Seite 33
A
djustment of the Dip Switches
DIP-Switch 1
Bus
ON Always "ON"
Language
1
9
10
11
German
ON
OFF
OFF OFF
English
ON
ON
OFF OFF
French
ON OFF ON OFF
Italian
ON
ON
ON
OFF
Spanish
ON
OFF
OFF ON
Dutch
ON
ON
OFF ON
turkish
ON OFF ON ON
4..20mA Current Interface
1
6
7
8 Warm-up
Error
4.. 20 mA
linear
ON OFF OFF OFF
3,2mA 3,2 mA
4 .. 20 mA
linear
ON ON
OFF OFF
0,8 mA 0,8 mA
0.. 20 mA
linear
ON OFF ON OFF
0 mA
0 mA
0 .. 20 mA
linear
ON ON
ON OFF
24 mA
24 mA
4 .. 20 mA
horiba
ON OFF OFF ON
3,2 mA 3,2 mA
4.. 20 mA
horiba
ON ON
OFF ON
0,8 mA 0,8 mA
0 .. 16 mA
horiba
ON OFF ON ON
0 mA
0 mA
0.. 10 V
linear
ON ON
ON ON
0 V
0 V
Gas
1
2
3
4
Methane 99%
UEG
ON OFF
OFF OFF
Buthane 99%
UEG
ON
ON OFF OFF
Propane 99%
UEG
ON
OFF
ON
OFF
Nonane 99%
UEG
ON
ON
ON
OFF
Relay
1
12
Mode 0
(*2)
ON
OFF
Mode 1
(*2)
ON
ON
UEG / LEL
1 5
Mode 0
(*1)
ON
OFF
UEG = default
Mode 1
(*1)
ON
ON
LEL
Содержание VarioGard IR EX