START-UP

1.

Close control air line and balance  line

needle valves as well as inlet isolation
shut-off valve. 

2.

Bring up system pressure.

3.

Fully open control air needle valve.

Check for leaks in control air line. Push
the “Push to Test” button on top of the
Model 1700

TM

to verify the air cylinder

strokes, opening the discharge ball valve.
Leave control air needle valve open.

4a. Applications where the balance line
is connected back to vessel being
drained.

Fully open the balance line nee-

dle valve. Check for air leaks on balance
line and fittings. Leave balance line nee-
dle valve fully opened.  The needle valve
can be used as an isolation shut-off valve.

4b. Applications where the balance line
needle valve is vented to atmosphere
or connected to a header pipe leaving
the vessel being drained.

Open the bal-

ance line needle valve only enough to
ensure a small amount of air can flow
through it. This will be adjusted in a later
step.

5.

Gradually open the inlet isolation shut-

off valve to the full open position to
allow liquid to enter the Model 1700

TM

.

The reservoir will fill until the float is
raised to the upper position actuating the
control circuit extending the air cylinder
and opening the ball valve. Once the dis-
charge starts, the liquid level in the
Drain-All reservoir begins to lower.  This
lowers the float back to its original posi-
tion which deactivates the control circuit
closing the ball valve.  

6a. Applications where the balance line
needle valve is vented to atmosphere
or connected to a header pipe leaving
the vessel being drained.

With liquid in

the reservoir and the liquid discharge ball
valve in the closed position, close the
balance line needle valve.  As you slight-
ly open the balance line needle valve,
look into the translucent sleeve just
above the inlet port and look for a trickle

of small bubbles. Continue to open the
needle valve until you see these bubbles
indicating a proper setting for the balance
line needle valve. Remember that bub-
bles will only be seen if there is a pres-
sure differential (when balance line is
vented to atmosphere or to a header leav-
ing the vessel being drained).

6b

. When the balance line is connected

back to the vessel being drained, there is
no pressure differential between the inlet
and balance line and there will be no
bubbles in the liquid. In this application
keep the balance line needle valve in this
connection fully open. The top of the
Model 1700

TM

must be below the bottom

of the vessel being drained.

7.

Once properly installed, no further

adjustments to the Model 1700

TM

are nec-

essary.  The Model 1700

TM

is fully auto-

matic, discharging on demand as needed
when liquid accumulates. 

TROUBLESHOOTING

1.   Water does not enter.

A.

Balance line isolation shutoff valve is

closed which does not allow liquid to
enter the Model 1700

TM

.   

Solution:

Adjust balance line needle

valve per installation instructions.

B.

Liquid inlet shut-off valve is closed.   

Solution:

Fully open liquid inlet shut-off

valve.

C. 

Vessel drain, and/or pipe from vessel

drain to Model 1700

TM

inlet is plugged.  

Solution: 

Clear obstruction.

D.

Location of balance line connection

causes higher balance line pressure than
liquid inlet pressure. Model 1700

TM

is

“back flowing”.   

Solution:

Refer to installation instruc-

tions for proper balance line installation.

2.  Fills and will not drain.

A.

Control air line needle valve is closed,

or not fully open. 

Solution:

Fully open control air needle

valve to full open.

B. 

Lack of adequate air pressure on con-

trol air line.  

Solution:

Provide more than the mini-

mum required PSIG to control air line
connection per the product specification.
If there is not enough control air pressure
available, there are lower control air
pressure options available - contact your
distributor for details.

C.

Hole in valve stem clogged. 

Solution: 

Clear obstruction. Do not alter

hole diameter.

D.

Filter element clogged or dirty.  

Solution:

Replace part.

3.   Discharge ball valve stays open.

A.

Center tube magnet installed upside

down, i.e., north and south poles
reversed.   

Solution:

Reinstall center tube magnet

rotating it 180 degrees, end for end.

B.

Bleed hole for air cylinder clogged.

Solution:

Clear bleed hole on side of air

cylinder located on opposite side from
control air connection to the cylinder. Do
not alter hole diameter.

C.

Center tube magnet stuck or not prop-

erly sealing against valve stem.  This can
result from excessive oil and water con-
taminates allowed to get into the control
air lines and then into the center tube,
thereby coating the center tube magnet
and causing it to stick.  

Solution:

Clean center tube and center

tube magnet and reassemble.  Also, if
possible, connect the control air line to a
clean dry air source which will prevent
reoccurrence.

4. Excessive bubbling action in reser-
voir.

A. 

Air leak in balance line and/or fittings.  

Solution:

Refer to installation instruc-

tions and start-up procedures.

B. 

Balance line needle valve opened too

far.  

Solution:

Adjust balance line needle

valve per installation instructions.

START-UP & TROUBLESHOOTING

Page 3

022802 Model 1700-IG

Содержание 870100

Страница 1: ...tents 4 444 217 4 562 855 4 574 829 5 004 004 5 014 735 5 983 919 Model 1700TM TM Model 1700 TM Part Number 870100 Max Liquid Temp ºF ºC 170 76 7 Max Liquid Pressure PSIG BARG 170 11 7 Control Air Min PSIG BARG 40 2 8 Control Air Max PSIG BARG 130 9 0 Ht cm 11 27 9 Width cm 9 1 4 23 5 Depth Inlet BV cm 10 1 2 26 7 Inlet Outlet NPT 1 2 Control Air NPT 1 4 Balance Line NPT 1 8 Max Capacity GPM l h 3...

Страница 2: ...n follow the start up instructions for adjusting the opening of the balance line needle valve There will be very little air loss to atmosphere NO MANIFOLDS There cannot be multiple system drains through a manifold to one Model 1700TM This will not work because all system drains will not be of the same pressure Therefore the liquid from the higher pressure drain lines will bypass the Model 1700TM a...

Страница 3: ...he Model 1700TM must be below the bottom of the vessel being drained 7 Once properly installed no further adjustments to the Model 1700TM are nec essary The Model 1700TM is fully auto matic discharging on demand as needed when liquid accumulates TROUBLESHOOTING 1 Water does not enter A Balance line isolation shutoff valve is closed which does not allow liquid to enter the Model 1700TM Solution Adj...

Страница 4: ...Page 4 MODEL 1700TM DIMENSIONAL PRINT 022802 Model 1700 IG ...

Страница 5: ... valve starting the discharge of accumulated liquid When the correct amount of liquid has been discharged leaving a liquid seal in the reservoir the float has been lowered to a point where the float magnet is below the center tube magnet In this position the float magnet repels the center tube magnet back upward against the valve stem orifice which seals off the control air flow to the actuating c...

Страница 6: ...Page 6 MODEL 1700TM COMPONENT PARTS DRAWING 022802 Model 1700 IG ...

Страница 7: ...ID x 0 069 T Viton Brown 1 14 200170 Center Tube 1 150 Dia x 4 500 L O ring Seal 6061 T6 Aluminum 1 15 302270 Hex Bolt 1 2 13 x 10 L Zinc Plated Steel 4 16 300314 Pneumatic Cylinder 2 Dia 40 130 PSI Stainless Steel Body and Rod Aluminum Ends 1 17 100480 Float Polyurethane Bullet Shaped 1 18 302200 Sleeve O ring 5 519 ID x 0 137 T Viton Brown 2 19 100300 Sleeve 6 ID x 7 L x 125 T Epoxy Fiberglass T...

Страница 8: ...e control air line be hooked together via a tee connection No Do not do this Each of these air lines has its own specific purpose and should never be tied together The con trol air should be the cleanest driest air available since it supplies air to the con trol circuit to operate the pneumatic actu ating cylinder which functions best and lasts longer if clean dry air is used The balance line allo...

Страница 9: ...ion With the addition of a Drain All cycle counter on the Drain All unit it is easy to track how much liquid is produced over any period of time This is particularly important for benchmarking system equipment performance and per forming trend analysis For example it is essential to know the quantity of liquid produced by a compressed air system to properly size oil water separators The counter co...

Страница 10: ...ups The Model 1700TM center fore ground in the photo above is Drain All Inc s flagship product used in facilities around the world to remove liquid from compressed air system applications In addition to the Model 1700TM there are other Product Groups that can include different models for specific require ments There are also situations where specific applications require the use of compo nents mat...

Страница 11: ...at Drain All Inc s election and cost to the repair or replacement of the defective part that does not comply with any applicable warran ty and shall in no event exceed the original purchase price of the unit Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limi tation may not apply to purchaser All claims under this warranty should be made by...

Страница 12: ...rst four applications above the balance line is connected back to the vessel that is producing the condensate The pres sure on the incoming condensate to the trap and the pressure in the balance line are the same and the trap is filling by gravity For this method the top of the trap must be below the bottom of the vessel being drained Method 2 Connect the balance line port to the head er pipe leav...

Отзывы: