background image

1

DRISTEEM DRANE-KOOLER WATER TEMPERING DEVICE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

COOL DISCHARGED HOT WATER

Drane-kooler is a water tempering device that mixes cold water 
with hot water discharged from various types of equipment, such 
as a humidifier, to reduce the discharged water temperature 
before it enters a municipal sewer system . 
There are two reasons to use a water tempering device . First, 
most municipalities prohibit draining water hotter than 140 °F (60 
°C) into their sewer systems . And second, PVC drain pipes are 
susceptible to damage from water that is too hot . When faced 
with either of these situations, Drane-kooler is the solution!

HORIZONTAL DESIGN

A space-efficient horizontal orientation and side drain outlet 
provide enough clearance to allow the Drane-kooler to be 
mounted directly underneath DRI-STEEM humidifiers, saving 
footprint space while allowing room for pitched drain piping .

HOW IT WORKS: HOT + COLD = TEMPERED!

1 .  Hot water discharged from a humidifier or other appliance 

enters the Drane-kooler through piping connected to the top 
threaded connection . A vacuum breaker prevents backflow 
into potable water systems . 

2 .  Cold water enters through the temperature-actuated valve . 

The valve and the Drane-kooler's straightforward design 
ensure efficient mixing of hot and cold water . The valve's 
sensor, located near the outlet, ensures that water leaving the 
Drane-kooler is 140 °F (60 °C) or less before entering the 
municipal sewer system .

3 .  Tempered water  at 140 °F (60 °C) or less exits through the 

side outlet for safe discharge into a municipal sewer system 
or PVC pipe .

RELIABLE, NON-ELECTRIC VALVE

The temperature-actuated valve is time-tested to be reliable and 
maintenance-free . And because it is non-electric, no wiring is 
required .

MULTIPLE MOUNTING OPTIONS

The Drane-kooler can be mounted by attaching the integral 
mounting plate to a wall, by attaching the mounting plate to an 
adjustable floor stand, or by using an assembly for suspension 
mounting . These multiple mounting options provide capability 
for the Drane-kooler to be properly supported and not secured 
entirely by piping .

1

2

3

Features summary

FIGURE 1-1: DRANE-KOOLER

OVERVIEW

Содержание Drane-Kooler Series

Страница 1: ...Water Tempering Device Installation Operation and Maintenance Manual DRANE KOOLER READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...ature to you Download DriSteem literature Most DriSteem product manuals are available on our website www dristeem com Overview Features Summary 1 Capacities and connection sizes 2 Dimensions 3 Install...

Страница 3: ...er or other appliance enters the Drane kooler through piping connected to the top threaded connection A vacuum breaker prevents backflow into potable water systems 2 Cold water enters through the temp...

Страница 4: ...ter inlet connection 1 DN25 pipe thread Tempered water outlet connection 2 DN50 pipe thread Cold water supply connection 3 8 DN10 pipe thread Evaporative Humidifier 1 air gap 25 mm Adjustable floor st...

Страница 5: ...with floor stand and extension from floor to top of hot water inlet in 1 25 mm increments 13 25 to 20 25 337 to 515 B Height from bottom of tank to top of hot water inlet 7 5 191 C Height from bottom...

Страница 6: ...ply water line that is dedicated to other appliances If installing the Drane kooler with a humidifier do not branch off the 1 4 DN8 cold water supply line to the humidifier Verify that the supply wate...

Страница 7: ...r Beam clamp assembly and 1 4 threaded rod are supplied by others INSTALLATION Mounting THREE MOUNTING OPTIONS Use one of the mounting options shown on this page to ensure that the Drane kooler will b...

Страница 8: ...ne kooler do not connect to a supply water line that is dedicated to other appliances Hot water inlet service union 1 DN25 pipe thread Cold water inlet service union 3 8 DN10 pipe thread Cold water su...

Страница 9: ...ers the Drane kooler through piping connected to the top threaded connection The vacuum breaker prevents backflow into potable water systems 2 Cold water enters through the temperature actuated valve...

Страница 10: ...ccumulation in mixing chamber Remove the Drane kooler and dislodge mineral accumulation Mineral accumulation on thermal sensor Remove thermal sensor from Drane kooler and gently remove mineral accumul...

Страница 11: ...ANCE Replacement parts FIGURE 9 1 REPLACEMENT PARTS Table 9 1 Model DK 12 replacement parts Item Description Part Number 1 Drane kooler weldment Model DK 12 167001 020 2 Water tempering valve 505090 3...

Страница 12: ...sought based on breach of warranty breach of contract negligence strict liability in tort or any other legal theory even if DriSteem has notice of the possibility of such damages By purchasing DriStee...

Отзывы:

Похожие инструкции для Drane-Kooler Series