P a g e   6   •   D R I S T E E M   R e t r o f i t   a c t u a t o r   i n s t r u c t i o n s  

Figure 6-1:
Mounting MS40-707X and MS40-715X and setting-up actuator/linkage/valve assembly.

A s s e m b l y

3-Way valve actuator replacement

Spring-return actuators without manual override 

MS40-707X and MS40-715X

•  Install the actuator onto the linkage and 3-way valve, and set-up 

the assembly according to Figure 6-1 below.

2

3

2

Tip:

A 1-5/8" open-end wrench can be used to

measure the amount of rotation (measured between

opposite sides of the slot).

L

R

L

LOCK

L

R

L

1

2

3

Tip:

• MS40-707X, MS40-715X Proportional Control - Change the

reversing switch setting from direct acting (L) to reverse acting (R),
and then apply power to drive the actuator to the end of stroke.
When finished, return the switch setting to direct acting (L).

1 MS40-707X and MS40-715X

actuators are shipped at the

end of stroke, without preload.

6 Apply power to the actuator to rotate it CCW into alignment

with the mounting plate, and then slide anti-rotation screw
NYBA-161 halfway into the slot on the bottom of the
actuator. Tighten the nut on the anti-rotation screw.

Warning:

Take care not to pinch your fingers or hand

between the actuator and the mounting plate, when
powering the actuator into alignment.

Caution:

When setting the valve preload, power must be

used to position the actuator. Do not manually force the
actuator into the mounting position. If forced, damage to the
pinion shaft or improper close-off may occur.

1-3/8"

3 Align the actuator with the

mounting plate, then rotate it

10° CW. Note that 1-3/8"

movement at the anti-rotation

slot (measured at the anti-

rotation slot's centerline) is

sufficiently equal to 10°.

4 Make sure the actuator is in

full contact with the plastic
stand-offs on the linkage.

5 Holding the actuator at the 10°

position, use a 10 mm wrench or
socket to tighten the two nuts
equally on the shaft clamp, 8 to
10 lb-ft (11 to 14 N-m).

2 Slide the actuator, "L" side

facing out, onto the linkage's

pinion shaft.

10°

Optional: Affix the Open and
Closed labels to the indicator
in the appropriate positions.

OPEN

CLOSED

NYBA-161
Anti-Rotation Screw for
MS40-707X, MS40-715X

2

1-5/8"

1-5/8" Open-End

Wrench

1 Rotate the linkage's pinion shaft CCW,

to retract the rack (stem up).

•  Apply power to the actuator and check the system's operation for 

proper operation, in response to the control signal.

•  For electronic hydraulic actuator to DuraDrive actuator change- 

over, refer to the wiring diagram on page 7.

•  For existing DuraDrive to DuraDrive actuator change-over, refer 

to wiring diagrams supplied with your humidifier.

Содержание MS40-7073

Страница 1: ...Retrofit Actuator MS40 7073 and MS40 7153 Instructions L R L LOCK...

Страница 2: ...ve existing actuator existing DuraDrive actuator 3 Assembly Assembling linkage to valve electronic hydraulic actuator only actuator only actuator only 4 Spring return actuators without manual override...

Страница 3: ...ng and square washer on top of spring Using a flat head screwdriver turn the brass square nut counter clockwise to release the washer CAUTION Spring is under compression and brass square nut and or sp...

Страница 4: ...e top nut 2 Tighten the jam nuts against each other using two 5 16 open end wrenches 3 Raise the valve stem to the full up position 6 Rotate the pinion shaft CW to fully lower the rack and then positi...

Страница 5: ...ed labels to the indicator in the appropriate positions OPEN CLOSED L R L 1 6 Lightly finger tighten the two nuts on the shaft clamp s and then set up the actuator and tighten the shaft clamp s as fol...

Страница 6: ...nd the mounting plate when powering the actuator into alignment Caution When setting the valve preload power must be used to position the actuator Do not manually force the actuator into the mounting...

Страница 7: ...ve Figure 7 1 Typical wiring diagram for MS40 7073 and MS40 7153 proportional actuators Environmental specifications Ambient temperature limits Shipping and storage 40 to 60 F 40 to 71 C Operating 22...

Страница 8: ...ucts Corporation U S Headquarters 14949 Technology Drive Eden Prairie MN 55344 800 328 4447 952 949 2415 952 229 3200 fax Invensys and DuraDrive are trademarks of Invensys plc and its subsidiaries and...

Отзывы: