background image

2. Undo the captive

restraining screw

3. Hinge from bottom

and pull top
forward. Lower
outer cover to
remove

4. Fix directly to a flat wall or onto a flush mounting

conduit box or optional Pattress box using suitable
screws

RTS8 Combi-Stat Thermostat

The RTS8 is a 24V-230V AC/DC mechanical thermostat

that can be used for either 2 or 3 wire applications,

making it suitable for replacement of older 2 wire

thermostats with no Neutral, or 3 wire thermostat

replacement where a Neutral connection has been

used. (Optimum performance is attained with 3 wire

connection.)

IMPORTANT NOTES

The installation instructions must be followed for this

thermostat to operate correctly. Failure to do so may

result in inadequate room temperature control.

Particular attention should be paid to the sections on

wiring and set up. 

All electrical work should be carried out by a

competent person to conform to all relevant standards

and regulations.

Isolate/disconnect the power supply to the appliance

and/or system before commencing any electrical work.

A switch having a contact separation of at least 3mm

on both Live and Neutral poles must be incorporated

in the fixed wiring of the system to provide full

isolation of the mains supply.

Ensure that the system fuse is the correct rating. For

Gas fired radiator heating systems this is 3A.

INSTALLATION INSTRUCTIONS

Location

Care should be taken to mount the thermostat in a

position, which is not subject to direct sunlight or

draughts. Preferably it should be mounted on an inside

wall about 1.5m (5ft) above the floor in a position

where it can respond to room temperature but away

from the direct influence of radiators or other

appliances giving off heat.

Fixing

Standard cable entry

can be from the rear

or top, if bottom

entry or extra space

for cabling is

required use the

optional Pattress box. 
1. Pull temperature

setting knob

forward to remove.

Set up to be followed when wiring to Fig 6 only 
The thermostat utilises a series resistor as a heat
anticipator when wired in accordance with Fig 6
diagram.

To avoid inaccurate room temperature control it

is VERY IMPORTANT that the following set up
procedure is followed.

An electrical multimeter will be required for the

following procedure. 

• Isolate electrical supply

• Mount base unit to wall

• Connect wires to L and 2

• Turn red setting shaft until switch contact opens

(see Fig 4)

• Set meter to 1 amp, current range

• Carry out electrical safety checks on the system/

appliance and turn system ON

• Put meter probes across L and 2

• Read current. Expected reading for Gas CH

systems = 0.1A to 0.6A 

• If reading is BELOW 0.6A wire as Fig 6 (isolate

electric supply before rewiring)

• If reading is ABOVE 0.6A wire as Fig 7 (isolate

electric supply before rewiring)

• Reset the red setting shaft so that the small slot

is vertically downwards

• Reassemble thermostat

Range limiting
The setting range may be limited or a particular
setting locked through the use of the mechanism
to be found under the control knob.

To set the range limits:

1. Set thermostat to the desired temperature

2. Remove the setting knob by carefully pulling it

forward

3. Lift and rotate the two limiting arms to

reposition them in the required notches

4. Replace the knob in its previous position

Continued overleaf

Earth loop  

connection

Red  

setting  

shaft

Screw  

slots

Fig 1

Fig 4

N

2
3
L

Acc.
Acc.

Call for heat

LOAD

L

N

N

230V AC 50Hz
Fused 3A

Fig 5. 

3 wire connection. Max load = 2A
Suitable for most wet CH systems 

N

2
3
L

Acc.
Acc.

Call for heat

LOAD

L

N

24V-230V AC/DC
Fused 3A

N

2
3
L

Acc.
Acc.

Call for heat

LOAD

L

N

24V-230V AC/DC

Suitably rated

fuse

Fig 7. 

2 wire connection. No Neutral. Load = 0.6A to 6A 
Typically for higher loads (ie electric heating) 

Fig 3

Fig 2

Fig 6. 

2 wire connection. No Neutral. Load = 0.1A to 0.6A 
Suitable for most wet CH systems 

Note:  Use this connection for gas CH systems, where there is 

no neutral wire, and follow set-up procedure. If current 
reading above 0.6 amps, wire as Fig 7. 2 wire 
connection no Neutral. 

Wiring
The RTS8 is double insulated and does not require an
earth, if there are existing earth wires that need to be
connected, use the Earth loop connection (Fig 4).

Terminate the wiring as shown in diagrams (Figs 5 to

7), ensure that the correct diagram is followed to match
the current load (Amps) and cabling of the heating
system. If unsure of current load, follow Set up
procedure 
to determine it.

Combi-Stat boiler compatibilty information

Make

Model

Worcester

Series

2/3 wire*

CDi Series

2/3 wire*

Si Series

2/3 wire*

Vaillant

EcoMax

2/3 wire*

TurboMax

2/3 wire*

Ideal

Isar

2 wire

Response

2 wire

Mini

2 wire  

Glow-Worm Energysaver 2/3 wire*

Compact E 2/3 wire*

Baxi

80 Eco

3 wire recommended 
by Baxi across range

Combi 80E 3 wire recommended 

by Baxi across range

105E

3 wire recommended 
by Baxi across range

Maxflow

3 wire recommended 
by Baxi across range

Potterton

Bahama

3 wire recommended 
by Pott’s across range

Puma

3 wire recommended 
by Pott’s across range

Combi

3 wire recommended 
by Pott’s across range

* Where 2/3 wire is indicated use 3 wire connection for
optimum performance. 
This information is for guidance only as the boiler
manufacturer may change the mode of operation at any
time without warning. For further information please
refer to the boiler manufacturers handbook.

Combi-Stat boiler compatibilty information

Make

Model

Worcester

Series

2/3 wire*

CDi Series

3 wire

Si Series

2/3 wire*

Vaillant

EcoMax

2/3 wire*

TurboMax

2/3 wire*

Ideal

Isar

2 wire

Response

2 wire

Mini

2 wire  

Glow-Worm Energysaver 2/3 wire*

Compact E 2/3 wire*

Baxi

80 Eco

3 wire recommended 
by Baxi across range

Combi 80E 3 wire recommended 

by Baxi across range

105E

3 wire recommended 
by Baxi across range

Maxflow

3 wire recommended 
by Baxi across range

Potterton

Bahama

3 wire recommended 
by Pott’s across range

Puma

3 wire recommended 
by Pott’s across range

Combi

3 wire recommended 
by Pott’s across range

* Where 2/3 wire is indicated use 3 wire connection for
optimum performance. 
This information is for guidance only as the boiler
manufacturer may change the mode of operation at any
time without warning. For further information please
refer to the boiler manufacturers handbook.