• Verify that the position of the pad, curb, or wall (when applicable) properly
supports the unit and that support structure dimensions coincide with unit
dimensions.
• DriSteem rooftop curbs are shipped knocked down for ease of transporting
to the roof. The curb is manufactured out of 14-gauge galvanized steel
and is shipped with all hardware for bolt-together assembly, a curb gasket
for sealing between the curb and the unit, and an installation drawing. All
holes are matched before leaving the factory.
• Roof curbs supplied by others must be at least 14” high, and there must
be a gasket between the top of the curb and the base surface of the unit to
prevent moisture from leaking into the building from either driving rain or
melting snow.
• Prior to installation, remove all of the unit packaging.
• The RTS outdoor enclosure must be lifted by the designated lift points as
shown in Figure 39-1 as lift points are different depending on enclosure
size. It must be lifted in a fashion that holds it level and keeps it from
tipping, falling, or twisting.
• If the unit is severely twisted during handling, permanent damage can
occur.
• It is the installer’s responsibility to verify the handling equipment’s
capability to safely handle the unit.
• All lifting operations must be accomplished with a load spreader of
sufficient width to ensure that the lifting cables clear the side of the unit.
Outdoor enclosure: Mounting
FIGURE 39-1: OUTDOOR ENCLOSURE MOUNTING WITH LIFT BRACKET
INSTALLATION
OM-8094
OM-8095
1½" Diameter (38 mm)
hole lifting bracket in each
corner (typical of 4)
1½" Diameter (38 mm)
hole lifting bracket in each
corner (typical of 2)