Страница 1: ...User Manual Building Status Unit II October 22 2004 D OC UM04A 22100 Visit our website at www dpstelecom com for the latest PDF manual and FAQs...
Страница 2: ...o make a derivative work by either mechanical electronic or any other means in whole or in part without prior written consent from DPS Telecom except as required by United States copyright laws The ma...
Страница 3: ...re the BSU II 7 5 Setting Internal Address 7 1 5 Setting the COM Port Baud Rate 7 2 6 Configure the NetGuardian 8 6 Using NGEdit 8 1 6 Configure the Sound On Time Settings 8 1 1 7 Using the Web Browse...
Страница 4: ......
Страница 5: ...ce to the NetGuardian via 4 wire RS485 interface and may be located up to 1500 feet away The NetGuardian will issue an alarm any time the communication to the BSU is interrupted so you will have const...
Страница 6: ...make sure that all of the following items are included If some parts are missing or if you ever need to order new parts please refer to the part numbers listed and call DPS Telecom at 800 622 3314 Bui...
Страница 7: ...then slide it down to lock into place Wire for Communication 6 2 6 2 1 Connection to the NetGuardian 832A The BSU II support is available for the NetGuardian Contact DPS for BSU II support for KDA IA...
Страница 8: ...X Negative 4 RX Positive White Blue 1 TX Positive Table 6 A Data port 8 and 4 Wire pinout connections Wire for Power 6 3 GND 48 VDC Fig 6 2 2 position barrier plug Use the following steps to wire the...
Страница 9: ...nding addresses Note The addressing begins at address 1 and increments in sequences up to address 12 Fig 7 1 The BSU II set to Internal Address 2 DIP Switch Definition 1 4 Address 5 7 Baud 8 reserved...
Страница 10: ...ate definitions Configure the NetGuardian 8 The NetGuardian must be provisioned to operate the BSU II You ll need to specify the number of BSU IIs on the communication bus the data port baud rate and...
Страница 11: ...ound timer only affects the duration of the audible alarm annunciation Set the value between zero and 120 and set the units to either seconds or minutes Sound may be manually overridden by pressing th...
Страница 12: ...s the number of BSU IIs connected to the NetGuardian see Figure 8 4 4 The default settings will automatically appear in Port 8 5 You may select a different baud rate by clicking on the baud rate itsel...
Страница 13: ...units to either seconds or minutes Sound may be manually overridden by pressing the acknowledge button on the front of the BSU II or the NetGuardian Use the following steps to configure your Sound On...
Страница 14: ...ation failure communication link idle for more than 2 mins Fuse Alarm Red Solid Blown fuse Table 9 A BSU II LED descriptions The COMM LED indicates communication with the host A red flash shows receiv...
Страница 15: ...tatus of bi directional communication On the unit a red blink indicates data receive while a green blink indicates data transmitted During normal operation the LED will flash red green If you observe...
Страница 16: ...D off Note Only alarms associated with a notification device are reported to the BSU II NetGuardian System Alarm 11 3 If communication is lost or not established with the BSU II the NetGuardian will s...
Страница 17: ...ort or disturb the upgrade process in any way while downloading is in progress as this may cause the unit to become inoperable When the firmware download is complete click the Exit button to exit Coml...
Страница 18: ...P M Pacific time During these hours Technical Support representatives are on duty in our fully equipped simulation lab Emergency Assistance Emergency assistance is available 24 hours a day 7 days a w...
Страница 19: ...r lightning unless and to the extent that the product specification provides for resistance to a defined disaster e damage caused by unauthorized attachments or modifications f damage during shipment...
Страница 20: ...www dpstelecom com 4955 E Yale Fresno CA 93727 Support 559 454 1600 Sales 800 622 3314 Fax 559 454 1688 We protect your network like your business depends on it TM...