31
Analogs
6.2
The Analog tab displays the current state of the voltage on your NetGuardian. To monitor your analogs in the
Turn-up and Test Mode, click on the Analog tab. Before you can monitor your analogs, you will be prompted to
read the analog channel descriptions from the NetGuardian 216 NVRAM.
Fig. 6.3.
Download analog descriptions to monitor analogs
To activate your channel and view the voltage in scaled units, enter your analog descriptions and threshold range
in the Editor Mode > Analog Alarms tab — see section 5.10 (Editor Analog Alarms Tab) for more information.
Fig. 6.4.
Monitor Analog Values
When an alarm is triggered, a red box will appear under the appropriate alarm type column: major under (MjU),
minor under (MnU), minor over (MnO), and major over (MjO). See Section 10 (Reference Information) Table A3
for channel locations.
Relays
6.3
Fig. 6.5.
The Relays Tab
The Relays tab displays the current state of the NetGuardian's two control relays. From this tab you may latch and
unlatch relays or you can latch them momentarily.
To latch a relay, click the Latch button. The relay's green display box will turn red and read "Latched." The Latch
button will also change to a Release button.