17
14. Display features cont.
15. Troubleshooting
FlowVis Digital has been designed to be an easy to install, accurate and reliable addition to the renowned FlowVis flow
meter. However, should an unexpected problem occur, please refer to the following Troubleshooting Guide.
As always, please feel free to contact us with any questions or concerns.
Observation
Solution
Digital Display not
illuminated
•
Check Power Supply is plugged into its receptacle, if yes...
•
Check for 12 VDC power at terminals PSU+ and PSU- on rear of Display, if no voltage...
•
Check to see if wires from the Power Supply are securely terminated into the PSU+ and
PSU- terminals, if yes...
•
Check to see if power source is active. If yes, Power Supply needs to be replaced
Digital Display reads
zero flow rate with pump
running
•
Is Display illuminated? If yes...
•
Check to see if FlowVis is reading the expected flow. If yes...
•
Check to see if there is a steady blue light on the sensor. If no...
•
Check sensor wiring and terminations into the rear of the Display - red wire to I input +,
black wire to I input -, and green wire to COM. Is everything is secure and correct? If yes...
continued on next page
On all FlowVis Digital installations for 8-inch FlowVis units, please note that the text ‘X10’ will appear above the flow reading at
all times. See the below examples and instructions on how to properly read these flow rates:
Note the ‘X10’
indicator
Note the
decimal point
92.4 x 10 = 924 GPM
103 x 10 = 1030 GPM
WWW.DRYDENAQUA.COM