Dr. Neuhaus ZDUE-GSM-PLUS-V Скачать руководство пользователя страница 2

ZDUE-GSM-PLUS-V   Installation Instructions

 

Connecting the device 

 
First connect the meter to the device and then connect the 
power supply. 
 

 

 
The device is equipped with 3 different meter interfaces, 
which are wired in parallel. 
 

RS232 interface (RJ45 jack): 

Pin 

Signal 

Description 

DSR 

Output; Always active 

GND 

Signal ground 

TXD 

Output; Data to meter 

RXD 

Input; Data from meter 

Signals and levels according to V.24 / V.28.  
All other pins are reserved. 

 

RS485 interface (terminal block): 

Signal 

Description 

RT- 

Negative RS-485 interface signal  

RT+ 

Positive RS-485 interface signal  

Dual-wire RS485 interface to connect up to 32 
transceivers. The bus connection is terminated to 
Z=120 Ω (nominal) (RT+ to RT-) and the cable length 
is limited to 1000m. 

 

CL1 interface (terminal block): 

Signal 

Description 

RTX- 

Negative CL1 interface signal  

RTX+ 

Positive CL1 interface signal  

20mA power interface (current loop) to connect meters 
with the power supply interface according to DIN EN 
62056-21. Approx. 4 meters can be connected to this 
interface. 
 
The CL1 interface is optional. Devices without CL1 
interface do not contain RTX- / RTX+ terminals. 
Please refer to the label of the terminal block. 

 

Important:  
If no meter is connected to the CL1 interface, the 
RTX- and RTX+ contacts need to be short-
circuited. Otherwise, the other interfaces will not 
operate. 

 
Auxiliary power source (HS; terminal block): 

Signal 

Description 

HS- 

Negative pole of the auxiliary power supply 

HS+ 

Positive pole of the auxiliary power supply 

Auxiliary power supply of 9V / max. 100mA 
The auxiliary power supply is not available for all the 
ZDUE-GSM-PLUS-V models. 

 

 

Power supply (terminal block): 

Signal 

Description 

AC: U

nom

 = 100VAC ... 230VAC 

DC: U

nom

 = 60VDC ... 100VDC

 


I

nom

 

= 84mA … 42mA

 

 
 

 
 

 

Connecting the antenna 

 

The antenna is connected to the Type SMA antenna jack 
(ANT). The antenna should be installed to ensure 
adequate signal quality. Make sure that there are no large 
metal objects (e.g. reinforced concrete) near the antenna, 
since they will have an adverse affect on signal quality. 
Please observe the safety instructions at the beginning of 
this manual when installing the antenna. Have this 
installation done by a qualified professional! Be sure to 
observe the instructions included with your antenna. 
 
 

Light-emitting diodes (LEDs) 

 
Status LED (2) / Green & Yellow with light pipe 

Permanently green 

Supply voltage available 

Permanently yellow 

GSM module on 

Depending on the firmware version, both LEDs may be off in 
case of a missing or defect SIM card. 

 
Current Loop LED (11) 

Permanently green 

Meter connected to the CL1 
interface or CL 1 interface short-
circuited. 

 
GSM-Status-/Error LED (1) / Orange 

 3s on / 3 x flashing 

Network search 

 3s on / 2 x flashing 

Error status 

 3s on / 1 x flashing 

SIM/PIN error 

Permanently off 

Signal strength unknown 

 3s off / 1-4 x flashing  

Signal strength (1=low; 4=high) 

Permanently on 

GSM connection active 

This LED operates in meter mode only. 

 

Service push button (7) 

Push the button 1x 
for more than 5 
seconds. 

The parameters being set by EN 62056-
21 commands will be deleted and the 
factory settings are reloaded. 

Push the button 
when switching 
the power on. 

The actual firmware version will be output 
at the local interface (19200bps; 8N1). 

The service push button operates in meter mode only. 

 
 

 

 

 

 

 

Copyright Statement 

The information published in this document is under copyright. Any 
translations, reprints, reproduction and storage in data-processing systems 
require the express prior consent of the manufacturer. 

 
Subject to technical modification. 

All trademarks and product names are trademarks, registered trademarks or 
product names of the respective owners. 
All information is based on the information provided by the manufacturer. 
No guarantee or liability will be assumed for any error or omissions. 
The contents of this handbook and the technical specifications may change 
without prior notice. The descriptions of the specifications in these 
instructions do not in any way represent a contract. 
 
© Dr. Neuhaus Telekommunikation GmbH 
Doc.-No. 8191AD013 / Version 1.3 / May 2016 

 

 

Отзывы: