RIGID LEVEL SENSOR INSTALLATION AND HANDLING PROCEDURE 

 

OPERATION MANUAL TLS-LM can be downloaded from the website below. 
http://www.drexelbrook.com/Continuous-Level-Measurement/Index.aspx 

 

Unpacking the Rigid Level Sensor 

 

IMPORTANT 

Be sure to read and understand all of the Installation Instructions before beginning the procedure! 
Unpacking 
Carefully remove the contents of the shipping carton and check each item against the packing list before destroying any 
packing materials. If there is any shortage or damage, report to the factory at 1-215-674-1234. 

Storage 

Tank Level Systems should be stored in their original shipping containers until ready for installation.  Damage that occurs in 
storage is not covered under manufacturer’s system warranty. 

o

 

CAUTION!

  DO NOT BEND RIGID LEVEL SENSORS: ANY RESULTING PERMANENT DAMAGE IS 

CONSIDERED USER DAMAGE, AND IS NOT COVERED UNDER WARRANTY. 

o

 

LONGER RIGID LEVEL SENSORS NEED TO BE SUPPORTED AT BOTH ENDS WHILE HANDLING. 

o

 

DO NOT ATTEMPT TO OPEN RIGID LEVEL SENSOR, OR ATTEMPT TO WELD ITS TUBING.  

 

Level Sensor Assembly (B style) 

 
If required, install the compression fitting and reducer bushing (not shown – user supplied) onto level sensor tubing. Then 
install floats and spacers on the end of the level sensor as shown. 

 
ONE FLOAT

 

requirement:

  Install the float, dead band spacer, and retaining fastener (“e-clip”).  

 
TWO FLOAT

 

requirement:  

Install as follows:  “

Product

” float 

(1)

, interposing spacer 

(2)

“Interface

” float 

(3)

, dead band 

spacer 

(4)

, and retaining fastener (“e-clip”).       

                  

                        

                          

 

Sensor Installation – Standard Fitting style 

 

NOTE:

 The Rigid Level sensor in this style requires a 

minimum tank bottom clearance of 1/2”. Tank bottom 
clearance is defined as the distance from tank bottom 
surface to the tubing plug on level sensor.  

 
STEP 1: 

 Lower the level sensor tube (with required floats 

and spacers) through opening on tank flange, and into tank.   
 

STEP 2: 

 Thread and tighten the ¾”NPT fitting on probe 

tubing into tank flange.   
                                                                                         
 
                                                           
 
 

 
 
 
 
 
 
Sensor Installation  – Adjustable 
Compression Fitting style 

 

NOTE:

 The Rigid Level sensor in this style requires a 

minimum tank bottom clearance of 1/2”. Tank bottom 
clearance is defined as the distance from tank bottom 
surface to the bottom of the tube on the level sensor.  

STEP 1: 

  Lower the lever sensor tube (with required floats 

and spacers) through opening on customer tank flange, and 
into tank.   

STEP 2: 

  Thread and tighten user supplied reducer bushing 

into tank flange. 

 
STEP 3: 

  Thread and tighten lower ¾”NPT half of 

compression fitting into reducer bushing on tank flange.  
 

STEP 4: 

  Adjust level sensor to desired tank depth 

(reference chart below), and hand tighten compression fitting 
into reducer bushing on tank flange. After hand tightening, 
turn the fitting 1-1/4 turns.  Do not over tighten.  
 
 
 
 
 
  
 
 
 
 
 
 
 
 
 
                                                             
 

STEP 2  

 

STEP 3                      STEP 4 

 
 