40
Dräger VarioGard
Installation
The internal power supply of a central unit can only generate limited
electrical power via the system bus. The power requirements of
all installed slaves can be determined as a busload as follows:
The maximum system bus length is derived from the voltage drop
across the cables used.
The total of all the busloads must not exceed 32 without an additional
power supply. The maximum total cable lengths, depending on the
total planned busloads, are shown below:
Bus load NEW
Current consumption
(mA)
VarioGard TOX (old)
2
50
VarioGard 3000 EC
1
30
VarioGard 3200 CAT
2.5
75
VarioGard 33x0 IR
2
60
VarioGard Relay Module
4
120
VarioGard Repeater
6
180
VarioGard ConverterM for
each 4..20 mA input
2
+ n x 1.5
60
n x 45
VarioGard central unit
maximum total
32
1200