CX9230
Recipro/Scroll(Chiller) Controller
REV DATE
R20180403
USERS MANUAL
- 17 -
4.9 COMPRESSOR
4.9 COMPRESSOR (CX9230-M2 Model)
4.10 FUNCTION
NO
Parameter
Default Min.
Max.
View
Access
Description
4 0161
COMPRES.
INSTALL
1=Use
0
1
FREE
MASTER 0=Unuse
1=Use
4 0162
COMP RUN
DELAY
3Sec
0
10
FREE
MASTER Even if comp. is at starting condition,
compressor will not be started during
restart delay time after comp. turns OFF
(To prevent frequent ON/Off of compressor)
4 0163
COMP RE-RUN TIME
60Sec
0
9999
FREE
SERVICE
4 0165
PUMP-DOWN TIME
0Sec
0
999
FREE
SERVICE Input pump down time of compressor
4 0166
PUMP-DOWN PRESS
0bar
-1.0
99.9
FREE
MASTER Input pump down pressure
4 0168
CONDENSOR PRESS
24.0bar -1.0
99.9
SERVICE SERVICE
NO
Parameter
Default Min.
Max.
View
Access
Description
4 0169
COMP1 USE
1=Use
0
1
FREE
MASTER 0=Unuse 1=Use
4 0170
COMP2 USE
1=Use
0
1
FREE
MASTER 0=Unuse 1=Use
4 0171
RUN/STOP SOURCE
0=Off
0
1
FREE
SERVICE 0=Off 1=On
NO
Parameter
Default
Min. Max. View
Access Description
4 0181
RUN/STOP SOURCE
1=Local 0
4
FREE
SERVICE 0=Both:
Use both local mode and remote mode
1=Local: Control by keypad
2=Remote: Control by digital input(ID8)
3=Comm.: Control by Comm.
4=Schedule: Time set at schedule menu
4 0182
CONTROL SOURCE
0=Temp 0
1
FREE
SERVICE 0=Temperature: Control by temperature
standard
1=Lpress: Control by press. standard
(support at CX9240)
4 0184
AUX.SENSOR RATIO
0%
0
100
FREE
SERVICE
4 0185
POWER RETURN
1=Use
0
1
FREE
SERVICE 0=Unuse, 1=Use
4 0187
PUMP Low Temp.
On
4.0
-50.0 150
FREE
SERVICE
4 0189
PUMP ON DELAY
3Sec
0
9999 FREE
SERVICE
4 0190
PUMP STOP DELAY
10Sec
0
9999 FREE
SERVICE