Doc. #
: M1800, Rev. 06
Page 65 of 101
www.opwglobal.com
Hydrocarbon Liquid Sensor with Water
Indicator
OPW P/Ns: 6 feet: 30-0234-HW-06; 15 feet: 30-0234-HW-15;
20 feet: 30-0234-HW-20
Hydrocarbon Liquid Sensor Installation
The Hydrocarbon Liquid/Water, which is available in lengths of 6 feet
(1.8 m), 15 feet (4.6 m) and 20 feet (6.1 m), is used primarily for
monitoring wet wells with fluctuating groundwater tables. The sensor
contains a carbon/polymer material that changes its resistance when
exposed to liquid hydrocarbons. Additionally, a water sensor that
relies on the conductivity of water to detect its presence is utilized,
providing the ability to discriminate between hydrocarbon liquid and
water. An alarm condition will result from the absence of groundwater
in a monitoring well. Detection of fuel entering the containment area
(indicating a leak) will also result in an alarm condition, as will a break
in the cable or sensor malfunction.
*NOTE
: Maximum Wiring Length is the maximum length of cable to
be used to connect all sensors on an individual channel. This length
includes run of cable from I.S. Barrier to each sensor board in the
string.
Hydrocarbon Liquid/Water Sensor Specifications
Primary Use(s):
Monitoring wells
Detects:
Liquid hydrocarbons and water
Operating Temperature:
-40°F to 158°F (-40°C to +70°C)
Dimensions:
Length: 6’ (1.9 m), 15’ (4.6 m) or 20’ (6.1 m)
Diameter: 0.7” (1.8 cm)
Nominal Resistance:
Uncontaminated: 1,000
– 3,000 ohms/ft
Contaminated: 30,000 - 200,000 ohms/ft
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel (64 per barrier)
Connections:
Red = Power, Black = Signal, Shield =
Ground
Содержание OPW SiteSentinel Integra 100
Страница 16: ...Doc M1800 Rev 06 Page 16 of 101 www opwglobal com 2 6 Petro Net Over Ethernet Option with VSmart ...
Страница 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Страница 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Страница 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Страница 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Страница 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Страница 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Страница 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Страница 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Страница 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Страница 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...