3. Remove the dispersion tube. Make sure
that nothing loose falls into the header.
INSTALLING INSULATED TUBES
Note: The photos below show the insulated dispersion tubes without the
clear poly film for demonstration purposes only. To prevent dirty
insulating material, install the insulated dispersion tubes before tearing
off the clear poly film.
Perform the following steps for each insulated
tube being installed:
1. Slide the new slip couplings onto the
insulated dispersion tube as shown.
2. Connect the dispersion tube to the supply
header with the shouldered slip coupling.
Push and twist the dispersion tube until
the shoulder bottoms out, then connect the
dispersion tube to the condensate header
with the other slip coupling.
3. Push the shoulder-less slip coupling against
the stop disk on the condensate header.
4. Rotate the dispersion tube to point the tubelets
across (perpendicular to) the airstream.
Retrofitting an existing Ultra-sorb
For more information
Ultra-sorb dispersion assemblies are shipped
with a comprehensive manual. Refer to it for
assembly, parts, installation, troubleshooting,
piping, maintenance, performance, and
warranty information.
Rapid-sorb dispersion assemblies are shipped
with installation instructions. See the Rapid-
sorb section of the manual shipped with your
humidifier.
This addendum must be left with the owner
and should be accessible for reference.
Step 3
Step 1
Slip coupling
with shoulder;
supply-header-
end of tube
Slip coupling
without shoulder;
condensate-header-
end of tube
Step 2
Step 3
Step 4