![DriSteem RO-200 series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/dristeem/ro-200-series/ro-200-series_installation-operation-and-maintenance-manual_2531613007.webp)
3
DRISTEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Table 3-1:
RO station capacities
Model
201
202
203
Rated capacity, permeate
Gallons/minute
0.2
0.4
0.6
Concentrate fl ow (reject)
1
Gallons/minute
0.6 - 1.1
0.7 - 1.2
0.5 - 1.0
Recirc fl ow (adjustable as needed)
1, 2
Gallons/minute
0 - 0.5
0 - 0.5
0 - 0.5
System pressure, psi (pump pressure through membranes)
100 - 150
100 - 150
100 - 150
°F (°C)
50 (10)
50 (10)
50 (10)
Pre-fi lters
Sediment cartridge - 5 micron
1
1
1
Carbon cartridge - 10 micron
2
2
2
Pressure sensor settings
Low pressure (for pump protection)
8 psi
8 psi
8 psi
1.
Reduce concentrate fl ow by the amount of recirc fl ow used to maintain the recommended maximum system level.
2.
Recirc fl ow usage will reduce water but may decrease membrane life.
System specifi cations
OVERVIEW