2.3.6. Wiring
Diagram
Notes:
1. All equipment to be installed in accordance with all applicable local, state, and federal codes, including, but
not limited to, the National Electrical Code (NFPA 70), NFPA 30, the Automotive and Marine Service
Station Code (NFPA 30A), and the Standard for Storage of Flammable and Combustible Liquids at Farms
& Isolated Sites (NFPA 395).
2. For wiring connections, use wires rated at least 90ºC, 600V, Gas & Oil Resistant.
3. See the wire size chart for proper gauge of the wires.
4. Aux AC – The Auxiliary AC Control Lead (brown) is hot when the pump is turned on and can be used to
provide a switch detect to a fuel management system, open a solenoid valve in the supply line for positive
head pressure applications, or power a signal light. Maximum load is 1 amp. Cap the wire if not used.
5. For full details on the electrical wiring, see entire Section 2.3.