dormakaba 8900 EMF Installation Instructions
08281000
03-2020
8900 EMF
5
Track
Wire connections
2.4.1 Slide wiring connection cover to allow access to
wire connections.
2.4.2 Determine power supply and unit voltage type:
24 VAC, 24VDC.
CAUTION! DO NOT CONNECT 120VAC TO A 24 VOLT
UNIT TYPE!
2.4.3 Connect power supply wires to terminal block as
shown (Terminal Block can be removed for easier
wiring).
NOTE: Be sure to use ground screw for power supply
ground wire when supplying 120 VAC.
2.4.4 Slide wiring connection cover over wire
connections.
2.4.5 Insert cover into track, align end cap in end of
track.
2.4.6 Install remaining screw as shown using 1/4-20x2”
metal or No.14 x 2-3/4” wood screw.
2.3.1
8900T and 8900DE:
•
Install the wire access plugs toward latch edge
of door.
•
Use (2) 1/4-20x2” metal or (2) No.14 x 2-3/4”
wood screws.
•
Route wires from frame through appropriate
wire access hole in track, being careful not to
pinch wires during installation.
8900T and 8900DE
Wire
connection
cover
8900PT
Hinge
CL
2.3.2
8900PT:
•
Install PT track to soffit with wire access plugs
toward hinge.
•
Install with (1) 1/4-20x1-1/4” combo screw and
(1) 1/4-20x2” metal or (1) No.14 x 2-3/4” wood
screw as shown.
•
Route wires from frame through appropriate
wire access hole in track, being careful not to
pinch wires during installation. (DO NOT
INSTALL END CAP ON HINGE SIDE IN THIS
STEP.)
End cap
End cap
2.3 Secure track to frame
Fig.3
End cap
2.4 Set up wire connections
Fig.4
CAUTION! IMPROPER
VOLTAGE TO UNIT
WILL RESULT IN
DAMAGE TO UNIT
AND VOID
WARRANTY.
NOTE: ALL WIRING
MUST COMPLY WITH
NATIONAL, STATE
AND LOCAL
ELECTRICAL CODES.
Terminal
block
Solenoid wires
Incoming power
connection
UL listed alarm
control unit or
smoke detector
NOTE: THIS CONNECTION IS NOT POLARITY
DEPENDENT. TERMINAL BLOCK 18 awg MAX.
UL listed alarm
control unit or
smoke detector