Factory default settings
Dräger Polytron 5100
25
6
Factory default settings
6.1
Settings which can be changed
via
the
menu
Menu
Factory Default Setting
A1 Set
depending on the sensor
A2 Set
depending on the sensor
A1 RIS / FALL
rising (except O2 falling)
A2 RIS / FALL
rising
A1 Lat / nLat
nLat
A2 Lat / nLat
Lat
A1 Ack / nAck
Ack
A2 Ack / nAck
nAck
A1 ENRG ON / OFF wired in
Docking Station
energized
/ NO
(normally
open)
A2 ENRG ON / OFF wired in
Docking Station
energized
/ NO
(normally
open)
Cal Set
steady
Pass Set
0000
LCD Set ON / OFF
on
FAIL FREQ PULS / STDY
PULS (pulsing)
6.2
Fixed settings
Fault
Meaning
Fault Relay
(cannot be
changed) / wired in
Docking Station
energized / NO (normally open)
Yellow Fault LED
Lit if a Fault message is available, see
Section
5.3 on Page
22.
Red Alarm LED
Single blink if A1 condition is present.
Double blink if A2 condition is present.
If an alarm is configured acknowledge-
able and the alarm is acknowledged,
single/double blink changes into
continuous lit.
Alarm Hierarchy
A2 overrides A1 on the LED. However,
the
A1 and A2 relays operate
independently. I.e. if A1 is acknow-
ledgeable, A2 is not, and the gas
concentration is such that it triggers A1
and A2: acknowledging will cause the A1
relay to release. However, the red LED
will still double blink as long as the A2
condition continues to exist.