Installing 

Electrical Installation

When installing, the entire wiring must meet currently valid national 
regulations regarding the installation of electrical devices, and - if necessary 
- the national regulations regarding the installation in potentially explosive 
atmospheres. In case of doubt, the o

  cial responsible authorities are to be 

consulted prior to installation of the device.  

CAUTION

Ensure that any power is switched off before connecting any 
cabling to the flame detector.  The connections are made in the 
rear terminal compartmant through suitable certified glands.

!

 

To access the terminal connections release the terminal cover locking screw using 
a 2 mm hexagon key and unscrew the terminal compartment cover. 
The detector requires 24 Volts DC nominal supply voltage, also available are an 
isolated 4-20mA output and 3 relays. 

Each detector has a built in terminal block of 37 terminals providing for a number 
of output connections:
• 4 terminals for 24v DC power 
• 2 terminals for 4 – 20mA output 
• 6 terminals for alarm relay 
• 6 terminals for fault relay 
• 6 terminals for spare relay 
• 2 terminals for manual test activation 
• 2 terminals for internal linking of cable screens (shields) 
• 2 terminals for passive components 
• 1 terminal for connection to the enclosure (housing) 

A 0-20mA current loop is provided along with an alarm relay and fault relay. A 2 
input manual test inputs are provided which take a 24V input (referenced to an 
external 0V, hence two inputs). This input allows the user to manually activate an 
optical test. There is also a pair of terminals (35 & 37) into which is connected 
a user de

fi

 ned passive component to allow for interfacing to a number of vendors 

fi

 re panels. 

NOTICE

Where terminals 35 & 37 are not interfaced with vendor panels but 
the alarm relay is required it is necessary to place a hard wired link 
between terminals 35 & 37.

!

Each terminal is capable of accepting a suitably crimped/ferruled 2.5mm² core 
wires. The detector also has an external earth (ground) connection capable of 
accepting 4mm² wires.

NOTICE

Wiring must be in accordance with local regulations.  No more than 
one conductor should be used in each terminal.  Duplicate terminals 
are supplied to allow ‘daisy chaining’ of connections if required.

Duplicate terminals are not supplied for 4-20mA connections, which 
cannot be ‘daisy-chained’.

!

Figure 2: Wiring for operation with isolated 4-20mA output

37

29

28

15

14

1

+24 VDC

0 VDC

+4-20mA

-4-20mA

8

10

12 13

Содержание FD 10 Series

Страница 1: ...tor FD 10 Range Instructions For Use en WARNING You must read understand and follow these instructions for use before you use the flame detector in order to ensure the proper operation and function of...

Страница 2: ...servation of these instructions This flame detector is only to be used for the purposes specified herein Maintenance The device must be inspected and serviced by experts at regular intervals and a rec...

Страница 3: ...lecting the Detector Position Mechanical Installation To ensure optimum performance and to minimise down time and false alarms consideration to the location and position of the flame detector must be...

Страница 4: ...activation 2 terminals for internal linking of cable screens shields 2 terminals for passive components 1 terminal for connection to the enclosure housing A 0 20mA current loop is provided along with...

Страница 5: ...able non setting silicone grease Hand tighten the terminal cover then tighten the locking screw with a 2mm hexagon key see Technical Specification section Finally the protective cover is fitted over t...

Страница 6: ...cted Red LED indicates a hazard has been detected Maintenance Observe respective national regulations e g in Europe 60079 17 applies The Draeger Flame Detector FD10 Range performs an automatic optics...

Страница 7: ...ctor outer cover weather shield is moulded ABS polycarbonate and is not antistatic Therefore CLEAN ONLY WITH A DAMP CLOTH Accessories The following accessories and spare parts are o ered for the Draeg...

Страница 8: ...than 5kg 11lbs Regulatory Approvals ATEX Certificate Number ITS 04 ATEX 11807 ATEX II 2 G EEx d IIC EEx d ia IIC T6 Tamb 50 C to 60 C EEx d ia IIC T5 Tamb 50 C to 70 C IECEx Certificate Number ITS 04...

Страница 9: ...y UK Ltd Ullswater Close Blyth Riverside Business Park Blyth Northumberland NE24 4RG United Kingdom Tel 44 1670 352 891 Fax 44 1670 450 033 www draeger com Distributed in the US by Draeger Safety Inc...

Отзывы: