TS 99 FLR-K EN 2-5

Installation arrangement of the FLR-K for

applications where the bottom surface of the ceiling

is less than 1m above the bottom edge of the lintel

on one or both sides of the door. 

        1)

        1)

        1)

        1)

        1)

See separate sheet for associated connection

diagrams.

If the bottom surface of the ceiling is more than 1m

above the bottom edge of the lintel on one or both

sides of the door, two ceiling-mounted smoke

detectors must be installed in addition to the lintel-

mounted detector (FLR-K) 

                1)

                1)

                1)

                1)

                1)

See separate sheet for associated connection

diagrams.

Drill fixing points for closer and slide channel using

TS 99 FLR-K template or as per dimensioned

drawing.

Drill holes of 12 mm dia. for the 230V AC power

cable (by others) and of 10 mm for connection to the

TS 99 FL, manual pushbutton and any required

ceiling-mounted detectors. Install cabling.

Fix junction box.

Fix mounting backplate.

Fix closer to the mounting backplate.

Ensure that the cable is located in the mounting
backplate groove and that it remains undamaged.

Connect 24V DC supply cable to the junction box

terminal   .

Connect interconnecting cable  .

Connect the internal cable to the connector of the

electro-hydraulic hold-open device  .

Fit arm at an angle of approx. 10° from the door leaf

and tighten fixing screw

LH (ISO 6) handing:

Fix FLR-K unit.

RH (ISO 5) handing:

Rotate slide channel 180° 

.

Fix FLR-K unit.

Close valve for adjusting closing speed  , and open

door approx. 45°  .

Push arm towards slide channel   and connect to

slide block  .

Adjust spring strength (closing force).

Adjust closing speed 180° - 0°  .

Adjust latching action 7° - 0°  .

Fit end caps   .

Break out spindle recess tab   and fit clip-on cover  .

Ensure that the cables are not damaged in this
process.

Clip on DORMA logo badge  .

FIXING INSTRUCTIONS

Technical Data TS 99 FLR-K

Input:

230 V AC +10%/-15%

120 mA/28 VA / 50 Hz

Output:

 24 V DC /460 mA / 11 W

Type of Protection: IP 30

Protection class:

II

Smoke switch:

24 V DC/50 mA

Temperature:

-20°C/+60°C

Technical Data, Hold-open Device (EMF)

Operating  voltage:

24 V DC

Power input:

2 W

Duty factor:

100 % continuous duty

• Work on electrical equipment and systems may

only be performed by properly trained specialist
personnel.

• Check to ensure that the line power supply (230V

AC) has been disconnected and is no longer live.

• IA 10 A/B miniature circuit breaker must be

provided in the supply circuit.  This can also be
used as the isolator for disconnecting the FLR-K
and making it dead.

• The power cable leading to the FLR-K must be

properly secured to ensure effective strain relief.

• The power cable (NYM) conductor cross section

should be not greater than max. 1.5 mm

2

  The PE

conductor is not electrically utilised.  The terminal
(PE) should, however, be used where a PE
conductor is provided.

• Fire/smoke detectors controlling hold-open

systems must not be used to actuate any further
alarm devices (e.g. fire alarm transmission
systems).

            1)

• If the optional alarm module is installed, the cable

connecting it to the smoke switch must be led over
and across the measurement chamber in order to
ensure that smoke penetration is in no way
hindered.

• According to the guidelines for hold-open systems

issued by the Institute of Building Technology,
Berlin, it must be possible to release every hold-
open device by manual means. If free-swing door
closers are used, release must be initiated by a
manual pushbutton. The manual release
pushbutton used for this must be red and carry the
inscription “Close Door”.  The pushbutton must be
in the immediate vicinity of the door (barrier) and
must not be concealed when the door (barrier) is
open.

Integral lintel-mounted smoke detector.

Electro-magnetic hold-open device.

Ceiling-mounted smoke detector.

DORMA HT manual release pushbutton for hold-

open devices.

a

b

1

2

3

4

5

6

7

8

9a

9b

10

11

12

13

14

1 )

1 )

1 )

1 )

1 )

Guidelines for hold-open systems issued by the Institute for Building Technology,
Berlin. In countries outside Germany, consult local regulations.

WN 057718  45532

   08/09

Содержание TS 99 FLR-K

Страница 1: ...aten TS 99 FLR K Eingang 230 V AC 10 15 120 mA 28 VA 50 Hz Ausgang 24 V DC 460 mA 11 W Schutzart IP 30 Schutzklasse II Rauchschalter 24 V DC 50 mA Temperatur 20 C 60 C Technische Daten EMF Betriebsspannung 24 V DC Leistungsaufnahme 2 W Einschaltdauer 100 ED Arbeiten an Elektroanlagen dürfen nur von geschulten Fachkräften ausgeführt werden Überprüfen ob die bauseitige Stromzuführung 230 VAC spannun...

Страница 2: ...tung erfolgt über den Reset Taster Betriebs anzeige leuchtet grün Endkappenblenden aufclipsen Markierte Aussparung an der Verkleidung ausbrechen Verkleidungen aufclipsen 15 16 17 18 19 20 21 Änderungen vorbehalten Funktionsprüfung Anwendungs und Sicherheitshinweise auf dem Prüfgas und Sicherheitsdatenblatt beachten Türflügel öffnen Prüfgas Hekatron 918 5 aus ca 10 15 cm Entfernung in Richtung Rauc...

Страница 3: ...otection IP 30 Protection class II Smoke switch 24 V DC 50 mA Temperature 20 C 60 C Technical Data Hold open Device EMF Operating voltage 24 V DC Power input 2 W Duty factor 100 continuous duty Work on electrical equipment and systems may only be performed by properly trained specialist personnel Check to ensure that the line power supply 230V AC has been disconnected and is no longer live IA 10 A...

Страница 4: ...heet Open door leaf Spray test gas Hekatron 918 5 from a distance of approx 10 15cm towards the smoke chamber After approx 4 6 short bursts the status display should switch to alarm red If the FLR K is equipped with the RS smoke alarm module option an audible alarm is also sounded The hold open device is tripped and released and the door closes Status display flashes green as soon as there is no l...

Отзывы: