background image

Install Smoke detectors in accordance with NFPA 72,
Chapter 11:

“Smoke detectors shall be installed outside

of each sleeping area in the immediate vicinity of the
bedrooms and on each additional story of the family liv-
ing unit, including basements and excluding crawl spaces
and unfinished attics. In new construction, a smoke
detector also shall be installed in each sleeping room.”

2. Mount Smoke Detector 
Backplate

Mount backplate on standard
4” octagonal electrical box
using the screws provided.

NOTE: 

Power supply must be

supplied from a UL Listed
alarm control unit. Install wir-
ing in accordance with the
appropriate national and local
electrical codes.

3. Wiring

Refer to the connection dia-
gram in this section. Before
connecting the unit, prepare
the wires from the electrical
box for connection; the wires
should not be frayed or bent.

CAUTION: If power connec-
tions are reversed, the unit
will not operate. The unit is
protected against damage
from incorrect wiring.

When wiring is completed,
inspect the wiring and cor-
rect any errors before apply-

ing power to the unit. When the wiring has been
thoroughly reviewed, neatly insert the wires into the elec-
trical box and secure the unit to the mounting plate.

NOTE

: This equipment should be installed in accordance

with the National Fire Protection Association Standard 72
(National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269).

Dust Cover

The dust cover is intended to protect the smoke detector
from dust and dirt entry while the unit is not in service.

CAUTION: The dust cover protects the unit ONLY when it
is not in service. Remove the dust cover before use.

Device Enrollment

The serial number located on the back of the device must
be enrolled into the alarm control panel via Installer’s Pro-
gramming ([

,

][8] [Installer Code]). This procedure is out-

lined for Power panels in the PC5100 Installation Manual
and for the PC4010/4020 v3.x in the control panel Instal-
lation Manual.

WARNING: Connect only DSC addressable series
devices to the addressable loop connections. Connec-
tion of any other type of device will impair operation.
Devices other than addressable series devices which
require power to operate must be powered separately.

Do NOT use looped wire under terminals for system
supervision. Break the wire run to provide supervision
of connections.

4. Mounting
Detector Installation

Position the detector on to the base plate using the
detector and base plate alignment marks. Press the
detector gently in place while rotating the detector clock-
wise until the detector snaps into place. Remove the side
tab from the locking tab to lock in place (optional).

Removal:

 If the side tab

is removed to lock the
detector, depress tab
with a small flat blade
screwdriver and rotate
the detector counter-
clockwise until the
alignment marks line
up. Remove detector.

5. Test Unit 

1. Program the Panel for Smoke Test. Refer to the Alarm

Control Panel Installation Manual for details.

NOTE: 

If the detector is in one of the following states

when test is initiated, it will not enter an alarm state: 

• Compensation trouble.
• Failure of heat or smoke detector.
• Other internal faults that could prevent a smoke or

heat alarm.

2. Use the FSD-100 meter to read the trouble status after

testing.  Refer to the FSD-100 User Guide for details.

NOTE: 

Place the meter close to the LED until it begins to

flash every 2 seconds. Then hold the meter on the oppo-
site side of the LED and read the message. The detector
will send out a test message 7 times in a 2-second inter-
val until the LED stops flashing.

6. Compensation Reset

Cleaning, replacement of the smoke sensor, or other
changes may change the background signal/noise of the
detector; this requires the drift compensation be reset.
Compensation trouble is one of the faults indicated when
the LED indicator is OFF.
• Remove power from the unit, then press and hold the

test button for 30 seconds to power down unit.

• Power up unit while pressing the test button.The LED

will flash; when 5 seconds has elapsed. Release the
test button within 1 second after the fifth LED flash.

• The LED will flash every 8 seconds  for 1 minute.

When the detector stops flashing test the detector to
verify normal operation.

Mounting Holes

Locking

Tab

CLOSE

OPEN

Alignment

Marks

Backplate

Tabs

Mounting

Surface

Detector

Содержание FSB-210 Series

Страница 1: ...ctor automatically compensates for long term environmentally induced changes to maintain a constant smoke sensitivity When the drift compensation has reached its high or low limit of adjustment the detector will go into the trouble state Heat Alarm The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold 135ºF 57ºC and send the alarm signal to the control pa...

Страница 2: ...tion of any other type of device will impair operation Devices other than addressable series devices which require power to operate must be powered separately Do NOT use looped wire under terminals for system supervision Break the wire run to provide supervision of connections 4 Mounting Detector Installation Position the detector on to the base plate using the detector and base plate alignment ma...

Страница 3: ...its use Keep all exits clear Be sure to remove snow from all paths in the winter and remove objects that are block ing any of the exits Have a predetermined assembly point where everyone can be accounted for for example across the street or in a parking lot Once everyone is out of the home building call the Fire Department A good plan emphasizes a quick escape Do not inves tigate first or attempt ...

Страница 4: ...ed to try to correct the interference by one or more of the fol lowing measures Re orient the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio television technician for help The user may find the following booklet prepared b...

Отзывы: