OPW Installation, Operation and Maintenance Manual, Page 43                  Executive Order VR-401-B 

 

OPW 301 SERIES EMERGENCY VENT 
INSTALLATION INSTRUCTIONS: 
 
Step 1: 

Apply pipe dope to pipe threads.  Pipe dope to be a 
non-hardening, gasoline resistant pipe thread seal 
compound.

 

Note: Do not use Teflon tape. 
 
Step 2: 

Thread the OPW 301 Series Emergency Vent onto 
the pipe nipple.  Tighten using a pipe wrench or 
strap wrench.  
 

Step 3: 

Check to be sure the lid raises and lowers once 
installation has been completed.  Make sure the seal 
is completely seated in the machined groove in the 
body. 
 
 

Operation and Maintenance:  

Periodic maintenance is required for all OPW 301 
Emergency Vents.  If the vent has been activated, 
inspect the seal for damage or debris and clean the 
seal and sealing area.  The lid should be raised and 
lowered once a year to assure no binding or 
obstruction.  Inspect the seal for damage or debris 
and clean the seal and sealing area.  

 

 

 