2-22
Connecting Voltage Measurement Cables, continued
Measurement
cable set with
optional fuse
diagram
WARNING
To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING
To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
WARNING
For continued protection against risk of fire or shock hazard replace only with
same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD0.30 rated 600V AC/DC, 0.3A fast blow.
WARNING
Do not replace fuse again if failure is repeated. Repeated failure indicates a
defective condition that will not clear with replacement of the fuse. Refer
condition to a qualified technician.
NOTE: 2 FT CABLE
INCLUDED WITH
FUSE VOLTAGE
ADAPTER
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
FUSE
VOLTAGE
ADAPTER
OPTIONAL
A+
B+
C+
D+
A-
B-
C-
D-
To AC Voltage Module with safety jack
or terminal block connectors
SF-207