Ex LC NPT1 DD and Polytron SE Ex HT M DD:

z

These metal housings need to be earthed at site by means 
of the external PE-terminal, so connect the cable shielding 
to the internal PE-terminal within the housing only. 

z

To avoid double earthing it is not recommended to connect 
the cable shielding to the earth terminal of the rack system 
or panel at the controller site.

The maximum cable length between sensing head and con-
troller depends on the cable’s core cross section and the con-
troller unit used:

Polytron SE Ex:

z

Connect terminals 1, 2, and 3 of the sensing head with the 
terminals 1, 2, and 3 of the Polytron rack system.

REGARD Ex:

z

Connect terminals 1, 2, and 3 of the sensing head with the 
terminals 10, 11, and 12 of the REGARD rack system.

z

Having finished the electrical installation fit the cover secu-
rely to the body of the enclosure, observe correct fitting of 
the gasket and ensure that the enclosure is free of dust.

Core cross-section:

 

1,0 mm

2

1,5 mm

2

2,5 mm

2

Polytron SE Ex, 
max. cable length:

950 m

1450 m

2400 m

REGARD Ex, 
max. cable length:

450 m

750 m

1200 m

Image 
no.

1)

1) The image numbers refer to the images printed on page 5.

Part no.

Sensing head
Polytron SE Ex

Category Ambient temperature

Ta

min

Ta

max

Typ of protection
Gas

Type of protection
Dust

IP

1

68 12 711 PR M1 DD

II 2 GD

- 50 °C + 40/55/85 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

2

68 12 710 PR M2 DD

II 2 GD

- 50 °C + 40/55/85 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

3

68 12 718 PR M3 DD

II 2 GD

- 50 °C + 40/55/65 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

4

68 12 800 PR NPT1 DD

II 2 GD

- 40 °C + 40/55/60 °C

Ex d IIC T6/T5/T4

Ex tD A21 T130°C 66

5

68 12 722 LC M1 DD

II 2 GD

- 40 °C + 40/50/85 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

6

68 12 721 LC M2 DD

II 2 GD

- 40 °C + 40/50/85 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

7

68 12 719 LC M3 DD

II 2 GD

- 40 °C + 40/50/65 °C

Ex de IIC T6/T5/T4

Ex tD A21 T130°C 66

8

68 12 801 LC NPT1 DD

II 2 GD

- 40 °C + 40/50/60 °C

Ex d IIC T6/T5/T4

Ex tD A21 T130°C 66

9

68 12 720 HT M DD

II 2 GD

- 50 °C + 40/55/85/

150 °C

Ex de IIC T6/T5/T4/
T3

Ex tD A21 T130/
T200°C

66

00333181.eps

1

2

3

1

2 3

1

2 3

10

11

12

1

16

REGARD Ex

00433181.eps

1

2

3

PE

1

2

3

4

10

11

12

1

16

REGARD Ex