...

Страница 25: ...programmed with a 2 in Section 33 to call the 2nd phone number only It is necessary to program both the 1st and 2nd phone number locations with the same telephone number Notes 1 The following restrict...

Страница 26: ...Call back disabled Light on Call back enabled See Downloading 48 Panel Identification Code Program using the same method as sections 24 25 and 26 49 Printer Configuration 1 Light off Not 110 baud Lig...

Страница 27: ...nds where 00 means no delay If the system is disarmed before the delay in transmission expires no transmission will take place 53 Auto arm Abort Reporting Code This code is programmed the same as sect...

Страница 28: ...digit Zone 2 Alarm Zone 6 Alarm Enter Q1Q HEX A to transmit a 0 Zone 3 Alarm Zone 7 Alarm A 0 digit is 10 pulses Zone 4 Alarm Zone 8 Alarm 06 Alarm Reporting Codes Zones 9 to 16 Page 15 Zone 9 Alarm Z...

Страница 29: ...ission reports with sections 11 to 14 AC Failure Trouble openings closings Day Zone s Trouble Bell Circuit Trouble Fire Zone Trouble Auxiliary Power Supply Trouble 11 Reporting Codes for Closing Armin...

Страница 30: ...pad Auxiliary Alarm A openings closings Keypad Panic Restoral P Keypad Fire Restoral F Keypad Auxiliary Restoral A Periodic Test Transmission 16 Zone Definitions for Zones 1 to 8 Page 17 Note When def...

Страница 31: ...eout Restorals on disarming Off Zone Light 3 Alarm display while armed No alarm display armed Off Zone Light 4 DTMF dialing Pulse dialing Off Zone Light 5 N C zones EOL resistors zones Off Zone Light...

Страница 32: ...Time in minutes 3 0 AC Failure Transmission Delay in minutes 5 0 Normal Zone Response Time x 10 ms 3 0 Test Transmission Cycle Time in days 23 System Clock Times Page 19 Default 9 9 9 9 Automatic Armi...

Страница 33: ...hake 3 1 extended format A Silent Knight fast 20 BPS 1400 Hz handshake 3 1 extended format B Radionics 2300 1400 Hz handshake 3 1 extended format C Radionics 2300 1400 Hz handshake 3 1 extended with p...

Страница 34: ...Light 2 On Zone Light 3 On Zone Light 4 On Zone Light 5 On Zone Light 6 On Zone Light 7 On Zone Light 8 30 Zone Group B Assignment Page 21 Default On Zone Light 1 On Zone Light 2 On Zone Light 3 On Z...

Страница 35: ...Group A Openings and Closings 1 Access Codes Group B Openings and Closings 1 Priority Alarms and Restorals 1 Maintenance Alarms and Restorals Enter 0 No transmissions for this group 1 Call 1st phone n...

Страница 36: ...On Zone Light 2 On Zone Light 3 On Zone Light 4 On Zone Light 5 On Zone Light 6 On Zone Light 7 On Zone Light 8 44 Access Bypass Mask Codes 9 to 16 Page 22 Default On Zone Light 1 On Zone Light 2 On...

Страница 37: ...15 all lights on On Zone Light 4 At least one light must be on Off Zone Light 5 Downloading answer enabled Downloading answer disabled Off Zone Light 6 User initiated call up No user initiated call up...

Страница 38: ...Zone Light 7 Answering machine over ride Answering machine over ride timer 120 seconds timer 60 seconds Off Zone Light 8 Bell shutdown active Bell shutdown not active 52 Delay Before Transmission Pag...

Страница 39: ...__________ ______________________________________________________________________ 6 ____________________________ ______________________________________________________________________ 7 ______________...

Страница 40: ...HOOKUP DIAGRAMS 36...

Страница 41: ...22AWG 540 164m 20AWG 850 259m 19AWG 1000 305m 18AWG 1360 414m FIRE CIRCUIT HOOKUP Smoke Detector Power Loop Wiring Chart Loop Current mA AWG14 AWG16 AWG18 AWG19 AWG22 Maximum wire run to EOL relay in...

Страница 42: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls Ltd This warranty contains the...

Страница 43: ...1997 Digital Security Controls Ltd 1645 Flint Rd Downsview Ontario Canada M3J 2J6 Tel 416 665 8460 Fax 416 665 7498...

Страница 44: ...29000543 R7...

Отзывы: