background image

- 17 -

 

 

5.

 

Designing the size and connection of ACCU tank to the heating system 

An ideal  size of the accumulation tank  is designed by a  design engineer, or a person sufficiently qualified to design 
heating systems.  

Product  assembly  must  be  implemented  by  an  authorised  person  (confirmed  in  the  warranty  certificate). 

It  is 

necessary to activate the heating circuit and remove potential impurities that are captured in the filter; after that 
the system is fully functional.

 

6.

 

General Technical Parameters 

The maximum operating pressure in the tank is 0.3 MPa. The maximum heating water temperature in the tank is 90°C.  

The maximum operating pressure in the inner tank is 0.6 MPa. The maximum hot  service water temperature in the 
inner tank is 90°C. 

In version 2 a 3 additionally: 

 

The  maximum  operating  pressure  in  the  exchanger  is  1  MPa,  the  maximum  temperature  of  heating  water  in  the 
exchanger is 110°C. 

 
Important: When putting into operation, water has to be filled first into the inner tank for HSW 

and the operating 

pressure inside it has to be kept, only then heating water can be filled into the outer accumulation tank, 
otherwise the product may get damaged!

 

The  manufacturer  explicitly  emphasises  the  necessity  of  being  particular  in  testing  the  tightness  of  the  heating 
circuit (radiators, piping joints, floor heating, etc.) with the connection of the accumulation tank. No pressure grow 
in  the  accumulation  tank  heating  water  compartment  may  occur  above  the  maximum  operating  pressure  
of  0.3  MPa,  if  the  heating  system  is  pressurised  to  higher  than  the  maximum  operating  pressure,  the  inner 
enamelled tank may get permanently damaged! 

No stop fitting can be put between the security fitting of the heating circuit and the accumulation tank!!! 

It is recommended that the product is used in an indoor environment with air temperatures from +5°C to 45°C and  
a maximum relative humidity up to 80 %. 

Safety valve has to be fitted on the cold water inlet. Each hot service water pressure heater must have a safety valve 
with  a  membrane  spring.  Nominal  clearance  of  safety  valves  is  defined  by  standard  ČSN  06  0830.  Heaters  are  not 
equipped with a safety valve. The safety valve must be easily accessible, as close to the heater as possible. The inlet 
pipes must have at least the same clearance as the safety valve. Safety valve is placed high enough to secure dripping 
water  drain  by  gravity.  We  recommend  mounting  the  safety  valve  onto  a  branch  pipe.  This  allows  easier  exchange 
without having to drain the water from the heater. Safety valves with fixed pressure settings from the manufacturer 
are  used  for  the  assembly.  Starting  pressure  of  a  safety  valve  must  be  identical  to  the  maximum  allowed  heater 
pressure, and at least 20% higher than the maximum pressure in the water main. If the water main pressure exceeds 
such value, a reduction valve must be added to the system. No stop valves can be put between the heater and the 
safety  valve.  During  assembly,  follow  the  guide  provided  by  the  safety  equipment  manufacturer.  It  is  necessary  to 
check the safety valve each time before putting it into operation. It is checked by manual moving of the membrane 
from the seat, turning the make-and-break device button always in the direction of the arrow. After being turned, the 
button must click back into a notch. Proper function of the make-and-break device results in water draining through 
the safety valve outlet pipe. In common operation, such a check needs to be implemented at least once a month, and 
after each heater shutdown for more than 5 days. Water may be dripping off the drain pipe of the safety valve; the 
pipe must be open into the air, pointed down; environment temperatures must not drop below zero.  

When draining the heater, use the recommended drain valve. First, close the water supply into the heater. 

Find necessary pressure values in the following table.  

For  proper  safety  valve  operation,  a  backflow 
valve  must  be  mounted  on  the  inlet  pipes, 
preventing spontaneous heater draining and hot 
water penetrating back into the water main.  

 

Safety valve 

starting 

pressure (MPa)

 

Admissible 

operating water 

heater pressure 

(MPa)

 

Max. pressure in 

the cold water 

pipe (MPa)

 

0.6 

0.6 

do 0.48 

0.7 

0.7 

do 0.56 

do 0.8 

Содержание NADO v1

Страница 1: ...peicherbeh lten typ NADO GB Storage tank NADO type H G jt tart lyok NADO t pus RUS e NADO F R servoir accumulation mod le NADO SK Akumula n n dr e typ NADO Dru stevn z vody Dra ice stroj rna s r o Dra...

Страница 2: ...edpisy 3 PL Instrukcja obs ugi i monta u 7 D Betriebs und Montagevorschriften 11 GB Operational mounting regulations 15 H Szerel si s zemeltet si el r sok 19 RUS 23 F Notice pour le Montan 27 SK Prev...

Страница 3: ...adovanou teplotu naopak zapojen na sol rn kolektory nebo tepeln erpadlo TUV jen p edeh eje a je nutn za adit dal nap elektrick oh va kter doh eje vodu na po adovanou teplotu nebo do akumula n n doby n...

Страница 4: ...4 4 Zobrazen verz NADO a popis v vod...

Страница 5: ...l u itkov vody mus b t vybaven membr nov m pru inou zat en m pojistn m ventilem Jmenovit sv tlost pojistn ch ventil se ur uje podle normy SN 06 0830 Oh va e nejsou vybaveny poji ovac m ventilem Pojist...

Страница 6: ...dvoulet m provozu kontrolu a p padn vy i t n n doby od vodn ho kamene kontrolu a p padnou v m nu anodov ty e ivotnost anody je teoreticky vypo tena na dva roky provozu m n se v ak s tvrdost a chemick...

Страница 7: ...CWU w zbiorniku wewn trznym na dan temperatur natomiast po czenie z kolektorami s onecznymi lub pomp ciep a umo liwia tylko wst pne nagrzewanie CWU i jest konieczne u ycie nast pnego np elektrycznego...

Страница 8: ...8 4 Przyk ad wersji NAD...

Страница 9: ...l dn maks 80 Na wlocie zimnej wody jest konieczny zaw r bezpiecze stwa Ka dy taki podgrzewacz ciep ej wody u ytkowej musi by wyposa ony w membranowy zaw r bezpiecze stwa obci ony spr yn rednic nominal...

Страница 10: ...ewacza co obni y straty ciep a Podgrzewacze musz posiada zaw r spustowy na doprowadzeniu zimnej wody do podgrzewacza do cel w ewentualnego demonta u lub naprawy Podczas monta u urz dzenia zabezpieczaj...

Страница 11: ...meist die direkte Erw rmung des Warmbrauchwassers im inneren Beh lter auf die gew nschte Temperatur im Gegenteil dazu w rmt die Schaltung mit den Solarkollektoren oder einer W rmepumpe das Warmbrauchw...

Страница 12: ...12 4 Abbildung der Versionen NAD...

Страница 13: ...on Warmbrauchwasser muss mit einem membranfederbelasteten Sicherheitsventil ausgestattet werden Die Nennweite der Sicherheitsventile wird gem der Norm SN 06 0830 festgelegt Die Warmwasserbereiter sind...

Страница 14: ...zu erm glichen Bei der Montage der Sicherungseinrichtung ist gem der Norm u268 CSN 06 0830 vorzugehen Wir empfehlen den Beh lter nach zweij hrigem Betrieb zu kontrollieren ggf von Kesselstein zu rein...

Страница 15: ...ection with boiler usually allows direct heating of HSW for required temperature inside the inner tank but connection to the solar collectors or heat pump only preheats and it is necessary to place an...

Страница 16: ...16 4 Illustration of NADO versions...

Страница 17: ...y valve with a membrane spring Nominal clearance of safety valves is defined by standard SN 06 0830 Heaters are not equipped with a safety valve The safety valve must be easily accessible as close to...

Страница 18: ...eplacement of the anode rod after two years of operation The anode life is theoretically calculated for two years of operation however it changes with water hardness and chemical composition in the pl...

Страница 19: ...eg t be el meleg t s Kaz nhoz val csatlakoztat s eset n a bels zom ncozott tart lyban k zvetlen l el ll that a megfelel h m rs klet haszn lati melegv z de p ld ul napkollektoros vagy h szivatty s rend...

Страница 20: ...20 4 Az egyes NAD verzi k br i...

Страница 21: ...nyom s alatt zemeltett haszn lati melegvizet el ll t rendszerbe rug val terhelt membr nos biztons gi szelepet kell be p teni A biztons gi szelep m ret t a SN 06 0830 szabv ny hat rozza meg A melegv z...

Страница 22: ...zabv ny szerint kell elv gezni K t v zemeltet s ut n javasoljuk a tart ly kitiszt t s t a v zk elt vol t s t valamint az an d r d ellen rz s t esetleg cser j t Az an d lettartama k t v azonban f gg a...

Страница 23: ...600 1990 750 750 2020 1000 850 2053 RUS 1 NADO 500 750 1000 1 5 2 182 TPK NADO TJ 6 4 TPK 2 3 NADO v1 210 G6 4 TJ G 6 4 NADO 140v1 140 200 NADO v2 210 1 5 2 SOLAR G6 4 TJ G 6 4 140 NADO v3 210 1 5 2 S...

Страница 24: ...24 4 NADO...

Страница 25: ...25 5 6 0 3 90 C 0 6 90 C 2 3 1 110 C 0 3 5 45 C 80 06 0830 20 5...

Страница 26: ...26 0 6 0 6 do 0 48 0 7 0 7 do 0 56 1 1 do 0 8 06 0830 NEODUL 100 20 C...

Страница 27: ...ns la plupart des cas le chauffage direct de l ECS la temp rature voulue dans un r cipient int rieur Par contre la combinaison avec des collecteurs solaires ou une pompe chaleur ne sert qu au r chauff...

Страница 28: ...28 4 Repr sentation des versions NADO et description des sorties...

Страница 29: ...C 45 C et l humidit relative ne d passe pas 80 l entr e d eau froide une soupape de s curit est n cessaire Chaque chauffe eau sous pression ECS doit tre muni d une soupape de s curit pour ECS Le diam...

Страница 30: ...tage ou une r paration ventuelle Lors de l installation du dispositif de s curit proc dez conform ment la norme SN 06 0830 Apr s deux ans de fonctionnement il est recommand d effectuer le contr le de...

Страница 31: ...a po adovan teplotu naopak zapojenie na sol rne kolektory alebo tepeln erpadlo TUV len predhreje a je nutn zaradi al napr elektrick ohrieva ktor dohreje vodu na po adovan teplotu alebo do akumula nej...

Страница 32: ...32 4 Zobrazenie verzi NADO a popis v vodov...

Страница 33: ...us by vybaven membr novou pru inou za a enou poistn m ventilom Menovit svetlos poistn ch ventilov sa ur uje pod a normy SN 06 0830 Ohrieva e nie s vybaven pois ovac m ventilom Poistn ventil mus by dob...

Страница 34: ...ostupujte pod a SN 06 0830 Odpor ame po dvojro nej prev dzke kontrolu a pr padn vy istenie n doby od vodn ho kame a kontrolu a pr padn v menu an dovej ty e ivotnos an dy je teoreticky vypo tan na dva...

Страница 35: ...lumen l Storage volume l T rol si t rfogat l Volume de stockage l Objem z sobn ka l 764 744 130 772 772 772 772 772 130 999 999 999 117 971 117 117 117 117 117 116 987 987 130 130 128 128 80 NADO 1000...

Отзывы: